EL9576 - Technical data

Technical data

EL9576

Technology

Brake chopper

Rated voltage

up to 72 V

Capacitance

155 µF

Ripple current

10 A in continuous operation

Internal resistance

< 10 mΩ

Overvoltage protection

Standard 50 V, parameterizable via CoE data

Recommended ballast resistor

ZB8110**)

Overvoltage control range

Standard 1 V, parameterizable via CoE data

Ballast resistor clock rate

load-dependent, max. 100 µs, 2-point control

Electrical isolation

1500 V

Diagnostics

Temperature on the PCB

Message to E-bus

Data for the switch-on behavior of the resistor as well as current and supply voltage

PE contact

no

Screen connection

-

E-Bus current consumption

typ. 80 mA

Power consumption from power contacts

0 mA

Bit width in process image

88 bit

Electrical connection to mounting rail

-

Addition to EtherCAT Terminals with power contact

yes, left side without PE

Addition to EtherCAT Terminals without power contact

yes

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Configuration

Via CoE data

Weight

approx. 90 g

permissible ambient temperature range during operation

0 °C ... +55 °C

permissible ambient temperature range during storage

-25 °C ... +85 °C

permissible relative humidity

95 %, no condensation

Mounting

on 35 mm mounting rail conforms to EN 60715

Increased mechanical load capacity

yes, see also Installation instructions for terminals with increased mechanical load capacity

Vibration/shock resistance

according to EN 60068-2-6/EN 60068-2-27,

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

Any, see Section Mounting

Marking / Approval*)

CE, EAC, UKCA
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).

**) depending on the application, a larger resistor may be necessary