| Technical data | EL6711-0010 | ||||
|---|---|---|---|---|---|
| Fieldbus | CC-Link | ||||
| CC-Link version | V 1.10 (or V 1.00) or V 2.00 | ||||
| Function | Slave | ||||
| Number of fieldbus channels | 1 | ||||
| Max. process data size | According to CC-Link V 2.00, see table | ||||
| Communication speed | 156 kbps | 625 kbps | 2.5 Mbps | 5 Mbps | 10 Mbps | 
| Max. total cable length | 1200 m | 900 m | 400 m | 160 m | 100 m | 
| Bus interface | 1 x open-style connector, 5-pin | ||||
| Hardware diagnostics | Status LEDs | ||||
| Power supply for the electronics | internal | ||||
| Current consumption via E-bus | typ. 150mA | ||||
| Electrical isolation | 500 V (E-Bus / CC-Link) | ||||
| Configuration | Via the EtherCAT master | ||||
| Weight | approx. 70 g | ||||
| Permissible ambient temperature at operation | 0...+55 °C | ||||
| Permissible ambient temperature for storage | -25...+85 °C | ||||
| Permissible relative air humidity | 95 % no condensation | ||||
| Dimensions (W x H x D) | 24 mm x 100 mm x 52 mm | ||||
| on 35 mm mounting rail conforms to EN 60715 | |||||
| Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | ||||
| EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | ||||
| Protect. rating | IP20 | ||||
| Installation position | see notice | ||||
| Approvals / markings* | CE, UKCA, EAC | ||||
*) Real applicable approvals/markings see type plate on the side (product marking).