TwinCAT System Manager

The TwinCAT System Manager tool is used for the configuration of the EL6752 DeviceNet® master/slave terminal. The System Manager provides a representation of the number of programs of the TwinCat PLC systems, the configuration of the axis control and of the connected I/O channels as a structure, and organizes the mapping of the data traffic.

TwinCAT System Manager 1:
Fig.29: TwinCAT System Manager logo

For applications without TwinCAT PLC or NC, the TwinCAT System Manager Tool configures the programming interfaces for a wide range of application programs:

System Manager – Features

Configuration by means of the TwinCAT System Manager

The procedure and the configuration facilities in the System Manager are described below.

EL6752 DeviceNet® master terminal
EL6752-0010 - DeviceNet® slave terminal

EL6752 DeviceNet® master terminal

Append device

The terminal can be appended to the I/O configuration either using the "Device search" routine in the TwinCAT System Manager or by manually selecting the "DeviceNet® Master EL6752, EtherCAT" from the possible DeviceNet® devices (Fig. Appending the device "DeviceNet slave EL6752, EtherCAT"). A right-click brings up the following context menu for selection:

TwinCAT System Manager 2:
Fig.30: Appending the device "DeviceNet master EL6752, EtherCAT"

"EL6752" tab

Click on the "Device EL6752" in the TwinCAT tree and then on the EL6752 tab:

TwinCAT System Manager 3:
Fig.31: "EL6752" tab

EtherCAT 

Terminal ID in the terminal network.

MAC-ID

Each DeviceNet® device - master included - requires a unique station number referred to as MAC ID (Medium Access Identifier) - value range: 0...63.

Baud rate

Baud rate setting: 125 kbaud, 250 kbaud or 500 kbaud

Cycle time

Displays the cycle time of the corresponding highest priority task. The display is updated when the mapping is generated.

IO-Cycle Time

Setting of the cycle time for the I/O connections. This value is the standard value for newly inserted boxes.

Watchdog time

Time until triggering of the watchdog

Search... 

This function searches for all existing channels of the EL6752 and the desired one can be selected.

Check configuration

In preparation.

Firmware 

Shows the current firmware version of the EL6752.

Firmware Update...

Updates the EL6752 firmware. Attention: The TwinCAT System must be stopped for this function.

“ADS” tab

TwinCAT System Manager 4:
Fig.32: “ADS” tab

The EL6752 is an ADS device with its own net ID, which can be changed here. All ADS services (diagnostics, acyclical communication) associated with the EL6752 device must address the card via this NetID.

”Box States" tab

TwinCAT System Manager 5:
Fig.33: "Box states" tab

Displays an overview of all current box statuses.

EL6752-0010 – DeviceNet® slave terminal

In the system configuration tree structure right-click on I/O Devices and “Append device” to open the selection list of supported fieldbus cards.
Select EL6752-0010 CANopenSlave. TwinCAT searches for the terminal and displays the memory addresses and slots it finds. Select the required address and confirm.

TwinCAT System Manager 6:
Fig.34: Appending the device "DeviceNet slave EL6752, EtherCAT"

Right-click on "Device (EL6752-0010)" to insert the box for the EL6752-0010:

TwinCAT System Manager 7:
Fig.35: Appending the box "DeviceNet slave EL6752, EtherCAT"

Selecting the I/O device for the EL6752-0010 in the tree structure opens a dialog with various configuration options:

“EL6752-0010” tab

TwinCAT System Manager 8:
Fig.36: “EL6752-0010” tab

EtherCAT

Terminal ID in the terminal network.

MAC-ID

Each DeviceNet® device requires a unique station number referred to as MAC ID (Medium Access Identifier) - value range: 0...63.

Baud rate

The baud rate is set here.

Cycle time

Displays the cycle time of the corresponding highest priority task. The display is updated when the mapping is generated. The network variables are updated with the cycle of this task.

Watchdog time

Time until the watchdog is triggered

Search...

Searches for all available EL6752-0010 channels, from which the required channel can be selected. In the case of an FC5102 both channels A and B appear. These behave in logical terms like two FC5101 cards.

Firmware

Displays the current EL6752-0010 firmware version.

Firmware Update...

Updates the EL6752-0010 firmware. Attention: The TwinCAT System must be stopped for this function.

“ADS” tab

TwinCAT System Manager 9:
Fig.37: “ADS” tab

The EL6752-0010 is an ADS device with its own net ID, which can be changed here. All ADS services (diagnostics, acyclic communication) associated with the EL6752-0010 device must address the card via this NetID. Additional ADS Net IDs can be entered for addressing subordinate ADS devices (e.g. an additional fieldbus card in the same PC) via the card.

"(Online) DPRAM" tab

Read access to the DPRAM of the card is provided for diagnostic purposes.

Box EL6752-0010 slave

A box "EL6752-0010 (DeviceNet slave)" is created automatically. Further parameters have to be set:

Box EL6752-0010 tab:

TwinCAT System Manager 10:
Fig.38: "General" tab, Box EL6752-0010

DeviceNet® IO modes

The EL6752-0010 supports the DeviceNet® modes cyclic polling, change of state / cyclic and bit strobe. The IO modes can be selected according to the DeviceNet® specification.

The DeviceNet® IO mode cyclic polling is the default selection for the EL6752-0010:

IO mode

Input data length / bytes

Output data length / bytes

Polling

0 - 255

0 - 255

Change of State

0 - 255

0 - 255

Cyclic

0 - 255

0 - 255

Bit strobe

1 bit

0-8

Polling / Change of State (COS) / Cyclic

The cyclic polling mode is characterized by cyclic polling of the IO data by the master. The change of state mode is characterized by event-oriented sending of IO data. In cyclic mode the IO data are sent cyclically based on the communication parameters configured by the master. Since the communication settings are specified through the master no further settings are possible. Further information on the modes can be found in section DeviceNet® Communication. The settings are identical for these modes.

The input and output data lengths are pre-initialized to 8 byte each:

TwinCAT System Manager 11:
Fig.39: Pre-initialized input and output data lengths in polling mode

According to needs and the application, further input or output data can be appended by right-clicking (Fig. Adding further variables). Any data type can be selected:

TwinCAT System Manager 12:
Fig.40: Adding further variables

The data length is converted to a byte stream according to the DeviceNet® specification and displayed in the tab for the corresponding connection:

TwinCAT System Manager 13:
Fig.41: "Connection" tab showing connection type "Polling" and input and output parameters
TwinCAT System Manager 14:

Maximum output data length

The maximum data length per data direction is 255 bytes.

The indicated input and output data lengths must be configured for the corresponding DeviceNet® master.

Bit strobe

The IO mode bit strobe involves an 8-byte command from the master to the slaves. For each possible address/MAC ID (DeviceNet address space: 64) 1 bit of user data is allocated.  The maximum length of the response message from the slave is 8 bytes. It is sent to the master immediately when the bit strobe command is received.

TwinCAT System Manager 15:
Fig.42: Display of output parameters in the TwinCAT tree for connection type "Bit strobe"
TwinCAT System Manager 16:

Maximum output data length

The maximum output data length is 8 bytes. The input data length is fixed.

Since the communication settings are specified through the master no further settings are possible.