Analog process data
In the delivery state the process data are shown in two's complement form (-1dez corresponds to 0xFFFF). The feature object 0x8020:02 (channel 1), 0x8030:02 (channel 2), 0x8040:02 (channel 3), 0x8050:02 (channel 4) can be used to select other presentation types (e.g. magnitude sign format, absolute value).
|
Output value |
Output voltage | |
|---|---|---|
|
hexadecimal |
decimal | |
|
0x8001 |
-32769 |
-10 V |
|
0xC001 |
-16383 |
-5 V |
|
0x0000 |
0 |
0 V |
|
0x3FFF |
+16383 |
+5 V |
|
0x7FFF |
+32767 |
+10 V |