Start types

The Positioning interface offers different types of positioning. The following table contains all commands supported; these are divided into four groups.

Supported “Start types” of the “Positioning interface”

Name

Command

Group

Description

ABSOLUTE

0x0001

Standard

Absolute positioning to a specified target position

RELATIVE

0x0002

Relative positioning to a calculated target position; a specified position difference is added to the current position

ENDLESS_PLUS

0x0003

Endless travel in the positive direction of rotation (direct specification of a speed)

ENDLESS_MINUS

0x0004

Endless travel in the negative direction of rotation (direct specification of a speed)

ADDITIVE

0x0006

Additive positioning to a calculated target position; a specified position difference is added to the last target position

ABSOLUTE_CHANGE

0x1001

Standard Ext.

Dynamic change of the target position during a travel command to a new absolute position

RELATIVE_CHANGE

0x1002

Dynamic change of the target position during a travel command to a new relative position (the current changing position value is used here also)

ADDITIVE_CHANGE

0x1006

Dynamic change of the target position during a travel command to a new additive position (the last target position is used here)

MODULO_SHORT

0x0105

Modulo

Modulo positioning along the shortest path to the modulo position (positive or negative), calculated by the "Modulo factor" (Index 0x8020:0E)

MODULO_SHORT_EXT

0x0115

Modulo positioning along the shortest path to the modulo position; the "Modulo tolerance window" (Index 0x8020:0F) is ignored

MODULO_PLUS

0x0205

Modulo positioning in the positive direction of rotation to the calculated modulo position

MODULO_PLUS_EXT

0x0215

Modulo positioning in the positive direction of rotation to the calculated modulo position; the "Modulo tolerance window" is ignored

MODULO_MINUS

0x0305

Modulo positioning in the negative direction of rotation to the calculated modulo position

MODULO_MINUS_EXT

0x0315

Modulo positioning in the negative direction of rotation to the calculated modulo position; the "Modulo tolerance window" is ignored

MODULO_CURRENT

0x0405

Modulo positioning in the last direction of rotation to the calculated modulo position

MODULO_CURRENT_EXT

0x0415

Modulo positioning in the last direction of rotation to the calculated modulo position; the "Modulo tolerance window" is ignored

CALI_PLC_CAM

0x6000

Calibration

Start a calibration with cam (digital inputs)

CALI_HW_SYNC

0x6100

Start a calibration with cam and HW sync pulse (C-track)

SET_CALIBRATION

0x6E00

Manually set the terminal to "Calibrated"

SET_CALIBRATION_AUTO

0x6E01

Automatically set the terminal to "Calibrated" on the first rising edge on "Enable"

CLEAR_CALIBRATION

0x6F00

Manually delete the calibration

ABSOLUTE

The absolute positioning represents the simplest positioning case. A position B is specified and travelled to from the start point A.

Start types 1:Fig.168: Absolute positioning

RELATIVE

In relative positioning, the user specifies a position delta S, which is added to the current position A, producing the target position B.

Start types 2:Fig.169: Relative positioning

ENDLESS_PLUS / ENDLESS_MINUS

The two start types ENDLESS_PLUS and ENDLESS_MINUS offer the possibility in the Positioning Interface to specify a direct motor velocity in order to travel endlessly in the positive or negative direction with the specified accelerations.

Start types 3:Fig.170: Endless travel

ADDITIVE

For additive positioning, the position delta S specified by the user is added to the target position E used for the last travel command in order to calculate the target position B.

This kind of positioning resembles the relative positioning, but there is a difference. If the last travel command was completed successfully, the new target position is the same. If there was an error, however, be it that the motor entered a stall state or an Emergency stop was triggered, the current position is arbitrary and not foreseeable. The user now has the advantage that he can use the last target position for the calculation of the following target position.

Start types 4:Fig.171: Additive positioning

ABSOLUTE_CHANGE / RELATIVE_CHANGE / ADDITIVE_CHANGE

These three kinds of positioning are completely identical to those described above. The important difference thereby is that the user uses these commands during an active travel command in order to dynamically specify a new target position.

The same rules and conditions apply as to the “normal” start types. ABSOLUTE_CHANGE and ADDITIVE_CHANGE are unique in the calculation of the target position i.e. in absolute positioning an absolute position is specified and in additive positioning a position delta is added to the momentarily active target position.

Notice

Caution when using the RELATIVE_CHANGE positioning

The change by means of RELATIVE_CHANGE must be used with caution, since the current position of the motor is also used here as the start position. Due to propagation delays in the system, the position indicated in the PDO never corresponds to the actual position of the motor! Therefore a difference to the desired target position always results in the calculation of the transferred position delta.

Start types 5:

Time of the change of the target position

A change of the target position cannot take place at an arbitrary point in time. If the calculation of the output parameters shows that the new target position cannot be readily reached, the command is rejected by the terminal and the Command rejected bit is set. This is the case, for example, at standstill (since the terminal expects a standard positioning here) and in the acceleration phase (since at this point the braking time cannot be calculated yet).

CALI_PLC_CAM / CALI_HW_SYNC / SET_CALIBRATION / SET_CALIBRATION_AUTO / CLEAR_CALIBRATION:

The simplest calibration case is calibration by cam only (connected to one digital input).

Here, the motor travels in the 1st step with velocity 1 (Index 0x8020:09) in direction 1 (Index 0x8021:13) towards the cam. Subsequently, in the 2nd step, it travels with velocity 2 (Index 0x8020:0A) in direction 2 (Index 0x8021:14) away from the cam. After the In-Target timeout"(Index 0x8020:0C) has elapsed, the calibration position (Index 0x8020:08) is taken on by the terminal as the current position.

Notice

Observe the switching hysteresis of the cam switch

With this simple calibration it must be noted that the position detection of the cam is only exact to a certain degree. The digital inputs are not interrupt-controlled and are "only" polled. The internal propagation delays may therefore result in a system-related position difference.

Start types 6:Fig.172: Calibration with cam

For a more precise calibration, an HW sync pulse (C-track) is used in addition to the cam. This calibration proceeds in exactly the same way as described above, up to the point at which the motor travels away from the cam. The travel is not stopped immediately; instead, the sync pulse is awaited. Subsequently, the In-Target timeout runs down again and the calibration position is taken on by the terminal as the current position.

Start types 7:Fig.173: Calibration with cam and C-track

If calibration by hardware is not possible due to the circumstances of the application, the user can also set the Calibrated bit manually or automatically. The manual setting or deletion takes place with the commands SET_CALIBRATION and CLEAR_CALIBRATION.

It is simpler, however, if the standard start types (Index 0x8021:01) are set to SET_CALIBRATION_AUTO. The Calibrated bit will now be set automatically by the first rising edge on Enable. The command is conceived only for this purpose; therefore, it does not make sense to use it via the synchronous data exchange.