ELM324x Overview measuring ranges
|
Measurement |
Connection |
FSV |
Mode |
Maximum value/ value range |
|---|---|---|---|---|
|
Temperature RTD |
2/3/4-wire |
5 kΩ |
Legacy
|
Depending on type
|
|
2 kΩ | ||||
|
500 Ω | ||||
|
200 Ω | ||||
|
4-wire |
50 Ω | |||
|
Resistance |
2/3/4-wire |
5 kΩ |
Extended |
0 Ω…5.368 kΩ |
|
Legacy |
0…5 kΩ | |||
|
2 kΩ |
Extended |
0 Ω…2.147 kΩ | ||
|
Legacy |
0…2 kΩ | |||
|
500 Ω |
Extended |
0 Ω…536.8 Ω | ||
|
Legacy |
0…500 Ω | |||
|
200 Ω |
Extended |
0 Ω…214.7 Ω | ||
|
Legacy |
0…200 Ω | |||
|
50 Ω |
Extended |
0 Ω…53.68 Ω | ||
|
Legacy |
0…50 Ω | |||
|
4-wire |
50 Ω |
Extended |
0 Ω…53.68 Ω | |
|
Legacy |
0…50 Ω |
![]() | Unused (unwired) channels Unused (unwired) channels must be set to "none" within CoE object 0x80n0:01 PAI Settings/Interface to disable the internal circuitry. |