Information data
Index 10F3 Diagnosis History
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
10F3:0 |
Diagnosis History |
Maximum subindex |
UINT8 |
RO |
0x15 (21dec) |
10F3:01 |
Maximum Messages |
reserved |
UINT8 |
RO |
0x00 (0dec) |
10F3:02 |
Newest Message |
reserved |
UINT8 |
RO |
0x00 (0dec) |
10F3:03 |
Newest Acknowledged Message |
reserved |
UINT8 |
RW |
0x00 (0dec) |
10F3:04 |
New Messages Available |
reserved |
BOOLEAN |
RO |
0x00 (0dec) |
10F3:05 |
Flags |
reserved |
UINT16 |
RW |
0x0000 (0dec) |
10F3:06 - 15 |
Diagnosis Message 001 - 016 |
reserved |
OCTET-STRING[20] |
RO |
{0} |
Index 10F8 Actual Time Stamp
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
10F8:0 |
Actual Time Stamp |
Time stamp |
UINT64 |
RO |
|
Index 9pp0 ASI Info Data Slave (for 00 ≤ pp ≤ 1F; slave 0 to slave 31)
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
9pp0:0 |
ASI Info Data Slave |
Maximum subindex |
UINT8 |
RO |
0x29 (41dec) |
9pp0:01 |
ASI Address |
Address of the AS-i slave (actual configuration) |
UINT16 |
RO |
0x0000 (0dec) |
9pp0:20 |
IO Configuration (A-Slave) |
Read I/O ID (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:21 |
ID Code (A-Slave) |
Read standard ID code (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:22 |
Extended ID Code 1 (A-Slave) |
Read extended ID code 1 (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:23 |
Extended ID Code 2 (A-Slave) |
Read extended ID code 2 (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:24 |
Parameter (A-Slave) |
Response of the slave to the activation parameter command (see object 0x8pp0:24) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:25 |
IO Configuration (B-slave) |
Read I/O ID (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:26 |
ID code (B-slave) |
Read standard ID code (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:27 |
Extended ID Code 1 (B-slave) |
Read extended ID code 1 (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:28 |
Extended ID Code 2 (B-slave) |
Read extended ID code 2 (actual configuration) |
UINT8 |
RO |
0x00 (0dec) |
9pp0:29 |
Parameter (B-slave) |
Response of the slave to the activation parameter command (see object 0x8pp0:29) |
UINT8 |
RO |
0x00 (0dec) |