Object description - standard objects
Standard objects
Index 1000 Device type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1000:0 |
Device type |
Device type of the EtherCAT slave: The Lo-Word contains the CoE profile used (5001). |
UINT32 |
RO |
0x18381389 (406328201dec) |
Index 1008 Device name
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1008:0 |
Device name |
Device name of the EtherCAT slave |
STRING |
RO |
EL6201 |
Index 1009 Hardware version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1009:0 |
Hardware version |
Hardware version of the EtherCAT slave |
STRING |
RO |
|
Index 100A Software version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
100A:0 |
Software version |
Firmware version of the EtherCAT slave |
STRING |
RO |
01 |
Index 1010 Store parameters
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1010:0 |
Store parameters |
reserved |
UINT8 |
RO |
0x01 (1dec) |
|
1010:01 |
SubIndex 001 |
reserved |
UINT32 |
RW |
0x00000000 (0dec) |
Index 1018 Identity
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1018:0 |
Identity |
Information for identifying the slave |
UINT8 |
RO |
0x04 (4dec) |
|
1018:01 |
Vendor ID |
Vendor ID of the EtherCAT slave |
UINT32 |
RO |
0x00000002 (2dec) |
|
1018:02 |
Product code |
Product code of the EtherCAT slave |
UINT32 |
RO |
0x18393052 (406401106dec) |
|
1018:03 |
Revision |
Revision number of the EtherCAT slave; the low word (bit 0-15) indicates the special terminal number, the high word (bit 16-31) refers to the device description |
UINT32 |
RO |
0x00000000 (0dec) |
|
1018:04 |
Serial number |
Serial number of the EtherCAT slave; the low byte (bit 0-7) of the low word contains the year of production, the high byte (bit 8-15) of the low word contains the week of production, the high word (bit 16-31) is 0 |
UINT32 |
RO |
0x00000000 (0dec) |
Index 10F0 Backup parameter handling
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
10F0:0 |
Backup parameter handling |
Information for standardized loading and saving of backup entries |
UINT8 |
RO |
0x01 (1dec) |
|
10F0:01 |
Checksum |
Checksum across all backup entries of the EtherCAT slave |
UINT32 |
RO |
0x00000000 (0dec) |
Index 10F2 Backup parameter storage
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
10F2:0 |
Backup parameter storage |
|
OCTET-STRING[4] |
RW |
{0} |
Index 1601 ASI RxPDO-Map Analog Outputs Slave 1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1601:0 |
ASI RxPDO-Map Analog Outputs Slave 1 |
PDO Mapping RxPDO 2 |
UINT8 |
RO |
0x08 (8dec) |
|
1601:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7010:01, 16 |
|
1601:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7010:02, 16 |
|
1601:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7010:03, 16 |
|
1601:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7010:04, 16 |
|
1601:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7010:05, 16 |
|
1601:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7010:06, 16 |
|
1601:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7010:07, 16 |
|
1601:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7010 (ASI Analog Outputs Slave 1 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7010:08, 16 |
Index 1602 ASI RxPDO-Map Analog Outputs Slave 2
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1602:0 |
ASI RxPDO-Map Analog Outputs Slave 2 |
PDO Mapping RxPDO 3 |
UINT8 |
RO |
0x08 (8dec) |
|
1602:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7020:01, 16 |
|
1602:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7020:02, 16 |
|
1602:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7020:03, 16 |
|
1602:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7020:04, 16 |
|
1602:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7020:05, 16 |
|
1602:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7020:06, 16 |
|
1602:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7020:07, 16 |
|
1602:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7020 (ASI Analog Outputs Slave 2 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7020:08, 16 |
Index 1603 ASI RxPDO-Map Analog Outputs Slave 3
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1603:0 |
ASI RxPDO-Map Analog Outputs Slave 3 |
PDO Mapping RxPDO 4 |
UINT8 |
RO |
0x08 (8dec) |
|
1603:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7030:01, 16 |
|
1603:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7030:02, 16 |
|
1603:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7030:03, 16 |
|
1603:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7030:04, 16 |
|
1603:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7030:05, 16 |
|
1603:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7030:06, 16 |
|
1603:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7030:07, 16 |
|
1603:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7030 (ASI Analog Outputs Slave 3 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7030:08, 16 |
Index 1604 ASI RxPDO-Map Analog Outputs Slave 4
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1604:0 |
ASI RxPDO-Map Analog Outputs Slave 4 |
PDO Mapping RxPDO 5 |
UINT8 |
RO |
0x08 (8dec) |
|
1604:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7040:01, 16 |
|
1604:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7040:02, 16 |
|
1604:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7040:03, 16 |
|
1604:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7040:04, 16 |
|
1604:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7040:05, 16 |
|
1604:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7040:06, 16 |
|
1604:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7040:07, 16 |
|
1604:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7040 (ASI Analog Outputs Slave 4 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7040:08, 16 |
Index 1605 ASI RxPDO-Map Analog Outputs Slave 5
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1605:0 |
ASI RxPDO-Map Analog Outputs Slave 5 |
PDO Mapping RxPDO 6 |
UINT8 |
RO |
0x08 (8dec) |
|
1605:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7050:01, 16 |
|
1605:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7050:02, 16 |
|
1605:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7050:03, 16 |
|
1605:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7050:04, 16 |
|
1605:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7050:05, 16 |
|
1605:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7050:06, 16 |
|
1605:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7050:07, 16 |
|
1605:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7050 (ASI Analog Outputs Slave 5 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7050:08, 16 |
Index 1606 ASI RxPDO-Map Analog Outputs Slave 6
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1606:0 |
ASI RxPDO-Map Analog Outputs Slave 6 |
PDO Mapping RxPDO 7 |
UINT8 |
RO |
0x08 (8dec) |
|
1606:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7060:01, 16 |
|
1606:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7060:02, 16 |
|
1606:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7060:03, 16 |
|
1606:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7060:04, 16 |
|
1606:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7060:05, 16 |
|
1606:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7060:06, 16 |
|
1606:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7060:07, 16 |
|
1606:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7060 (ASI Analog Outputs Slave 6 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7060:08, 16 |
Index 1607 ASI RxPDO-Map Analog Outputs Slave 7
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1607:0 |
ASI RxPDO-Map Analog Outputs Slave 7 |
PDO Mapping RxPDO 8 |
UINT8 |
RO |
0x08 (8dec) |
|
1607:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7070:01, 16 |
|
1607:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7070:02, 16 |
|
1607:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7070:03, 16 |
|
1607:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7070:04, 16 |
|
1607:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7070:05, 16 |
|
1607:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7070:06, 16 |
|
1607:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7070:07, 16 |
|
1607:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7070 (ASI Analog Outputs Slave 7 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7070:08, 16 |
Index 1608 ASI RxPDO-Map Analog Outputs Slave 8
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1608:0 |
ASI RxPDO-Map Analog Outputs Slave 8 |
PDO Mapping RxPDO 9 |
UINT8 |
RO |
0x08 (8dec) |
|
1608:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7080:01, 16 |
|
1608:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7080:02, 16 |
|
1608:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7080:03, 16 |
|
1608:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7080:04, 16 |
|
1608:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7080:05, 16 |
|
1608:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7080:06, 16 |
|
1608:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7080:07, 16 |
|
1608:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7080 (ASI Analog Outputs Slave 8 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7080:08, 16 |
Index 1609 ASI RxPDO-Map Analog Outputs Slave 9
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1609:0 |
ASI RxPDO-Map Analog Outputs Slave 9 |
PDO Mapping RxPDO 10 |
UINT8 |
RO |
0x08 (8dec) |
|
1609:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7090:01, 16 |
|
1609:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7090:02, 16 |
|
1609:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7090:03, 16 |
|
1609:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7090:04, 16 |
|
1609:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7090:05, 16 |
|
1609:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7090:06, 16 |
|
1609:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7090:07, 16 |
|
1609:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7090 (ASI Analog Outputs Slave 9 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7090:08, 16 |
Index 160A ASI RxPDO-Map Analog Outputs Slave 10
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160A:0 |
ASI RxPDO-Map Analog Outputs Slave 10 |
PDO Mapping RxPDO 11 |
UINT8 |
RO |
0x08 (8dec) |
|
160A:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70A0:01, 16 |
|
160A:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70A0:02, 16 |
|
160A:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70A0:03, 16 |
|
160A:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70A0:04, 16 |
|
160A:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70A0:05, 16 |
|
160A:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70A0:06, 16 |
|
160A:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70A0:07, 16 |
|
160A:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x70A0 (ASI Analog Outputs Slave 10 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70A0:08, 16 |
Index 160B ASI RxPDO-Map Analog Outputs Slave 11
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160B:0 |
ASI RxPDO-Map Analog Outputs Slave 11 |
PDO Mapping RxPDO 12 |
UINT8 |
RO |
0x08 (8dec) |
|
160B:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70B0:01, 16 |
|
160B:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70B0:02, 16 |
|
160B:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70B0:03, 16 |
|
160B:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70B0:04, 16 |
|
160B:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70B0:05, 16 |
|
160B:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70B0:06, 16 |
|
160B:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70B0:07, 16 |
|
160B:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x70B0 (ASI Analog Outputs Slave 11 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70B0:08, 16 |
Index 160C ASI RxPDO-Map Analog Outputs Slave 12
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160C:0 |
ASI RxPDO-Map Analog Outputs Slave 12 |
PDO Mapping RxPDO 13 |
UINT8 |
RO |
0x08 (8dec) |
|
160C:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70C0:01, 16 |
|
160C:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70C0:02, 16 |
|
160C:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70C0:03, 16 |
|
160C:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70C0:04, 16 |
|
160C:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70C0:05, 16 |
|
160C:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70C0:06, 16 |
|
160C:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70C0:07, 16 |
|
160C:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x70C0 (ASI Analog Outputs Slave 12 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70C0:08, 16 |
Index 160D ASI RxPDO-Map Analog Outputs Slave 13
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160D:0 |
ASI RxPDO-Map Analog Outputs Slave 13 |
PDO Mapping RxPDO 14 |
UINT8 |
RO |
0x08 (8dec) |
|
160D:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70D0:01, 16 |
|
