EL6821 – connection
Terminal point | No. | Connection for |
|---|---|---|
+24 V | 1 | Power supply connection +24 V |
Input 1 | 2 | Digital input 1 |
DA + | 3 | DALI-2 bus + (internally connected to terminal point 7) |
DA - | 4 | DALI-2 bus - (internally connected to terminal point 8) |
0 V | 5 | Power supply connection 0 V |
Input 2 | 6 | Digital input 2 |
DA + | 7 | DALI-2 bus + (internally connected to terminal point 3) |
DA - | 8 | DALI-2 bus - (internally connected to terminal point 4) |
Connection instructions
|
Priority of the digital inputs
The digital Input 1 and Input 2 have priority over automatic control through the PLC program. If the digital inputs are operated, other PLC-controlled DALI commands are blocked. For release, a positive edge must be applied to the “bResetInactiveProcessImage” input of the “FB_EL6821Communication” function block (see documentation TwinCAT 3 | PLC libraries: Tc3_DALI). Alternatively, the priority rule can also be changed via the setting in TwinCAT 3 (do not lock process image).
Behavior of the digital inputs
The behavior of the digital inputs "Input 1" and "Input 2" can be changed via the library function blocks or via the settings in TwinCAT 3. To support commissioning, the following default behavior is assigned in the delivery state.
Signal | Broadcast | Action | Comment |
|---|---|---|---|
Rising edge at DI1 | 00hex | Turns OFF all control gears (without fading). | Factory setting |
Rising edge at DI2 | 05hex | Switches all control gears to maximum brightness. | Factory setting |