EL6761 - LEDs and connection
 Fig.4: EL6761
Fig.4: EL6761LED
| LED | Color | Meaning | |
|---|---|---|---|
| Run | green | These LEDs indicate the terminal's operating state: | |
| off | State of the EtherCAT State Machine: INIT = initialization of the terminal or BOOTSTRAP = function for terminal firmware updates | ||
| flashing | State of the EtherCAT State Machine: PREOP = function for mailbox communication and different default settings set | ||
| single flash | State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks. | ||
| on | State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible | ||
| Com | Displays the communication to the ISO 15118 module | ||
| green | off | No communication to the CME active | |
| on | Communication to the CME active | ||
| flashing | Firmware update of the CME active | ||
| yellow | flashing | File is read or written via FoE | |
| red | off | No error or reset active | |
| on | Error present or reset active | ||
| flashing | - | ||
| State | Displays the status of communication with the EV | ||
| green | off | No EV connected | |
| on | Charge stop/pause | ||
| flashing | Pre-Charge/Charge/Welding | ||
| single flash | Pause (DC only - ISO 15118) | ||
| yellow | off | No EV connected | |
| on | High level: Initialization phase (DC only - ISO 15118) | ||
| flashing | Authentication/parameter phase | ||
| single flash | Isolation phase | ||
| red | off | - | |
| on | - | ||
| flashing | Error present | ||
Connections "X1"
| Connection | Description | Function | 
|---|---|---|
| PP | Proximity pin | Presence control pin - DC: presence recognition + evaluation of the plug lock - AC: optional (fixed cable) Type2: - DC: optional - AC: measures the current coded in the cable (if cable is not fixed) | 
| CP | Control Pilot | Communication pin | 
| 
 | Ground | Functional earth (FE), see Example circuit EL6761 | 
| n.c. | Not connected | Not connected | 
 "Ground"
 "Ground"