160D:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70D0:02, 16 |
|
160D:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70D0:03, 16 |
|
160D:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70D0:04, 16 |
|
160D:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70D0:05, 16 |
|
160D:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70D0:06, 16 |
|
160D:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70D0:07, 16 |
|
160D:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x70D0 (ASI Analog Outputs Slave 13 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70D0:08, 16 |
Index 160E ASI RxPDO-Map Analog Outputs Slave 14
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160E:0 |
ASI RxPDO-Map Analog Outputs Slave 14 |
PDO Mapping RxPDO 15 |
UINT8 |
RO |
0x08 (8dec) |
|
160E:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70E0:01, 16 |
|
160E:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70E0:02, 16 |
|
160E:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70E0:03, 16 |
|
160E:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70E0:04, 16 |
|
160E:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70E0:05, 16 |
|
160E:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70E0:06, 16 |
|
160E:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70E0:07, 16 |
|
160E:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x70E0 (ASI Analog Outputs Slave 14 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70E0:08, 16 |
Index 160F ASI RxPDO-Map Analog Outputs Slave 15
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
160F:0 |
ASI RxPDO-Map Analog Outputs Slave 15 |
PDO Mapping RxPDO 16 |
UINT8 |
RO |
0x08 (8dec) |
|
160F:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70F0:01, 16 |
|
160F:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x70F0:02, 16 |
|
160F:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70F0:03, 16 |
|
160F:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x70F0:04, 16 |
|
160F:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70F0:05, 16 |
|
160F:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x70F0:06, 16 |
|
160F:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70F0:07, 16 |
|
160F:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x70F0 (ASI Analog Outputs Slave 15 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x70F0:08, 16 |
Index 1610 ASI RxPDO-Map Analog Outputs Slave 16
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1610:0 |
ASI RxPDO-Map Analog Outputs Slave 16 |
PDO Mapping RxPDO 17 |
UINT8 |
RO |
0x08 (8dec) |
|
1610:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7100:01, 16 |
|
1610:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7100:02, 16 |
|
1610:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7100:03, 16 |
|
1610:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7100:04, 16 |
|
1610:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7100:05, 16 |
|
1610:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7100:06, 16 |
|
1610:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7100:07, 16 |
|
1610:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7100 (ASI Analog Outputs Slave 16 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7100:08, 16 |
Index 1611 ASI RxPDO-Map Analog Outputs Slave 17
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1611:0 |
ASI RxPDO-Map Analog Outputs Slave 17 |
PDO Mapping RxPDO 18 |
UINT8 |
RO |
0x08 (8dec) |
|
1611:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7110:01, 16 |
|
1611:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7110:02, 16 |
|
1611:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7110:03, 16 |
|
1611:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7110:04, 16 |
|
1611:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7110:05, 16 |
|
1611:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7110:06, 16 |
|
1611:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7110:07, 16 |
|
1611:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7110 (ASI Analog Outputs Slave 17 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7110:08, 16 |
Index 1612 ASI RxPDO-Map Analog Outputs Slave 18
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1612:0 |
ASI RxPDO-Map Analog Outputs Slave 18 |
PDO Mapping RxPDO 19 |
UINT8 |
RO |
0x08 (8dec) |
|
1612:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7120:01, 16 |
|
1612:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7120:02, 16 |
|
1612:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7120:03, 16 |
|
1612:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7120:04, 16 |
|
1612:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7120:05, 16 |
|
1612:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7120:06, 16 |
|
1612:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7120:07, 16 |
|
1612:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7120 (ASI Analog Outputs Slave 18 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7120:08, 16 |
Index 1613 ASI RxPDO-Map Analog Outputs Slave 19
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1613:0 |
ASI RxPDO-Map Analog Outputs Slave 19 |
PDO Mapping RxPDO 20 |
UINT8 |
RO |
0x08 (8dec) |
|
1613:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7130:01, 16 |
|
1613:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7130:02, 16 |
|
1613:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7130:03, 16 |
|
1613:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7130:04, 16 |
|
1613:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7130:05, 16 |
|
1613:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7130:06, 16 |
|
1613:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7130:07, 16 |
|
1613:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7130 (ASI Analog Outputs Slave 19 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7130:08, 16 |
Index 1614 ASI RxPDO-Map Analog Outputs Slave 20
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1614:0 |
ASI RxPDO-Map Analog Outputs Slave 20 |
PDO Mapping RxPDO 21 |
UINT8 |
RO |
0x08 (8dec) |
|
1614:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7140:01, 16 |
|
1614:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7140:02, 16 |
|
1614:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7140:03, 16 |
|
1614:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7140:04, 16 |
|
1614:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7140:05, 16 |
|
1614:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7140:06, 16 |
|
1614:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7140:07, 16 |
|
1614:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7140 (ASI Analog Outputs Slave 20 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7140:08, 16 |
Index 1615 ASI RxPDO-Map Analog Outputs Slave 21
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1615:0 |
ASI RxPDO-Map Analog Outputs Slave 21 |
PDO Mapping RxPDO 22 |
UINT8 |
RO |
0x08 (8dec) |
|
1615:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7150:01, 16 |
|
1615:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7150:02, 16 |
|
1615:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7150:03, 16 |
|
1615:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7150:04, 16 |
|
1615:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7150:05, 16 |
|
1615:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7150:06, 16 |
|
1615:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7150:07, 16 |
|
1615:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7150 (ASI Analog Outputs Slave 21 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7150:08, 16 |
Index 1616 ASI RxPDO-Map Analog Outputs Slave 22
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1616:0 |
ASI RxPDO-Map Analog Outputs Slave 22 |
PDO Mapping RxPDO 23 |
UINT8 |
RO |
0x08 (8dec) |
|
1616:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7160:01, 16 |
|
1616:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7160:02, 16 |
|
1616:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7160:03, 16 |
|
1616:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7160:04, 16 |
|
1616:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7160:05, 16 |
|
1616:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7160:06, 16 |
|
1616:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7160:07, 16 |
|
1616:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7160 (ASI Analog Outputs Slave 22 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7160:08, 16 |
Index 1617 ASI RxPDO-Map Analog Outputs Slave 23
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1617:0 |
ASI RxPDO-Map Analog Outputs Slave 23 |
PDO Mapping RxPDO 24 |
UINT8 |
RO |
0x08 (8dec) |
|
1617:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7170:01, 16 |
|
1617:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7170:02, 16 |
|
1617:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7170:03, 16 |
|
1617:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7170:04, 16 |
|
1617:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7170:05, 16 |
|
1617:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7170:06, 16 |
|
1617:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7170:07, 16 |
|
1617:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7170 (ASI Analog Outputs Slave 23 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7170:08, 16 |
Index 1618 ASI RxPDO-Map Analog Outputs Slave 24
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1618:0 |
ASI RxPDO-Map Analog Outputs Slave 24 |
PDO Mapping RxPDO 25 |
UINT8 |
RO |
0x08 (8dec) |
|
1618:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7180:01, 16 |
|
1618:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7180:02, 16 |
|
1618:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7180:03, 16 |
|
1618:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7180:04, 16 |
|
1618:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7180:05, 16 |
|
1618:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7180:06, 16 |
|
1618:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7180:07, 16 |
|
1618:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7180 (ASI Analog Outputs Slave 24 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7180:08, 16 |
Index 1619 ASI RxPDO-Map Analog Outputs Slave 25
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1619:0 |
ASI RxPDO-Map Analog Outputs Slave 25 |
PDO Mapping RxPDO 26 |
UINT8 |
RO |
0x08 (8dec) |
|
1619:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7190:01, 16 |
|
1619:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x7190:02, 16 |
|
1619:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7190:03, 16 |
|
1619:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x7190:04, 16 |
|
1619:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7190:05, 16 |
|
1619:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x7190:06, 16 |
|
1619:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7190:07, 16 |
|
1619:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7190 (ASI Analog Outputs Slave 25 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x7190:08, 16 |
Index 161A ASI RxPDO-Map Analog Outputs Slave 26
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
161A:0 |
ASI RxPDO-Map Analog Outputs Slave 26 |
PDO Mapping RxPDO 27 |
UINT8 |
RO |
0x08 (8dec) |
|
161A:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71A0:01, 16 |
|
161A:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71A0:02, 16 |
|
161A:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71A0:03, 16 |
|
161A:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71A0:04, 16 |
|
161A:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71A0:05, 16 |
|
161A:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71A0:06, 16 |
|
161A:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71A0:07, 16 |
|
161A:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x71A0 (ASI Analog Outputs Slave 26 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71A0:08, 16 |
Index 161B ASI RxPDO-Map Analog Outputs Slave 27
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
161B:0 |
ASI RxPDO-Map Analog Outputs Slave 27 |
PDO Mapping RxPDO 28 |
UINT8 |
RO |
0x08 (8dec) |
|
161B:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71B0:01, 16 |
|
161B:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71B0:02, 16 |
|
161B:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71B0:03, 16 |
|
161B:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71B0:04, 16 |
|
161B:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71B0:05, 16 |
|
161B:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71B0:06, 16 |
|
161B:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71B0:07, 16 |
|
161B:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x71B0 (ASI Analog Outputs Slave 27 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71B0:08, 16 |
Index 161C ASI RxPDO-Map Analog Outputs Slave 28
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
161C:0 |
ASI RxPDO-Map Analog Outputs Slave 28 |
PDO Mapping RxPDO 29 |
UINT8 |
RO |
0x08 (8dec) |
|
