EL9550, EL9550-0010, EL9550-0012 - Technical data

Technical data

EL9550

EL9550-0010

EL9550‑0012

Function

Surge filter system and field supply

Nominal voltage

24 V (-15 %/+20 %)

Surge filter field supply

yes

Surge filter system supply

yes

Current carrying capacity
field supply

≤ 10 A

up to 10 A, field+system in total 10 A

≤ 10 A

Current carrying capacity
system supply

≤ 1.5 A
(from hardware version 03)

up to 10 A, field+system in total 10 A

≤ 10 A

Diagnostics

-

yes

-

Message to E-bus

-

yes

-

Shield connection

-

E-bus current consumption

-

typ. 40 mA

-

Bit width in process image

-

4

-

Electrical connection to mounting rail

-

Electrical isolation

500 V (E-bus/field voltage)

Renewed infeed

yes

Connection facility to additional power contact

1

Side by side mounting on EtherCAT Terminals with power contact

yes

Side by side mounting on EtherCAT Terminals without power contact

yes

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Configuration

no address or configuration settings required

Weight

approx. 50 g

Permissible ambient temperature range during operation

-25 °C ... +60 °C

0 °C ... +55 °C

Permissible ambient temperature range during storage

-40 °C ... +85 °C

-25 °C ... +85 °C

Permissible relative air humidity

95 %, no condensation

Installation

on 35 mm mounting rail, conforms to EN 60715

Enhanced mechanical load capacity

yes, see Installation instructions for terminals with enhanced mechanical load capacity

-

-

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable, see chapter Mounting of passive terminals

Markings*

CE, UKCA EAC

Approvals*

cULus, CCC, ATEX, IECEx, cFMus,

DNV

-

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc

cFMus

Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc