EL9181, EL9182, EL9183 - Introduction and Technical Data

Potential distribution terminal, HD housing

EL9181, EL9182, EL9183 - Introduction and Technical Data 1:
EL9181
EL9181, EL9182, EL9183 - Introduction and Technical Data 2:
EL9182
EL9181, EL9182, EL9183 - Introduction and Technical Data 3:
EL9183

The potential distribution terminals EL9181, EL9182 and EL9183 provide 16 terminal points for potential distribution and enable the voltage to be picked up without further terminal blocks or wiring. The power contacts are fed through to the next terminal without connecting to the terminal points.

The HD EtherCAT Terminals (High Density) with increased packing density feature 16 connection points in the housing of a 12 mm EtherCAT Terminal. The conductors can be connected without tools in the case of solid wires using a direct plug-in technique

Technical data

Technical Data

EL9181

EL9182

EL9183

Technology

Potential distribution terminal

Number of separate potentials

2

8

1

Terminal points per potential

8

2

16

Nominal voltage

≤ 60 VDC

Current load

max. 10 A

Current consumption from E-Bus

-

E-bus looped through

yes

Power contacts looped through

yes (2 power contacts)

Diagnosis

-

Message to E-Bus

-

PE contact

no

Renewed infeed

-

Connection facility to additional power contact

-

Side by side mounting on Bus Terminals with power contact

yes

Side by side mounting on Bus Terminals without power contact

-

Bit width in the process image

0

Electrical connection to mounting rail

-

Electrical connection to power contacts

-

Electrical isolation

500 V (E-bus/field potential)

Configuration

no address or configuration settings

Conductor types

solid wire, stranded wire and ferrule

Conductor connection

solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver

Rated cross-section

solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm²

Weight

approx. 60 g

Permissible ambient temperature range (during operation)

-25°C ... +60°C (extended temperature range)

Permissible ambient temperature range (during storage)

-40°C ... +85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Enhanced mechanical load capacity

yes, see Installation instructions for enhanced mechanical load capacity

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC resistance burst / ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable, see chapter "Mounting of Passive Terminals"

Approvals / markings*

CE, cULus, UKCA, EAC, ATEX, IECEx,

CE, cULus, UKCA, EAC,

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex nA IIC T4 Gc

IECEx

Ex nA IIC T4 Gc

Connection EL9181

Terminal point

Meaning

Indication

No.

1 - 8

1 - 8

Terminal points 1 - 8 are connected internally

9 - 16

9 - 16

Terminal points 9 - 16 are connected internally

Connection EL9182

Terminal point

Meaning

Indication

No.

1, 9

1 + 9

Terminal points 1 + 9 are connected internally

2, 10

2 + 10

Terminal points 2 +10 are connected internally

3, 11

3 + 11

Terminal points 3 + 11 are connected internally

4, 12

4 + 12

Terminal points 4 + 12 are connected internally

5, 13

5 + 13

Terminal points 5 + 13 are connected internally

6, 14

6 + 14

Terminal points 6 + 14 are connected internally

7, 15

7 + 15

Terminal points 7 + 15 are connected internally

8, 16

8 + 16

Terminal points 8 + 16 are connected internally

Connection EL9183

Terminal point

Meaning

Indication

No.

1 - 16

1 - 16

Terminal points 1 - 16 are connected internally