161C:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71C0:01, 16 |
|
161C:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71C0:02, 16 |
|
161C:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71C0:03, 16 |
|
161C:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71C0:04, 16 |
|
161C:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71C0:05, 16 |
|
161C:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71C0:06, 16 |
|
161C:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71C0:07, 16 |
|
161C:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x71C0 (ASI Analog Outputs Slave 28 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71C0:08, 16 |
Index 161D ASI RxPDO-Map Analog Outputs Slave 29
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
161D:0 |
ASI RxPDO-Map Analog Outputs Slave 29 |
PDO Mapping RxPDO 30 |
UINT8 |
RO |
0x08 (8dec) |
|
161D:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71D0:01, 16 |
|
161D:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71D0:02, 16 |
|
161D:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71D0:03, 16 |
|
161D:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71D0:04, 16 |
|
161D:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71D0:05, 16 |
|
161D:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71D0:06, 16 |
|
161D:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71D0:07, 16 |
|
161D:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x71D0 (ASI Analog Outputs Slave 29 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71D0:08, 16 |
Index 161E ASI RxPDO-Map Analog Outputs Slave 30
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
161E:0 |
ASI RxPDO-Map Analog Outputs Slave 30 |
PDO Mapping RxPDO 31 |
UINT8 |
RO |
0x08 (8dec) |
|
161E:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71E0:01, 16 |
|
161E:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71E0:02, 16 |
|
161E:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71E0:03, 16 |
|
161E:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71E0:04, 16 |
|
161E:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71E0:05, 16 |
|
161E:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71E0:06, 16 |
|
161E:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71E0:07, 16 |
|
161E:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x71E0 (ASI Analog Outputs Slave 30 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71E0:08, 16 |
Index 161F ASI RxPDO-Map Analog Outputs Slave 31
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
161F:0 |
ASI RxPDO-Map Analog Outputs Slave 31 |
PDO Mapping RxPDO 32 |
UINT8 |
RO |
0x08 (8dec) |
|
161F:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71F0:01, 16 |
|
161F:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x71F0:02, 16 |
|
161F:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71F0:03, 16 |
|
161F:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x71F0:04, 16 |
|
161F:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71F0:05, 16 |
|
161F:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x71F0:06, 16 |
|
161F:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71F0:07, 16 |
|
161F:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x71F0 (ASI Analog Outputs Slave 31 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x71F0:08, 16 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:0 |
ASI RxPDO-Map Outputs Device |
PDO Mapping RxPDO 65 |
UINT8 |
RO |
0xF8 (248dec) |
|
1640:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x01 (Slave 1 Outputs__Slave 1A, DO0)) |
UINT32 |
RO |
0xF700:01, 1 |
|
1640:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x02 (Slave 1 Outputs__Slave 1A, DO1)) |
UINT32 |
RO |
0xF700:02, 1 |
|
1640:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x03 (Slave 1 Outputs__Slave 1A, DO2)) |
UINT32 |
RO |
0xF700:03, 1 |
|
1640:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x04 (Slave 1 Outputs__Slave 1A, DO3)) |
UINT32 |
RO |
0xF700:04, 1 |
|
1640:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x05 (Slave 1 Outputs__Slave 1B, DO0)) |
UINT32 |
RO |
0xF700:05, 1 |
|
1640:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x06 (Slave 1 Outputs__Slave 1B, DO1)) |
UINT32 |
RO |
0xF700:06, 1 |
|
1640:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x07 (Slave 1 Outputs__Slave 1B, DO2)) |
UINT32 |
RO |
0xF700:07, 1 |
|
1640:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x08 (Slave 1 Outputs__Slave 1B, DO3)) |
UINT32 |
RO |
0xF700:08, 1 |
|
1640:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x09 (Slave 2 Outputs__Slave 2A, DO0)) |
UINT32 |
RO |
0xF700:09, 1 |
|
1640:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x0A (Slave 2 Outputs__Slave 2A, DO1)) |
UINT32 |
RO |
0xF700:0A, 1 |
|
1640:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x0B (Slave 2 Outputs__Slave 2A, DO2)) |
UINT32 |
RO |
0xF700:0B, 1 |
|
1640:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x0C (Slave 2 Outputs__Slave 2A, DO3)) |
UINT32 |
RO |
0xF700:0C, 1 |
|
1640:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x0D (Slave 2 Outputs__Slave 2B, DO0)) |
UINT32 |
RO |
0xF700:0D, 1 |
|
1640:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x0E (Slave 2 Outputs__Slave 2B, DO1)) |
UINT32 |
RO |
0xF700:0E, 1 |
|
1640:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x0F (Slave 2 Outputs__Slave 2B, DO2)) |
UINT32 |
RO |
0xF700:0F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:10 |
SubIndex 016 |
16. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x10 (Slave 2 Outputs__Slave 2B, DO3)) |
UINT32 |
RO |
0xF700:10, 1 |
|
1640:11 |
SubIndex 017 |
17. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x11 (Slave 3 Outputs__Slave 3A, DO0)) |
UINT32 |
RO |
0xF700:11, 1 |
|
1640:12 |
SubIndex 018 |
18. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x12 (Slave 3 Outputs__Slave 3A, DO1)) |
UINT32 |
RO |
0xF700:12, 1 |
|
1640:13 |
SubIndex 019 |
19. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x13 (Slave 3 Outputs__Slave 3A, DO2)) |
UINT32 |
RO |
0xF700:13, 1 |
|
1640:14 |
SubIndex 020 |
20. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x14 (Slave 3 Outputs__Slave 3A, DO3)) |
UINT32 |
RO |
0xF700:14, 1 |
|
1640:15 |
SubIndex 021 |
21. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x15 (Slave 3 Outputs__Slave 3B, DO0)) |
UINT32 |
RO |
0xF700:15, 1 |
|
1640:16 |
SubIndex 022 |
22. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x16 (Slave 3 Outputs__Slave 3B, DO1)) |
UINT32 |
RO |
0xF700:16, 1 |
|
1640:17 |
SubIndex 023 |
23. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x17 (Slave 3 Outputs__Slave 3B, DO2)) |
UINT32 |
RO |
0xF700:17, 1 |
|
1640:18 |
SubIndex 024 |
24. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x18 (Slave 3 Outputs__Slave 3B, DO3)) |
UINT32 |
RO |
0xF700:18, 1 |
|
1640:19 |
SubIndex 025 |
25. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x19 (Slave 4 Outputs__Slave 4A, DO0)) |
UINT32 |
RO |
0xF700:19, 1 |
|
1640:1A |
SubIndex 026 |
26. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x1A (Slave 4 Outputs__Slave 4A, DO1)) |
UINT32 |
RO |
0xF700:1A, 1 |
|
1640:1B |
SubIndex 027 |
27. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x1B (Slave 4 Outputs__Slave 4A, DO2)) |
UINT32 |
RO |
0xF700:1B, 1 |
|
1640:1C |
SubIndex 028 |
28. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x1C (Slave 4 Outputs__Slave 4A, DO3)) |
UINT32 |
RO |
0xF700:1C, 1 |
|
1640:1D |
SubIndex 029 |
29. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x1D (Slave 4 Outputs__Slave 4B, DO0)) |
UINT32 |
RO |
0xF700:1D, 1 |
|
1640:1E |
SubIndex 030 |
30. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x1E (Slave 4 Outputs__Slave 4B, DO1)) |
UINT32 |
RO |
0xF700:1E, 1 |
|
1640:1F |
SubIndex 031 |
31. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x1F (Slave 4 Outputs__Slave 4B, DO2)) |
UINT32 |
RO |
0xF700:1F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:20 |
SubIndex 032 |
32. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x20 (Slave 4 Outputs__Slave 4B, DO3)) |
UINT32 |
RO |
0xF700:20, 1 |
|
1640:21 |
SubIndex 033 |
33. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x21 (Slave 5 Outputs__Slave 5A, DO0)) |
UINT32 |
RO |
0xF700:21, 1 |
|
1640:22 |
SubIndex 034 |
34. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x22 (Slave 5 Outputs__Slave 5A, DO1)) |
UINT32 |
RO |
0xF700:22, 1 |
|
1640:23 |
SubIndex 035 |
35. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x23 (Slave 5 Outputs__Slave 5A, DO2)) |
UINT32 |
RO |
0xF700:23, 1 |
|
1640:24 |
SubIndex 036 |
36. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x24 (Slave 5 Outputs__Slave 5A, DO3)) |
UINT32 |
RO |
0xF700:24, 1 |
|
1640:25 |
SubIndex 037 |
37. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x25 (Slave 5 Outputs__Slave 5B, DO0)) |
UINT32 |
RO |
0xF700:25, 1 |
|
1640:26 |
SubIndex 038 |
38. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x26 (Slave 5 Outputs__Slave 5B, DO1)) |
UINT32 |
RO |
0xF700:26, 1 |
|
1640:27 |
SubIndex 039 |
39. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x27 (Slave 5 Outputs__Slave 5B, DO2)) |
UINT32 |
RO |
0xF700:27, 1 |
|
1640:28 |
SubIndex 040 |
40. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x28 (Slave 5 Outputs__Slave 5B, DO3)) |
UINT32 |
RO |
0xF700:28, 1 |
|
1640:29 |
SubIndex 041 |
41. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x29 (Slave 6 Outputs__Slave 6A, DO0)) |
UINT32 |
RO |
0xF700:29, 1 |
|
1640:2A |
SubIndex 042 |
42. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x2A (Slave 6 Outputs__Slave 6A, DO1)) |
UINT32 |
RO |
0xF700:2A, 1 |
|
1640:2B |
SubIndex 043 |
43. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x2B (Slave 6 Outputs__Slave 6A, DO2)) |
UINT32 |
RO |
0xF700:2B, 1 |
|
1640:2C |
SubIndex 044 |
44. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x2C (Slave 6 Outputs__Slave 6A, DO3)) |
UINT32 |
RO |
0xF700:2C, 1 |
|
1640:2D |
SubIndex 045 |
45. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x2D (Slave 6 Outputs__Slave 6B, DO0)) |
UINT32 |
RO |
0xF700:2D, 1 |
|
1640:2E |
SubIndex 046 |
46. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x2E (Slave 6 Outputs__Slave 6B, DO1)) |
UINT32 |
RO |
0xF700:2E, 1 |
|
1640:2F |
SubIndex 047 |
47. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x2F (Slave 6 Outputs__Slave 6B, DO2)) |
UINT32 |
RO |
0xF700:2F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:30 |
SubIndex 048 |
48. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x30 (Slave 6 Outputs__Slave 6B, DO3)) |
UINT32 |
RO |
0xF700:30, 1 |
|
1640:31 |
SubIndex 049 |
49. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x31 (Slave 7 Outputs__Slave 7A, DO0)) |
UINT32 |
RO |
0xF700:31, 1 |
|
1640:32 |
SubIndex 050 |
50. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x32 (Slave 7 Outputs__Slave 7A, DO1)) |
UINT32 |
RO |
0xF700:32, 1 |
|
1640:33 |
SubIndex 051 |
51. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x33 (Slave 7 Outputs__Slave 7A, DO2)) |
UINT32 |
RO |
0xF700:33, 1 |
|
1640:34 |
SubIndex 052 |
52. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x34 (Slave 7 Outputs__Slave 7A, DO3)) |
UINT32 |
RO |
0xF700:34, 1 |
|
1640:35 |
SubIndex 053 |
53. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x35 (Slave 7 Outputs__Slave 7B, DO0)) |
UINT32 |
RO |
0xF700:35, 1 |
|
1640:36 |
SubIndex 054 |
54. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x36 (Slave 7 Outputs__Slave 7B, DO1)) |
UINT32 |
RO |
0xF700:36, 1 |
|
1640:37 |
SubIndex 055 |
55. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x37 (Slave 7 Outputs__Slave 7B, DO2)) |
UINT32 |
RO |
0xF700:37, 1 |
|
1640:38 |
SubIndex 056 |
56. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x38 (Slave 7 Outputs__Slave 7B, DO3)) |
UINT32 |
RO |
0xF700:38, 1 |
|
1640:39 |
SubIndex 057 |
57. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x39 (Slave 8 Outputs__Slave 8A, DO0)) |
UINT32 |
RO |
0xF700:39, 1 |
|
1640:3A |
SubIndex 058 |
58. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x3A (Slave 8 Outputs__Slave 8A, DO1)) |
UINT32 |
RO |
0xF700:3A, 1 |
|
1640:3B |
SubIndex 059 |
59. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x3B (Slave 8 Outputs__Slave 8A, DO2)) |
UINT32 |
RO |
0xF700:3B, 1 |
|
1640:3C |
SubIndex 060 |
60. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x3C (Slave 8 Outputs__Slave 8A, DO3)) |
UINT32 |
RO |
0xF700:3C, 1 |
|
1640:3D |
SubIndex 061 |
61. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x3D (Slave 8 Outputs__Slave 8B, DO0)) |
UINT32 |
RO |
0xF700:3D, 1 |
|
1640:3E |
SubIndex 062 |
62. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x3E (Slave 8 Outputs__Slave 8B, DO1)) |
UINT32 |
RO |
0xF700:3E, 1 |
|
1640:3F |
SubIndex 063 |
63. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x3F (Slave 8 Outputs__Slave 8B, DO2)) |
UINT32 |
RO |
0xF700:3F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:40 |
SubIndex 064 |
64. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x40 (Slave 8 Outputs__Slave 8B, DO3)) |
UINT32 |
RO |
0xF700:40, 1 |
|
1640:41 |
SubIndex 065 |
65. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x41 (Slave 9 Outputs__Slave 9A, DO0)) |
UINT32 |
RO |
0xF700:41, 1 |
|
1640:42 |
SubIndex 066 |
66. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x42 (Slave 9 Outputs__Slave 9A, DO1)) |
UINT32 |
RO |
0xF700:42, 1 |
|
1640:43 |
SubIndex 067 |
67. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x43 (Slave 9 Outputs__Slave 9A, DO2)) |
UINT32 |
RO |
0xF700:43, 1 |
|
1640:44 |
SubIndex 068 |
68. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x44 (Slave 9 Outputs__Slave 9A, DO3)) |
UINT32 |
RO |
0xF700:44, 1 |
|
1640:45 |
SubIndex 069 |
69. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x45 (Slave 9 Outputs__Slave 9B, DO0)) |
UINT32 |
RO |
0xF700:45, 1 |
|
1640:46 |
SubIndex 070 |
70. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x46 (Slave 9 Outputs__Slave 9B, DO1)) |
UINT32 |
RO |
0xF700:46, 1 |
|
1640:47 |
SubIndex 071 |
71. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x47 (Slave 9 Outputs__Slave 9B, DO2)) |
UINT32 |
RO |
0xF700:47, 1 |
|
1640:48 |
SubIndex 072 |
72. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x48 (Slave 9 Outputs__Slave 9B, DO3)) |
UINT32 |
RO |
0xF700:48, 1 |
|
1640:49 |
SubIndex 073 |
73. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x49 (Slave 10 Outputs__Slave 10A, DO0)) |
UINT32 |
RO |
0xF700:49, 1 |
|
1640:4A |
SubIndex 074 |
74. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x4A (Slave 10 Outputs__Slave 10A, DO1)) |
UINT32 |
RO |
0xF700:4A, 1 |
|
1640:4B |
SubIndex 075 |
75. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x4B (Slave 10 Outputs__Slave 10A, DO2)) |
UINT32 |
RO |
0xF700:4B, 1 |
|
1640:4C |
SubIndex 076 |
76. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x4C (Slave 10 Outputs__Slave 10A, DO3)) |
UINT32 |
RO |
0xF700:4C, 1 |
|
1640:4D |
SubIndex 077 |
77. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x4D (Slave 10 Outputs__Slave 10B, DO0)) |
UINT32 |
RO |
0xF700:4D, 1 |
|
1640:4E |
SubIndex 078 |
78. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x4E (Slave 10 Outputs__Slave 10B, DO1)) |
UINT32 |
RO |
0xF700:4E, 1 |
|
1640:4F |
SubIndex 079 |
79. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x4F (Slave 10 Outputs__Slave 10B, DO2)) |
UINT32 |
RO |
0xF700:4F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:50 |
SubIndex 080 |
80. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x50 (Slave 10 Outputs__Slave 10B, DO3)) |
UINT32 |
RO |
0xF700:50, 1 |
|
1640:51 |
SubIndex 081 |
81. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x51 (Slave 11 Outputs__Slave 11A, DO0)) |
UINT32 |
RO |
0xF700:51, 1 |
|
1640:52 |
SubIndex 082 |
82. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x52 (Slave 11 Outputs__Slave 11A, DO1)) |
UINT32 |
RO |
0xF700:52, 1 |
|
1640:53 |
SubIndex 083 |
83. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x53 (Slave 11 Outputs__Slave 11A, DO2)) |
UINT32 |
RO |
0xF700:53, 1 |
|
1640:54 |
SubIndex 084 |
84. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x54 (Slave 11 Outputs__Slave 11A, DO3)) |
UINT32 |
RO |
0xF700:54, 1 |
|
1640:55 |
SubIndex 085 |
85. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x55 (Slave 11 Outputs__Slave 11B, DO0)) |
UINT32 |
RO |
0xF700:55, 1 |
|
1640:56 |
SubIndex 086 |
86. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x56 (Slave 11 Outputs__Slave 11B, DO1)) |
UINT32 |
RO |
0xF700:56, 1 |
|
1640:57 |
SubIndex 087 |
87. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x57 (Slave 11 Outputs__Slave 11B, DO2)) |
UINT32 |
RO |
0xF700:57, 1 |
|
1640:58 |
SubIndex 088 |
88. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x58 (Slave 11 Outputs__Slave 11B, DO3)) |
UINT32 |
RO |
0xF700:58, 1 |
|
1640:59 |
SubIndex 089 |
89. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x59 (Slave 12 Outputs__Slave 12A, DO0)) |
UINT32 |
RO |
0xF700:59, 1 |
|
1640:5A |
SubIndex 090 |
90. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x5A (Slave 12 Outputs__Slave 12A, DO1)) |
UINT32 |
RO |
0xF700:5A, 1 |
|
1640:5B |
SubIndex 091 |
91. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x5B (Slave 12 Outputs__Slave 12A, DO2)) |
UINT32 |
RO |
0xF700:5B, 1 |
|
1640:5C |
SubIndex 092 |
92. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x5C (Slave 12 Outputs__Slave 12A, DO3)) |
UINT32 |
RO |
0xF700:5C, 1 |
|
1640:5D |
SubIndex 093 |
93. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x5D (Slave 12 Outputs__Slave 12B, DO0)) |
UINT32 |
RO |
0xF700:5D, 1 |
|
1640:5E |
SubIndex 094 |
94. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x5E (Slave 12 Outputs__Slave 12B, DO1)) |
UINT32 |
RO |
0xF700:5E, 1 |
|
1640:5F |
SubIndex 095 |
95. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x5F (Slave 12 Outputs__Slave 12B, DO2)) |
UINT32 |
RO |
0xF700:5F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:60 |
SubIndex 096 |
96. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x60 (Slave 12 Outputs__Slave 12B, DO3)) |
UINT32 |
RO |
0xF700:60, 1 |
|
1640:61 |
SubIndex 097 |
97. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x61 (Slave 13 Outputs__Slave 13A, DO0)) |
UINT32 |
RO |
0xF700:61, 1 |
|
1640:62 |
SubIndex 098 |
98. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x62 (Slave 13 Outputs__Slave 13A, DO1)) |
UINT32 |
RO |
0xF700:62, 1 |
|
1640:63 |
SubIndex 099 |
99. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x63 (Slave 13 Outputs__Slave 13A, DO2)) |
UINT32 |
RO |
0xF700:63, 1 |
|
1640:64 |
SubIndex 100 |
100. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x64 (Slave 13 Outputs__Slave 13A, DO3)) |
UINT32 |
RO |
0xF700:64, 1 |
|
1640:65 |
SubIndex 101 |
101. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x65 (Slave 13 Outputs__Slave 13B, DO0)) |
UINT32 |
RO |
0xF700:65, 1 |
|
1640:66 |
SubIndex 102 |
102. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x66 (Slave 13 Outputs__Slave 13B, DO1)) |
UINT32 |
RO |
0xF700:66, 1 |
|
1640:67 |
SubIndex 103 |
103. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x67 (Slave 13 Outputs__Slave 13B, DO2)) |
UINT32 |
RO |
0xF700:67, 1 |
|
1640:68 |
SubIndex 104 |
104. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x68 (Slave 13 Outputs__Slave 13B, DO3)) |
UINT32 |
RO |
0xF700:68, 1 |
|
1640:69 |
SubIndex 105 |
105. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x69 (Slave 14 Outputs__Slave 14A, DO0)) |
UINT32 |
RO |
0xF700:69, 1 |
|
1640:6A |
SubIndex 106 |
106. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x6A (Slave 14 Outputs__Slave 14A, DO1)) |
UINT32 |
RO |
0xF700:6A, 1 |
|
1640:6B |
SubIndex 107 |
107. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x6B (Slave 14 Outputs__Slave 14A, DO2)) |
UINT32 |
RO |
0xF700:6B, 1 |
|
1640:6C |
SubIndex 108 |
108. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x6C (Slave 14 Outputs__Slave 14A, DO3)) |
UINT32 |
RO |
0xF700:6C, 1 |
|
1640:6D |
SubIndex 109 |
109. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x6D (Slave 14 Outputs__Slave 14B, DO0)) |
UINT32 |
RO |
0xF700:6D, 1 |
|
1640:6E |
SubIndex 110 |
110. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x6E (Slave 14 Outputs__Slave 14B, DO1)) |
UINT32 |
RO |
0xF700:6E, 1 |
|
1640:6F |
SubIndex 111 |
111. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x6F (Slave 14 Outputs__Slave 14B, DO2)) |
UINT32 |
RO |
0xF700:6F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:70 |
SubIndex 112 |
112. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x70 (Slave 14 Outputs__Slave 14B, DO3)) |
UINT32 |
RO |
0xF700:70, 1 |
|
1640:71 |
SubIndex 113 |
113. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x71 (Slave 15 Outputs__Slave 15A, DO0)) |
UINT32 |
RO |
0xF700:71, 1 |
|
1640:72 |
SubIndex 114 |
114. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x72 (Slave 15 Outputs__Slave 15A, DO1)) |
UINT32 |
RO |
0xF700:72, 1 |
|
1640:73 |
SubIndex 115 |
115. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x73 (Slave 15 Outputs__Slave 15A, DO2)) |
UINT32 |
RO |
0xF700:73, 1 |
|
1640:74 |
SubIndex 116 |
116. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x74 (Slave 15 Outputs__Slave 15A, DO3)) |
UINT32 |
RO |
0xF700:74, 1 |
|
1640:75 |
SubIndex 117 |
117. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x75 (Slave 15 Outputs__Slave 15B, DO0)) |
UINT32 |
RO |
0xF700:75, 1 |
|
1640:76 |
SubIndex 118 |
118. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x76 (Slave 15 Outputs__Slave 15B, DO1)) |
UINT32 |
RO |
0xF700:76, 1 |
|
1640:77 |
SubIndex 119 |
119. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x77 (Slave 15 Outputs__Slave 15B, DO2)) |
UINT32 |
RO |
0xF700:77, 1 |
|
1640:78 |
SubIndex 120 |
120. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x78 (Slave 15 Outputs__Slave 15B, DO3)) |
UINT32 |
RO |
0xF700:78, 1 |
|
1640:79 |
SubIndex 121 |
121. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x79 (Slave 16 Outputs__Slave 16A, DO0)) |
UINT32 |
RO |
0xF700:79, 1 |
|
1640:7A |
SubIndex 122 |
122. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x7A (Slave 16 Outputs__Slave 16A, DO1)) |
UINT32 |
RO |
0xF700:7A, 1 |
|
1640:7B |
SubIndex 123 |
123. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x7B (Slave 16 Outputs__Slave 16A, DO2)) |
UINT32 |
RO |
0xF700:7B, 1 |
|
1640:7C |
SubIndex 124 |
124. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x7C (Slave 16 Outputs__Slave 16A, DO3)) |
UINT32 |
RO |
0xF700:7C, 1 |
|
1640:7D |
SubIndex 125 |
125. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x7D (Slave 16 Outputs__Slave 16B, DO0)) |
UINT32 |
RO |
0xF700:7D, 1 |
|
1640:7E |
SubIndex 126 |
126. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x7E (Slave 16 Outputs__Slave 16B, DO1)) |
UINT32 |
RO |
0xF700:7E, 1 |
|
1640:7F |
SubIndex 127 |
127. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x7F (Slave 16 Outputs__Slave 16B, DO2)) |
UINT32 |
RO |
0xF700:7F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:80 |
SubIndex 128 |
128. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x80 (Slave 16 Outputs__Slave 16B, DO3)) |
UINT32 |
RO |
0xF700:80, 1 |
|
1640:81 |
SubIndex 129 |
129. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x81 (Slave 17 Outputs__Slave 17A, DO0)) |
UINT32 |
RO |
0xF700:81, 1 |
|
1640:82 |
SubIndex 130 |
130. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x82 (Slave 17 Outputs__Slave 17A, DO1)) |
UINT32 |
RO |
0xF700:82, 1 |
|
1640:83 |
SubIndex 131 |
131. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x83 (Slave 17 Outputs__Slave 17A, DO2)) |
UINT32 |
RO |
0xF700:83, 1 |
|
1640:84 |
SubIndex 132 |
132. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x84 (Slave 17 Outputs__Slave 17A, DO3)) |
UINT32 |
RO |
0xF700:84, 1 |
|
1640:85 |
SubIndex 133 |
133. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x85 (Slave 17 Outputs__Slave 17B, DO0)) |
UINT32 |
RO |
0xF700:85, 1 |
|
1640:86 |
SubIndex 134 |
134. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x86 (Slave 17 Outputs__Slave 17B, DO1)) |
UINT32 |
RO |
0xF700:86, 1 |
|
1640:87 |
SubIndex 135 |
135. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x87 (Slave 17 Outputs__Slave 17B, DO2)) |
UINT32 |
RO |
0xF700:87, 1 |
|
1640:88 |
SubIndex 136 |
136. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x88 (Slave 17 Outputs__Slave 17B, DO3)) |
UINT32 |
RO |
0xF700:88, 1 |
|
1640:89 |
SubIndex 137 |
137. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x89 (Slave 18 Outputs__Slave 18A, DO0)) |
UINT32 |
RO |
0xF700:89, 1 |
|
1640:8A |
SubIndex 138 |
138. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x8A (Slave 18 Outputs__Slave 18A, DO1)) |
UINT32 |
RO |
0xF700:8A, 1 |
|
1640:8B |
SubIndex 139 |
139. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x8B (Slave 18 Outputs__Slave 18A, DO2)) |
UINT32 |
RO |
0xF700:8B, 1 |
|
1640:8C |
SubIndex 140 |
140. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x8C (Slave 18 Outputs__Slave 18A, DO3)) |
UINT32 |
RO |
0xF700:8C, 1 |
|
1640:8D |
SubIndex 141 |
141. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x8D (Slave 18 Outputs__Slave 18B, DO0)) |
UINT32 |
RO |
0xF700:8D, 1 |
|
1640:8E |
SubIndex 142 |
142. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x8E (Slave 18 Outputs__Slave 18B, DO1)) |
UINT32 |
RO |
0xF700:8E, 1 |
|
1640:8F |
SubIndex 143 |
143. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x8F (Slave 18 Outputs__Slave 18B, DO2)) |
UINT32 |
RO |
0xF700:8F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:90 |
SubIndex 144 |
144. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x90 (Slave 18 Outputs__Slave 18B, DO3)) |
UINT32 |
RO |
0xF700:90, 1 |
|
1640:91 |
SubIndex 145 |
145. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x91 (Slave 19 Outputs__Slave 19A, DO0)) |
UINT32 |
RO |
0xF700:91, 1 |
|
1640:92 |
SubIndex 146 |
146. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x92 (Slave 19 Outputs__Slave 19A, DO1)) |
UINT32 |
RO |
0xF700:92, 1 |
|
1640:93 |
SubIndex 147 |
147. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x93 (Slave 19 Outputs__Slave 19A, DO2)) |
UINT32 |
RO |
0xF700:93, 1 |
|
1640:94 |
SubIndex 148 |
148. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x94 (Slave 19 Outputs__Slave 19A, DO3)) |
UINT32 |
RO |
0xF700:94, 1 |
|
1640:95 |
SubIndex 149 |
149. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x95 (Slave 19 Outputs__Slave 19B, DO0)) |
UINT32 |
RO |
0xF700:95, 1 |
|
1640:96 |
SubIndex 150 |
150. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x96 (Slave 19 Outputs__Slave 19B, DO1)) |
UINT32 |
RO |
0xF700:96, 1 |
|
1640:97 |
SubIndex 151 |
151. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x97 (Slave 19 Outputs__Slave 19B, DO2)) |
UINT32 |
RO |
0xF700:97, 1 |
|
1640:98 |
SubIndex 152 |
152. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x98 (Slave 19 Outputs__Slave 19B, DO3)) |
UINT32 |
RO |
0xF700:98, 1 |
|
1640:99 |
SubIndex 153 |
153. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x99 (Slave 20 Outputs__Slave 20A, DO0)) |
UINT32 |
RO |
0xF700:99, 1 |
|
1640:9A |
SubIndex 154 |
154. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x9A (Slave 20 Outputs__Slave 20A, DO1)) |
UINT32 |
RO |
0xF700:9A, 1 |
|
1640:9B |
SubIndex 155 |
155. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x9B (Slave 20 Outputs__Slave 20A, DO2)) |
UINT32 |
RO |
0xF700:9B, 1 |
|
1640:9C |
SubIndex 156 |
156. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x9C (Slave 20 Outputs__Slave 20A, DO3)) |
UINT32 |
RO |
0xF700:9C, 1 |
|
1640:9D |
SubIndex 157 |
157. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x9D (Slave 20 Outputs__Slave 20B, DO0)) |
UINT32 |
RO |
0xF700:9D, 1 |
|
1640:9E |
SubIndex 158 |
158. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x9E (Slave 20 Outputs__Slave 20B, DO1)) |
UINT32 |
RO |
0xF700:9E, 1 |
|
1640:9F |
SubIndex 159 |
159. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0x9F (Slave 20 Outputs__Slave 20B, DO2)) |
UINT32 |
RO |
0xF700:9F, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:A0 |
SubIndex 160 |
160. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA0 (Slave 20 Outputs__Slave 20B, DO3)) |
UINT32 |
RO |
0xF700:A0, 1 |
|
1640:A1 |
SubIndex 161 |
161. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA1 (Slave 21 Outputs__Slave 21A, DO0)) |
UINT32 |
RO |
0xF700:A1, 1 |
|
1640:A2 |
SubIndex 162 |
162. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA2 (Slave 21 Outputs__Slave 21A, DO1)) |
UINT32 |
RO |
0xF700:A2, 1 |
|
1640:A3 |
SubIndex 163 |
163. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA3 (Slave 21 Outputs__Slave 21A, DO2)) |
UINT32 |
RO |
0xF700:A3, 1 |
|
1640:A4 |
SubIndex 164 |
164. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA4 (Slave 21 Outputs__Slave 21A, DO3)) |
UINT32 |
RO |
0xF700:A4, 1 |
|
1640:A5 |
SubIndex 165 |
165. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA5 (Slave 21 Outputs__Slave 21B, DO0)) |
UINT32 |
RO |
0xF700:A5, 1 |
|
1640:A6 |
SubIndex 166 |
166. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA6 (Slave 21 Outputs__Slave 21B, DO1)) |
UINT32 |
RO |
0xF700:A6, 1 |
|
1640:A7 |
SubIndex 167 |
167. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA7 (Slave 21 Outputs__Slave 21B, DO2)) |
UINT32 |
RO |
0xF700:A7, 1 |
|
1640:A8 |
SubIndex 168 |
168. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA8 (Slave 21 Outputs__Slave 21B, DO3)) |
UINT32 |
RO |
0xF700:A8, 1 |
|
1640:A9 |
SubIndex 169 |
169. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xA9 (Slave 22 Outputs__Slave 22A, DO0)) |
UINT32 |
RO |
0xF700:A9, 1 |
|
1640:AA |
SubIndex 170 |
170. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xAA (Slave 22 Outputs__Slave 22A, DO1)) |
UINT32 |
RO |
0xF700:AA, 1 |
|
1640:AB |
SubIndex 171 |
171. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xAB (Slave 22 Outputs__Slave 22A, DO2)) |
UINT32 |
RO |
0xF700:AB, 1 |
|
1640:AC |
SubIndex 172 |
172. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xAC (Slave 22 Outputs__Slave 22A, DO3)) |
UINT32 |
RO |
0xF700:AC, 1 |
|
1640:AD |
SubIndex 173 |
173. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xAD (Slave 22 Outputs__Slave 22B, DO0)) |
UINT32 |
RO |
0xF700:AD, 1 |
|
1640:AE |
SubIndex 174 |
174. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xAE (Slave 22 Outputs__Slave 22B, DO1)) |
UINT32 |
RO |
0xF700:AE, 1 |
|
1640:AF |
SubIndex 175 |
175. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xAF (Slave 22 Outputs__Slave 22B, DO2)) |
UINT32 |
RO |
0xF700:AF, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:B0 |
SubIndex 176 |
176. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB0 (Slave 22 Outputs__Slave 22B, DO3)) |
UINT32 |
RO |
0xF700:B0, 1 |
|
1640:B1 |
SubIndex 177 |
177. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB1 (Slave 23 Outputs__Slave 23A, DO0)) |
UINT32 |
RO |
0xF700:B1, 1 |
|
1640:B2 |
SubIndex 178 |
178. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB2 (Slave 23 Outputs__Slave 23A, DO1)) |
UINT32 |
RO |
0xF700:B2, 1 |
|
1640:B3 |
SubIndex 179 |
179. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB3 (Slave 23 Outputs__Slave 23A, DO2)) |
UINT32 |
RO |
0xF700:B3, 1 |
|
1640:B4 |
SubIndex 180 |
180. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB4 (Slave 23 Outputs__Slave 23A, DO3)) |
UINT32 |
RO |
0xF700:B4, 1 |
|
1640:B5 |
SubIndex 181 |
181. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB5 (Slave 23 Outputs__Slave 23B, DO0)) |
UINT32 |
RO |
0xF700:B5, 1 |
|
1640:B6 |
SubIndex 182 |
182. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB6 (Slave 23 Outputs__Slave 23B, DO1)) |
UINT32 |
RO |
0xF700:B6, 1 |
|
1640:B7 |
SubIndex 183 |
183. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB7 (Slave 23 Outputs__Slave 23B, DO2)) |
UINT32 |
RO |
0xF700:B7, 1 |
|
1640:B8 |
SubIndex 184 |
184. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB8 (Slave 23 Outputs__Slave 23B, DO3)) |
UINT32 |
RO |
0xF700:B8, 1 |
|
1640:B9 |
SubIndex 185 |
185. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xB9 (Slave 24 Outputs__Slave 24A, DO0)) |
UINT32 |
RO |
0xF700:B9, 1 |
|
1640:BA |
SubIndex 186 |
186. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xBA (Slave 24 Outputs__Slave 24A, DO1)) |
UINT32 |
RO |
0xF700:BA, 1 |
|
1640:BB |
SubIndex 187 |
187. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xBB (Slave 24 Outputs__Slave 24A, DO2)) |
UINT32 |
RO |
0xF700:BB, 1 |
|
1640:BC |
SubIndex 188 |
188. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xBC (Slave 24 Outputs__Slave 24A, DO3)) |
UINT32 |
RO |
0xF700:BC, 1 |
|
1640:BD |
SubIndex 189 |
189. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xBD (Slave 24 Outputs__Slave 24B, DO0)) |
UINT32 |
RO |
0xF700:BD, 1 |
|
1640:BE |
SubIndex 190 |
190. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xBE (Slave 24 Outputs__Slave 24B, DO1)) |
UINT32 |
RO |
0xF700:BE, 1 |
|
1640:BF |
SubIndex 191 |
191. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xBF (Slave 24 Outputs__Slave 24B, DO2)) |
UINT32 |
RO |
0xF700:BF, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:C0 |
SubIndex 192 |
192. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC0 (Slave 24 Outputs__Slave 24B, DO3)) |
UINT32 |
RO |
0xF700:C0, 1 |
|
1640:C1 |
SubIndex 193 |
193. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC1 (Slave 25 Outputs__Slave 25A, DO0)) |
UINT32 |
RO |
0xF700:C1, 1 |
|
1640:C2 |
SubIndex 194 |
194. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC2 (Slave 25 Outputs__Slave 25A, DO1)) |
UINT32 |
RO |
0xF700:C2, 1 |
|
1640:C3 |
SubIndex 195 |
195. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC3 (Slave 25 Outputs__Slave 25A, DO2)) |
UINT32 |
RO |
0xF700:C3, 1 |
|
1640:C4 |
SubIndex 196 |
196. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC4 (Slave 25 Outputs__Slave 25A, DO3)) |
UINT32 |
RO |
0xF700:C4, 1 |
|
1640:C5 |
SubIndex 197 |
197. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC5 (Slave 25 Outputs__Slave 25B, DO0)) |
UINT32 |
RO |
0xF700:C5, 1 |
|
1640:C6 |
SubIndex 198 |
198. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC6 (Slave 25 Outputs__Slave 25B, DO1)) |
UINT32 |
RO |
0xF700:C6, 1 |
|
1640:C7 |
SubIndex 199 |
199. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC7 (Slave 25 Outputs__Slave 25B, DO2)) |
UINT32 |
RO |
0xF700:C7, 1 |
|
1640:C8 |
SubIndex 200 |
200. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC8 (Slave 25 Outputs__Slave 25B, DO3)) |
UINT32 |
RO |
0xF700:C8, 1 |
|
1640:C9 |
SubIndex 201 |
201. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xC9 (Slave 26 Outputs__Slave 26A, DO0)) |
UINT32 |
RO |
0xF700:C9, 1 |
|
1640:CA |
SubIndex 202 |
202. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xCA (Slave 26 Outputs__Slave 26A, DO1)) |
UINT32 |
RO |
0xF700:CA, 1 |
|
1640:CB |
SubIndex 203 |
203. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xCB (Slave 26 Outputs__Slave 26A, DO2)) |
UINT32 |
RO |
0xF700:CB, 1 |
|
1640:CC |
SubIndex 204 |
204. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xCC (Slave 26 Outputs__Slave 26A, DO3)) |
UINT32 |
RO |
0xF700:CC, 1 |
|
1640:CD |
SubIndex 205 |
205. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xCD (Slave 26 Outputs__Slave 26B, DO0)) |
UINT32 |
RO |
0xF700:CD, 1 |
|
1640:CE |
SubIndex 206 |
206. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xCE (Slave 26 Outputs__Slave 26B, DO1)) |
UINT32 |
RO |
0xF700:CE, 1 |
|
1640:CF |
SubIndex 207 |
207. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xCF (Slave 26 Outputs__Slave 26B, DO2)) |
UINT32 |
RO |
0xF700:CF, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:D0 |
SubIndex 208 |
208. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD0 (Slave 26 Outputs__Slave 26B, DO3)) |
UINT32 |
RO |
0xF700:D0, 1 |
|
1640:D1 |
SubIndex 209 |
209. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD1 (Slave 27 Outputs__Slave 27A, DO0)) |
UINT32 |
RO |
0xF700:D1, 1 |
|
1640:D2 |
SubIndex 210 |
210. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD2 (Slave 27 Outputs__Slave 27A, DO1)) |
UINT32 |
RO |
0xF700:D2, 1 |
|
1640:D3 |
SubIndex 211 |
211. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD3 (Slave 27 Outputs__Slave 27A, DO2)) |
UINT32 |
RO |
0xF700:D3, 1 |
|
1640:D4 |
SubIndex 212 |
212. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD4 (Slave 27 Outputs__Slave 27A, DO3)) |
UINT32 |
RO |
0xF700:D4, 1 |
|
1640:D5 |
SubIndex 213 |
213. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD5 (Slave 27 Outputs__Slave 27B, DO0)) |
UINT32 |
RO |
0xF700:D5, 1 |
|
1640:D6 |
SubIndex 214 |
214. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD6 (Slave 27 Outputs__Slave 27B, DO1)) |
UINT32 |
RO |
0xF700:D6, 1 |
|
1640:D7 |
SubIndex 215 |
215. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD7 (Slave 27 Outputs__Slave 27B, DO2)) |
UINT32 |
RO |
0xF700:D7, 1 |
|
1640:D8 |
SubIndex 216 |
216. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD8 (Slave 27 Outputs__Slave 27B, DO3)) |
UINT32 |
RO |
0xF700:D8, 1 |
|
1640:D9 |
SubIndex 217 |
217. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xD9 (Slave 28 Outputs__Slave 28A, DO0)) |
UINT32 |
RO |
0xF700:D9, 1 |
|
1640:DA |
SubIndex 218 |
218. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xDA (Slave 28 Outputs__Slave 28A, DO1)) |
UINT32 |
RO |
0xF700:DA, 1 |
|
1640:DB |
SubIndex 219 |
219. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xDB (Slave 28 Outputs__Slave 28A, DO2)) |
UINT32 |
RO |
0xF700:DB, 1 |
|
1640:DC |
SubIndex 220 |
220. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xDC (Slave 28 Outputs__Slave 28A, DO3)) |
UINT32 |
RO |
0xF700:DC, 1 |
|
1640:DD |
SubIndex 221 |
221. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xDD (Slave 28 Outputs__Slave 28B, DO0)) |
UINT32 |
RO |
0xF700:DD, 1 |
|
1640:DE |
SubIndex 222 |
222. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xDE (Slave 28 Outputs__Slave 28B, DO1)) |
UINT32 |
RO |
0xF700:DE, 1 |
|
1640:DF |
SubIndex 223 |
223. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xDF (Slave 28 Outputs__Slave 28B, DO2)) |
UINT32 |
RO |
0xF700:DF, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:E0 |
SubIndex 224 |
224. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE0 (Slave 28 Outputs__Slave 28B, DO3)) |
UINT32 |
RO |
0xF700:E0, 1 |
|
1640:E1 |
SubIndex 225 |
225. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE1 (Slave 29 Outputs__Slave 29A, DO0)) |
UINT32 |
RO |
0xF700:E1, 1 |
|
1640:E2 |
SubIndex 226 |
226. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE2 (Slave 29 Outputs__Slave 29A, DO1)) |
UINT32 |
RO |
0xF700:E2, 1 |
|
1640:E3 |
SubIndex 227 |
227. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE3 (Slave 29 Outputs__Slave 29A, DO2)) |
UINT32 |
RO |
0xF700:E3, 1 |
|
1640:E4 |
SubIndex 228 |
228. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE4 (Slave 29 Outputs__Slave 29A, DO3)) |
UINT32 |
RO |
0xF700:E4, 1 |
|
1640:E5 |
SubIndex 229 |
229. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE5 (Slave 29 Outputs__Slave 29B, DO0)) |
UINT32 |
RO |
0xF700:E5, 1 |
|
1640:E6 |
SubIndex 230 |
230. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE6 (Slave 29 Outputs__Slave 29B, DO1)) |
UINT32 |
RO |
0xF700:E6, 1 |
|
1640:E7 |
SubIndex 231 |
231. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE7 (Slave 29 Outputs__Slave 29B, DO2)) |
UINT32 |
RO |
0xF700:E7, 1 |
|
1640:E8 |
SubIndex 232 |
232. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE8 (Slave 29 Outputs__Slave 29B, DO3)) |
UINT32 |
RO |
0xF700:E8, 1 |
|
1640:E9 |
SubIndex 233 |
233. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xE9 (Slave 30 Outputs__Slave 30A, DO0)) |
