TwinSAFE SC process data EL6224-0090

The process data size and the process data themselves can be selected under the Process Image tab in TwinCAT. The process data depend on the connected IO-Link device and have to be adjusted accordingly. The corresponding information can be found in the sensor-specific data sheet. By default, a 16-bit unsigned integer is mapped with byte offset 0 from IO-Link channel 1.

TwinSAFE SC process data EL6224-0090 1:
EL6224-0090, process data image (default)

The process data can be adjusted to user requirements by selecting the Edit button in the dialog Configure I/O element(s).

The following rule applies for process data mapping:

0x60ab:0c

a = IO-Link port

b = data type integer

c = byte offset

0 = IO-Link port 1

0 = data type bit

01 = offset byte 0

1 = IO-Link port 2

1 = UDINT

02 = offset byte 1

2 = IO-Link port 3

2 = DINT

03 = offset byte 2

3 = IO-Link port 4

3 = UINT

…..

 

4 = INT

0p = offset byte p-1

Examples for index mapping:

0x6004:01 => IO-Link port 1, data type INT, offset byte 0

0x6011:01 => IO-Link port 2, data type UDINT, offset byte 0

TwinSAFE SC process data EL6224-0090 2:

TwinSAFE SC objects

The TwinSAFE SC objects of the EL6224-0090 are listed in the chapter Objects TwinSAFE Single Channel (EL6224-0090).