UINT32 |
RO |
0xF700:E9, 1 |
|
1640:EA |
SubIndex 234 |
234. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xEA (Slave 30 Outputs__Slave 30A, DO1)) |
UINT32 |
RO |
0xF700:EA, 1 |
|
1640:EB |
SubIndex 235 |
235. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xEB (Slave 30 Outputs__Slave 30A, DO2)) |
UINT32 |
RO |
0xF700:EB, 1 |
|
1640:EC |
SubIndex 236 |
236. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xEC (Slave 30 Outputs__Slave 30A, DO3)) |
UINT32 |
RO |
0xF700:EC, 1 |
|
1640:ED |
SubIndex 237 |
237. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xED (Slave 30 Outputs__Slave 30B, DO0)) |
UINT32 |
RO |
0xF700:ED, 1 |
|
1640:EE |
SubIndex 238 |
238. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xEE (Slave 30 Outputs__Slave 30B, DO1)) |
UINT32 |
RO |
0xF700:EE, 1 |
|
1640:EF |
SubIndex 239 |
239. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xEF (Slave 30 Outputs__Slave 30B, DO2)) |
UINT32 |
RO |
0xF700:EF, 1 |
Index 1640 ASI RxPDO-Map Outputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1640:F0 |
SubIndex 240 |
240. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF0 (Slave 30 Outputs__Slave 30B, DO3)) |
UINT32 |
RO |
0xF700:F0, 1 |
|
1640:F1 |
SubIndex 241 |
241. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF1 (Slave 31 Outputs__Slave 31A, DO0)) |
UINT32 |
RO |
0xF700:F1, 1 |
|
1640:F2 |
SubIndex 242 |
242. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF2 (Slave 31 Outputs__Slave 31A, DO1)) |
UINT32 |
RO |
0xF700:F2, 1 |
|
1640:F3 |
SubIndex 243 |
243. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF3 (Slave 31 Outputs__Slave 31A, DO2)) |
UINT32 |
RO |
0xF700:F3, 1 |
|
1640:F4 |
SubIndex 244 |
244. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF4 (Slave 31 Outputs__Slave 31A, DO3)) |
UINT32 |
RO |
0xF700:F4, 1 |
|
1640:F5 |
SubIndex 245 |
245. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF5 (Slave 31 Outputs__Slave 31B, DO0)) |
UINT32 |
RO |
0xF700:F5, 1 |
|
1640:F6 |
SubIndex 246 |
246. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF6 (Slave 31 Outputs__Slave 31B, DO1)) |
UINT32 |
RO |
0xF700:F6, 1 |
|
1640:F7 |
SubIndex 247 |
247. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF7 (Slave 31 Outputs__Slave 31B, DO2)) |
UINT32 |
RO |
0xF700:F7, 1 |
|
1640:F8 |
SubIndex 248 |
248. PDO Mapping entry (object 0xF700 (ASI Digital Outputs), entry 0xF8 (Slave 31 Outputs__Slave 31B, DO3)) |
UINT32 |
RO |
0xF700:F8, 1 |
Index 1680 ASI RxPDO-Map Control
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1680:0 |
ASI RxPDO-Map Control |
PDO Mapping RxPDO 129 |
UINT8 |
RO |
0x06 (6dec) |
|
1680:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF200 (ASI Control), entry 0x01 (Auto Programming Enable)) |
UINT32 |
RO |
0xF200:01, 1 |
|
1680:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF200 (ASI Control), entry 0x02 (Go Offline Mode)) |
UINT32 |
RO |
0xF200:02, 1 |
|
1680:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF200 (ASI Control), entry 0x03 (Data Exchange Active)) |
UINT32 |
RO |
0xF200:03, 1 |
|
1680:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF200 (ASI Control), entry 0x04 (Go Protected Mode)) |
UINT32 |
RO |
0xF200:04, 1 |
|
1680:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF200 (ASI Control), entry 0x05 (Go Configuration Mode)) |
UINT32 |
RO |
0xF200:05, 1 |
|
1680:06 |
SubIndex 006 |
6. PDO Mapping entry (11 bits align) |
UINT32 |
RO |
0x0000:00, 11 |
Index 1A01 ASI TxPDO-Map Analog Inputs Slave 1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A01:0 |
ASI TxPDO-Map Analog Inputs Slave 1 |
PDO Mapping TxPDO 2 |
UINT8 |
RO |
0x08 (8dec) |
|
1A01:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6010:01, 16 |
|
1A01:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6010:02, 16 |
|
1A01:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6010:03, 16 |
|
1A01:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6010:04, 16 |
|
1A01:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6010:05, 16 |
|
1A01:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6010:06, 16 |
|
1A01:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6010:07, 16 |
|
1A01:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6010 (ASI Analog Inputs Slave 1 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6010:08, 16 |
Index 1A02 ASI TxPDO-Map Analog Inputs Slave 2
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A02:0 |
ASI TxPDO-Map Analog Inputs Slave 2 |
PDO Mapping TxPDO 3 |
UINT8 |
RO |
0x08 (8dec) |
|
1A02:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6020:01, 16 |
|
1A02:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6020:02, 16 |
|
1A02:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6020:03, 16 |
|
1A02:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6020:04, 16 |
|
1A02:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6020:05, 16 |
|
1A02:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6020:06, 16 |
|
1A02:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6020:07, 16 |
|
1A02:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6020 (ASI Analog Inputs Slave 2 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6020:08, 16 |
Index 1A03 ASI TxPDO-Map Analog Inputs Slave 3
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A03:0 |
ASI TxPDO-Map Analog Inputs Slave 3 |
PDO Mapping TxPDO 4 |
UINT8 |
RO |
0x08 (8dec) |
|
1A03:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6030:01, 16 |
|
1A03:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6030:02, 16 |
|
1A03:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6030:03, 16 |
|
1A03:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6030:04, 16 |
|
1A03:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6030:05, 16 |
|
1A03:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6030:06, 16 |
|
1A03:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6030:07, 16 |
|
1A03:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6030 (ASI Analog Inputs Slave 3 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6030:08, 16 |
Index 1A04 ASI TxPDO-Map Analog Inputs Slave 4
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A04:0 |
ASI TxPDO-Map Analog Inputs Slave 4 |
PDO Mapping TxPDO 5 |
UINT8 |
RO |
0x08 (8dec) |
|
1A04:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6040:01, 16 |
|
1A04:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6040:02, 16 |
|
1A04:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6040:03, 16 |
|
1A04:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6040:04, 16 |
|
1A04:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6040:05, 16 |
|
1A04:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6040:06, 16 |
|
1A04:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6040:07, 16 |
|
1A04:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6040 (ASI Analog Inputs Slave 4 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6040:08, 16 |
Index 1A05 ASI TxPDO-Map Analog Inputs Slave 5
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A05:0 |
ASI TxPDO-Map Analog Inputs Slave 5 |
PDO Mapping TxPDO 6 |
UINT8 |
RO |
0x08 (8dec) |
|
1A05:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6050:01, 16 |
|
1A05:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6050:02, 16 |
|
1A05:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6050:03, 16 |
|
1A05:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6050:04, 16 |
|
1A05:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6050:05, 16 |
|
1A05:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6050:06, 16 |
|
1A05:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6050:07, 16 |
|
1A05:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6050 (ASI Analog Inputs Slave 5 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6050:08, 16 |
Index 1A06 ASI TxPDO-Map Analog Inputs Slave 6
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A06:0 |
ASI TxPDO-Map Analog Inputs Slave 6 |
PDO Mapping TxPDO 7 |
UINT8 |
RO |
0x08 (8dec) |
|
1A06:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6060:01, 16 |
|
1A06:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6060:02, 16 |
|
1A06:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6060:03, 16 |
|
1A06:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6060:04, 16 |
|
1A06:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6060:05, 16 |
|
1A06:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6060:06, 16 |
|
1A06:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6060:07, 16 |
|
1A06:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6060 (ASI Analog Inputs Slave 6 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6060:08, 16 |
Index 1A07 ASI TxPDO-Map Analog Inputs Slave 7
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A07:0 |
ASI TxPDO-Map Analog Inputs Slave 7 |
PDO Mapping TxPDO 8 |
UINT8 |
RO |
0x08 (8dec) |
|
1A07:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6070:01, 16 |
|
1A07:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6070:02, 16 |
|
1A07:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6070:03, 16 |
|
1A07:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6070:04, 16 |
|
1A07:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6070:05, 16 |
|
1A07:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6070:06, 16 |
|
1A07:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6070:07, 16 |
|
1A07:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6070 (ASI Analog Inputs Slave 7 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6070:08, 16 |
Index 1A08 ASI TxPDO-Map Analog Inputs Slave 8
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A08:0 |
ASI TxPDO-Map Analog Inputs Slave 8 |
PDO Mapping TxPDO 9 |
UINT8 |
RO |
0x08 (8dec) |
|
1A08:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6080:01, 16 |
|
1A08:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6080:02, 16 |
|
1A08:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6080:03, 16 |
|
1A08:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6080:04, 16 |
|
1A08:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6080:05, 16 |
|
1A08:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6080:06, 16 |
|
1A08:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6080:07, 16 |
|
1A08:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6080 (ASI Analog Inputs Slave 8 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6080:08, 16 |
Index 1A09 ASI TxPDO-Map Analog Inputs Slave 9
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A09:0 |
ASI TxPDO-Map Analog Inputs Slave 9 |
PDO Mapping TxPDO 10 |
UINT8 |
RO |
0x08 (8dec) |
|
1A09:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6090:01, 16 |
|
1A09:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6090:02, 16 |
|
1A09:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6090:03, 16 |
|
1A09:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6090:04, 16 |
|
1A09:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6090:05, 16 |
|
1A09:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6090:06, 16 |
|
1A09:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6090:07, 16 |
|
1A09:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6090 (ASI Analog Inputs Slave 9 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6090:08, 16 |
Index 1A0A ASI TxPDO-Map Analog Inputs Slave 10
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0A:0 |
ASI TxPDO-Map Analog Inputs Slave 10 |
PDO Mapping TxPDO 11 |
UINT8 |
RO |
0x08 (8dec) |
|
1A0A:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60A0:01, 16 |
|
1A0A:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60A0:02, 16 |
|
1A0A:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60A0:03, 16 |
|
1A0A:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60A0:04, 16 |
|
1A0A:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60A0:05, 16 |
|
1A0A:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60A0:06, 16 |
|
1A0A:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60A0:07, 16 |
|
1A0A:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60A0 (ASI Analog Inputs Slave 10 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60A0:08, 16 |
Index 1A0B ASI TxPDO-Map Analog Inputs Slave 11
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0B:0 |
ASI TxPDO-Map Analog Inputs Slave 11 |
PDO Mapping TxPDO 12 |
UINT8 |
RO |
0x08 (8dec) |
|
1A0B:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60B0:01, 16 |
|
1A0B:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60B0:02, 16 |
|
1A0B:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60B0:03, 16 |
|
1A0B:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60B0:04, 16 |
|
1A0B:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60B0:05, 16 |
|
1A0B:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60B0:06, 16 |
|
1A0B:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60B0:07, 16 |
|
1A0B:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60B0 (ASI Analog Inputs Slave 11 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60B0:08, 16 |
Index 1A0C ASI TxPDO-Map Analog Inputs Slave 12
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0C:0 |
ASI TxPDO-Map Analog Inputs Slave 12 |
PDO Mapping TxPDO 13 |
UINT8 |
RO |
0x08 (8dec) |
|
1A0C:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60C0:01, 16 |
|
1A0C:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60C0:02, 16 |
|
1A0C:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60C0:03, 16 |
|
1A0C:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60C0:04, 16 |
|
1A0C:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60C0:05, 16 |
|
1A0C:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60C0:06, 16 |
|
1A0C:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60C0:07, 16 |
|
1A0C:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60C0 (ASI Analog Inputs Slave 12 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60C0:08, 16 |
Index 1A0D ASI TxPDO-Map Analog Inputs Slave 13
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0D:0 |
ASI TxPDO-Map Analog Inputs Slave 13 |
PDO Mapping TxPDO 14 |
UINT8 |
RO |
0x08 (8dec) |
|
1A0D:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60D0:01, 16 |
|
1A0D:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60D0:02, 16 |
|
1A0D:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60D0:03, 16 |
|
1A0D:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60D0:04, 16 |
|
1A0D:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60D0:05, 16 |
|
1A0D:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60D0:06, 16 |
|
1A0D:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60D0:07, 16 |
|
1A0D:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60D0 (ASI Analog Inputs Slave 13 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60D0:08, 16 |
Index 1A0E ASI TxPDO-Map Analog Inputs Slave 14
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0E:0 |
ASI TxPDO-Map Analog Inputs Slave 14 |
PDO Mapping TxPDO 15 |
UINT8 |
RO |
0x08 (8dec) |
|
1A0E:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60E0:01, 16 |
|
1A0E:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60E0:02, 16 |
|
1A0E:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60E0:03, 16 |
|
1A0E:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60E0:04, 16 |
|
1A0E:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60E0:05, 16 |
|
1A0E:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60E0:06, 16 |
|
1A0E:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60E0:07, 16 |
|
1A0E:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60E0 (ASI Analog Inputs Slave 14 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60E0:08, 16 |
Index 1A0F ASI TxPDO-Map Analog Inputs Slave 15
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A0F:0 |
ASI TxPDO-Map Analog Inputs Slave 15 |
PDO Mapping TxPDO 16 |
UINT8 |
RO |
0x08 (8dec) |
|
1A0F:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60F0:01, 16 |
|
1A0F:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x60F0:02, 16 |
|
1A0F:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60F0:03, 16 |
|
1A0F:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x60F0:04, 16 |
|
1A0F:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60F0:05, 16 |
|
1A0F:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x60F0:06, 16 |
|
1A0F:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60F0:07, 16 |
|
1A0F:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x60F0 (ASI Analog Inputs Slave 15 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x60F0:08, 16 |
Index 1A10 ASI TxPDO-Map Analog Inputs Slave 16
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A10:0 |
ASI TxPDO-Map Analog Inputs Slave 16 |
PDO Mapping TxPDO 17 |
UINT8 |
RO |
0x08 (8dec) |
|
1A10:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6100:01, 16 |
|
1A10:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6100:02, 16 |
|
1A10:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6100:03, 16 |
|
1A10:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6100:04, 16 |
|
1A10:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6100:05, 16 |
|
1A10:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6100:06, 16 |
|
1A10:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6100:07, 16 |
|
1A10:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6100 (ASI Analog Inputs Slave 16 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6100:08, 16 |
Index 1A11 ASI TxPDO-Map Analog Inputs Slave 17
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A11:0 |
ASI TxPDO-Map Analog Inputs Slave 17 |
PDO Mapping TxPDO 18 |
UINT8 |
RO |
0x08 (8dec) |
|
1A11:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6110:01, 16 |
|
1A11:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6110:02, 16 |
|
1A11:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6110:03, 16 |
|
1A11:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6110:04, 16 |
|
1A11:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6110:05, 16 |
|
1A11:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6110:06, 16 |
|
1A11:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6110:07, 16 |
|
1A11:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6110 (ASI Analog Inputs Slave 17 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6110:08, 16 |
Index 1A12 ASI TxPDO-Map Analog Inputs Slave 18
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A12:0 |
ASI TxPDO-Map Analog Inputs Slave 18 |
PDO Mapping TxPDO 19 |
UINT8 |
RO |
0x08 (8dec) |
|
1A12:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6120:01, 16 |
|
1A12:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6120:02, 16 |
|
1A12:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6120:03, 16 |
|
1A12:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6120:04, 16 |
|
1A12:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6120:05, 16 |
|
1A12:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6120:06, 16 |
|
1A12:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6120:07, 16 |
|
1A12:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6120 (ASI Analog Inputs Slave 18 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6120:08, 16 |
Index 1A13 ASI TxPDO-Map Analog Inputs Slave 19
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A13:0 |
ASI TxPDO-Map Analog Inputs Slave 19 |
PDO Mapping TxPDO 20 |
UINT8 |
RO |
0x08 (8dec) |
|
1A13:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6130:01, 16 |
|
1A13:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6130:02, 16 |
|
1A13:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6130:03, 16 |
|
1A13:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6130:04, 16 |
|
1A13:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6130:05, 16 |
|
1A13:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6130:06, 16 |
|
1A13:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6130:07, 16 |
|
1A13:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6130 (ASI Analog Inputs Slave 19 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6130:08, 16 |
Index 1A14 ASI TxPDO-Map Analog Inputs Slave 20
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A14:0 |
ASI TxPDO-Map Analog Inputs Slave 20 |
PDO Mapping TxPDO 21 |
UINT8 |
RO |
0x08 (8dec) |
|
1A14:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6140:01, 16 |
|
1A14:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6140:02, 16 |
|
1A14:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6140:03, 16 |
|
1A14:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6140:04, 16 |
|
1A14:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6140:05, 16 |
|
1A14:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6140:06, 16 |
|
1A14:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6140:07, 16 |
|
1A14:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6140 (ASI Analog Inputs Slave 20 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6140:08, 16 |
Index 1A15 ASI TxPDO-Map Analog Inputs Slave 21
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A15:0 |
ASI TxPDO-Map Analog Inputs Slave 21 |
PDO Mapping TxPDO 22 |
UINT8 |
RO |
0x08 (8dec) |
|
1A15:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6150:01, 16 |
|
1A15:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6150:02, 16 |
|
1A15:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6150:03, 16 |
|
1A15:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6150:04, 16 |
|
1A15:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6150:05, 16 |
|
1A15:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6150:06, 16 |
|
1A15:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6150:07, 16 |
|
1A15:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6150 (ASI Analog Inputs Slave 21 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6150:08, 16 |
Index 1A16 ASI TxPDO-Map Analog Inputs Slave 22
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A16:0 |
ASI TxPDO-Map Analog Inputs Slave 22 |
PDO Mapping TxPDO 23 |
UINT8 |
RO |
0x08 (8dec) |
|
1A16:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6160:01, 16 |
|
1A16:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6160:02, 16 |
|
1A16:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6160:03, 16 |
|
1A16:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6160:04, 16 |
|
1A16:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6160:05, 16 |
|
1A16:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6160:06, 16 |
|
1A16:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6160:07, 16 |
|
1A16:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6160 (ASI Analog Inputs Slave 22 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6160:08, 16 |
Index 1A17 ASI TxPDO-Map Analog Inputs Slave 23
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A17:0 |
ASI TxPDO-Map Analog Inputs Slave 23 |
PDO Mapping TxPDO 24 |
UINT8 |
RO |
0x08 (8dec) |
|
1A17:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6170:01, 16 |
|
1A17:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6170:02, 16 |
|
1A17:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6170:03, 16 |
|
1A17:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6170:04, 16 |
|
1A17:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6170:05, 16 |
|
1A17:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6170:06, 16 |
|
1A17:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6170:07, 16 |
|
1A17:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6170 (ASI Analog Inputs Slave 23 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6170:08, 16 |
Index 1A18 ASI TxPDO-Map Analog Inputs Slave 24
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A18:0 |
ASI TxPDO-Map Analog Inputs Slave 24 |
PDO Mapping TxPDO 25 |
UINT8 |
RO |
0x08 (8dec) |
|
1A18:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6180:01, 16 |
|
1A18:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6180:02, 16 |
|
1A18:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6180:03, 16 |
|
1A18:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6180:04, 16 |
|
1A18:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6180:05, 16 |
|
1A18:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6180:06, 16 |
|
1A18:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6180:07, 16 |
|
1A18:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6180 (ASI Analog Inputs Slave 24 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6180:08, 16 |
Index 1A19 ASI TxPDO-Map Analog Inputs Slave 25
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A19:0 |
ASI TxPDO-Map Analog Inputs Slave 25 |
PDO Mapping TxPDO 26 |
UINT8 |
RO |
0x08 (8dec) |
|
1A19:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6190:01, 16 |
|
1A19:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x6190:02, 16 |
|
1A19:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6190:03, 16 |
|
1A19:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x6190:04, 16 |
|
1A19:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6190:05, 16 |
|
1A19:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x6190:06, 16 |
|
1A19:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6190:07, 16 |
|
1A19:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6190 (ASI Analog Inputs Slave 25 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x6190:08, 16 |
Index 1A1A ASI TxPDO-Map Analog Inputs Slave 26
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A1A:0 |
ASI TxPDO-Map Analog Inputs Slave 26 |
PDO Mapping TxPDO 27 |
UINT8 |
RO |
0x08 (8dec) |
|
1A1A:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61A0:01, 16 |
|
1A1A:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61A0:02, 16 |
|
1A1A:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61A0:03, 16 |
|
1A1A:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61A0:04, 16 |
|
1A1A:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61A0:05, 16 |
|
1A1A:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61A0:06, 16 |
|
1A1A:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61A0:07, 16 |
|
1A1A:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x61A0 (ASI Analog Inputs Slave 26 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61A0:08, 16 |
Index 1A1B ASI TxPDO-Map Analog Inputs Slave 27
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A1B:0 |
ASI TxPDO-Map Analog Inputs Slave 27 |
PDO Mapping TxPDO 28 |
UINT8 |
RO |
0x08 (8dec) |
|
1A1B:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61B0:01, 16 |
|
1A1B:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61B0:02, 16 |
|
1A1B:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61B0:03, 16 |
|
1A1B:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61B0:04, 16 |
|
1A1B:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61B0:05, 16 |
|
1A1B:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61B0:06, 16 |
|
1A1B:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61B0:07, 16 |
|
1A1B:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x61B0 (ASI Analog Inputs Slave 27 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61B0:08, 16 |
Index 1A1C ASI TxPDO-Map Analog Inputs Slave 28
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A1C:0 |
ASI TxPDO-Map Analog Inputs Slave 28 |
PDO Mapping TxPDO 29 |
UINT8 |
RO |
0x08 (8dec) |
|
1A1C:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61C0:01, 16 |
|
1A1C:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61C0:02, 16 |
|
1A1C:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61C0:03, 16 |
|
1A1C:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61C0:04, 16 |
|
1A1C:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61C0:05, 16 |
|
1A1C:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61C0:06, 16 |
|
1A1C:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61C0:07, 16 |
|
1A1C:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x61C0 (ASI Analog Inputs Slave 28 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61C0:08, 16 |
Index 1A1D ASI TxPDO-Map Analog Inputs Slave 29
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A1D:0 |
ASI TxPDO-Map Analog Inputs Slave 29 |
PDO Mapping TxPDO 30 |
UINT8 |
RO |
0x08 (8dec) |
|
1A1D:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61D0:01, 16 |
|
1A1D:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61D0:02, 16 |
|
1A1D:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61D0:03, 16 |
|
1A1D:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61D0:04, 16 |
|
1A1D:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61D0:05, 16 |
|
1A1D:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61D0:06, 16 |
|
1A1D:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61D0:07, 16 |
|
1A1D:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x61D0 (ASI Analog Inputs Slave 29 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61D0:08, 16 |
Index 1A1E ASI TxPDO-Map Analog Inputs Slave 30
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A1E:0 |
ASI TxPDO-Map Analog Inputs Slave 30 |
PDO Mapping TxPDO 31 |
UINT8 |
RO |
0x08 (8dec) |
|
1A1E:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61E0:01, 16 |
|
1A1E:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61E0:02, 16 |
|
1A1E:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61E0:03, 16 |
|
1A1E:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61E0:04, 16 |
|
1A1E:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61E0:05, 16 |
|
1A1E:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61E0:06, 16 |
|
1A1E:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61E0:07, 16 |
|
1A1E:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x61E0 (ASI Analog Inputs Slave 30 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61E0:08, 16 |
Index 1A1F ASI TxPDO-Map Analog Inputs Slave 31
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A1F:0 |
ASI TxPDO-Map Analog Inputs Slave 31 |
PDO Mapping TxPDO 32 |
UINT8 |
RO |
0x08 (8dec) |
|
1A1F:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x01 (State Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61F0:01, 16 |
|
1A1F:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x02 (Value Ch.1 (A-Slave))) |
UINT32 |
RO |
0x61F0:02, 16 |
|
1A1F:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x03 (State Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61F0:03, 16 |
|
1A1F:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x04 (Value Ch.2 (A-Slave))) |
UINT32 |
RO |
0x61F0:04, 16 |
|
1A1F:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x05 (State Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61F0:05, 16 |
|
1A1F:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x06 (Value Ch.3 (A-Slave))) |
UINT32 |
RO |
0x61F0:06, 16 |
|
1A1F:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x07 (State Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61F0:07, 16 |
|
1A1F:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x61F0 (ASI Analog Inputs Slave 31 ), entry 0x08 (Value Ch.4 (A-Slave))) |
UINT32 |
RO |
0x61F0:08, 16 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:0 |
ASI TxPDO-Map Inputs Device |
PDO Mapping TxPDO 65 |
UINT8 |
RO |
0xF8 (248dec) |
|
1A40:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x01 (Slave 1 Inputs__Slave 1A, DI0)) |
UINT32 |
RO |
0xF600:01, 1 |
|
1A40:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x02 (Slave 1 Inputs__Slave 1A, DI1)) |
UINT32 |
RO |
0xF600:02, 1 |
|
1A40:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x03 (Slave 1 Inputs__Slave 1A, DI2)) |
UINT32 |
RO |
0xF600:03, 1 |
|
1A40:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x04 (Slave 1 Inputs__Slave 1A, DI3)) |
UINT32 |
RO |
0xF600:04, 1 |
|
1A40:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x05 (Slave 1 Inputs__Slave 1B, DI0)) |
UINT32 |
RO |
0xF600:05, 1 |
|
1A40:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x06 (Slave 1 Inputs__Slave 1B, DI1)) |
UINT32 |
RO |
0xF600:06, 1 |
|
1A40:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x07 (Slave 1 Inputs__Slave 1B, DI2)) |
UINT32 |
RO |
0xF600:07, 1 |
|
1A40:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x08 (Slave 1 Inputs__Slave 1B, DI3)) |
UINT32 |
RO |
0xF600:08, 1 |
|
1A40:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x09 (Slave 2 Inputs__Slave 2A, DI0)) |
UINT32 |
RO |
0xF600:09, 1 |
|
1A40:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x0A (Slave 2 Inputs__Slave 2A, DI1)) |
UINT32 |
RO |
0xF600:0A, 1 |
|
1A40:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x0B (Slave 2 Inputs__Slave 2A, DI2)) |
UINT32 |
RO |
0xF600:0B, 1 |
|
1A40:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x0C (Slave 2 Inputs__Slave 2A, DI3)) |
UINT32 |
RO |
0xF600:0C, 1 |
|
1A40:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x0D (Slave 2 Inputs__Slave 2B, DI0)) |
UINT32 |
RO |
0xF600:0D, 1 |
|
1A40:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x0E (Slave 2 Inputs__Slave 2B, DI1)) |
UINT32 |
RO |
0xF600:0E, 1 |
|
1A40:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x0F (Slave 2 Inputs__Slave 2B, DI2)) |
UINT32 |
RO |
0xF600:0F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:10 |
SubIndex 016 |
16. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x10 (Slave 2 Inputs__Slave 2B, DI3)) |
UINT32 |
RO |
0xF600:10, 1 |
|
1A40:11 |
SubIndex 017 |
17. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x11 (Slave 3 Inputs__Slave 3A, DI0)) |
UINT32 |
RO |
0xF600:11, 1 |
|
1A40:12 |
SubIndex 018 |
18. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x12 (Slave 3 Inputs__Slave 3A, DI1)) |
UINT32 |
RO |
0xF600:12, 1 |
|
1A40:13 |
SubIndex 019 |
19. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x13 (Slave 3 Inputs__Slave 3A, DI2)) |
UINT32 |
RO |
0xF600:13, 1 |
|
1A40:14 |
SubIndex 020 |
20. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x14 (Slave 3 Inputs__Slave 3A, DI3)) |
UINT32 |
RO |
0xF600:14, 1 |
|
1A40:15 |
SubIndex 021 |
21. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x15 (Slave 3 Inputs__Slave 3B, DI0)) |
UINT32 |
RO |
0xF600:15, 1 |
|
1A40:16 |
SubIndex 022 |
22. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x16 (Slave 3 Inputs__Slave 3B, DI1)) |
UINT32 |
RO |
0xF600:16, 1 |
|
1A40:17 |
SubIndex 023 |
23. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x17 (Slave 3 Inputs__Slave 3B, DI2)) |
UINT32 |
RO |
0xF600:17, 1 |
|
1A40:18 |
SubIndex 024 |
24. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x18 (Slave 3 Inputs__Slave 3B, DI3)) |
UINT32 |
RO |
0xF600:18, 1 |
|
1A40:19 |
SubIndex 025 |
25. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x19 (Slave 4 Inputs__Slave 4A, DI0)) |
UINT32 |
RO |
0xF600:19, 1 |
|
1A40:1A |
SubIndex 026 |
26. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x1A (Slave 4 Inputs__Slave 4A, DI1)) |
UINT32 |
RO |
0xF600:1A, 1 |
|
1A40:1B |
SubIndex 027 |
27. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x1B (Slave 4 Inputs__Slave 4A, DI2)) |
UINT32 |
RO |
0xF600:1B, 1 |
|
1A40:1C |
SubIndex 028 |
28. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x1C (Slave 4 Inputs__Slave 4A, DI3)) |
UINT32 |
RO |
0xF600:1C, 1 |
|
1A40:1D |
SubIndex 029 |
29. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x1D (Slave 4 Inputs__Slave 4B, DI0)) |
UINT32 |
RO |
0xF600:1D, 1 |
|
1A40:1E |
SubIndex 030 |
30. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x1E (Slave 4 Inputs__Slave 4B, DI1)) |
UINT32 |
RO |
0xF600:1E, 1 |
|
1A40:1F |
SubIndex 031 |
31. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x1F (Slave 4 Inputs__Slave 4B, DI2)) |
UINT32 |
RO |
0xF600:1F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:20 |
SubIndex 032 |
32. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x20 (Slave 4 Inputs__Slave 4B, DI3)) |
UINT32 |
RO |
0xF600:20, 1 |
|
1A40:21 |
SubIndex 033 |
33. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x21 (Slave 5 Inputs__Slave 5A, DI0)) |
UINT32 |
RO |
0xF600:21, 1 |
|
1A40:22 |
SubIndex 034 |
34. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x22 (Slave 5 Inputs__Slave 5A, DI1)) |
UINT32 |
RO |
0xF600:22, 1 |
|
1A40:23 |
SubIndex 035 |
35. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x23 (Slave 5 Inputs__Slave 5A, DI2)) |
UINT32 |
RO |
0xF600:23, 1 |
|
1A40:24 |
SubIndex 036 |
36. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x24 (Slave 5 Inputs__Slave 5A, DI3)) |
UINT32 |
RO |
0xF600:24, 1 |
|
1A40:25 |
SubIndex 037 |
37. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x25 (Slave 5 Inputs__Slave 5B, DI0)) |
UINT32 |
RO |
0xF600:25, 1 |
|
1A40:26 |
SubIndex 038 |
38. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x26 (Slave 5 Inputs__Slave 5B, DI1)) |
UINT32 |
RO |
0xF600:26, 1 |
|
1A40:27 |
SubIndex 039 |
39. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x27 (Slave 5 Inputs__Slave 5B, DI2)) |
UINT32 |
RO |
0xF600:27, 1 |
|
1A40:28 |
SubIndex 040 |
40. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x28 (Slave 5 Inputs__Slave 5B, DI3)) |
UINT32 |
RO |
0xF600:28, 1 |
|
1A40:29 |
SubIndex 041 |
41. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x29 (Slave 6 Inputs__Slave 6A, DI0)) |
UINT32 |
RO |
0xF600:29, 1 |
|
1A40:2A |
SubIndex 042 |
42. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x2A (Slave 6 Inputs__Slave 6A, DI1)) |
UINT32 |
RO |
0xF600:2A, 1 |
|
1A40:2B |
SubIndex 043 |
43. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x2B (Slave 6 Inputs__Slave 6A, DI2)) |
UINT32 |
RO |
0xF600:2B, 1 |
|
1A40:2C |
SubIndex 044 |
44. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x2C (Slave 6 Inputs__Slave 6A, DI3)) |
UINT32 |
RO |
0xF600:2C, 1 |
|
1A40:2D |
SubIndex 045 |
45. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x2D (Slave 6 Inputs__Slave 6B, DI0)) |
UINT32 |
RO |
0xF600:2D, 1 |
|
1A40:2E |
SubIndex 046 |
46. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x2E (Slave 6 Inputs__Slave 6B, DI1)) |
UINT32 |
RO |
0xF600:2E, 1 |
|
1A40:2F |
SubIndex 047 |
47. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x2F (Slave 6 Inputs__Slave 6B, DI2)) |
UINT32 |
RO |
0xF600:2F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:30 |
SubIndex 048 |
48. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x30 (Slave 6 Inputs__Slave 6B, DI3)) |
UINT32 |
RO |
0xF600:30, 1 |
|
1A40:31 |
SubIndex 049 |
49. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x31 (Slave 7 Inputs__Slave 7A, DI0)) |
UINT32 |
RO |
0xF600:31, 1 |
|
1A40:32 |
SubIndex 050 |
50. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x32 (Slave 7 Inputs__Slave 7A, DI1)) |
UINT32 |
RO |
0xF600:32, 1 |
|
1A40:33 |
SubIndex 051 |
51. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x33 (Slave 7 Inputs__Slave 7A, DI2)) |
UINT32 |
RO |
0xF600:33, 1 |
|
1A40:34 |
SubIndex 052 |
52. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x34 (Slave 7 Inputs__Slave 7A, DI3)) |
UINT32 |
RO |
0xF600:34, 1 |
|
1A40:35 |
SubIndex 053 |
53. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x35 (Slave 7 Inputs__Slave 7B, DI0)) |
UINT32 |
RO |
0xF600:35, 1 |
|
1A40:36 |
SubIndex 054 |
54. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x36 (Slave 7 Inputs__Slave 7B, DI1)) |
UINT32 |
RO |
0xF600:36, 1 |
|
1A40:37 |
SubIndex 055 |
55. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x37 (Slave 7 Inputs__Slave 7B, DI2)) |
UINT32 |
RO |
0xF600:37, 1 |
|
1A40:38 |
SubIndex 056 |
56. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x38 (Slave 7 Inputs__Slave 7B, DI3)) |
UINT32 |
RO |
0xF600:38, 1 |
|
1A40:39 |
SubIndex 057 |
57. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x39 (Slave 8 Inputs__Slave 8A, DI0)) |
UINT32 |
RO |
0xF600:39, 1 |
|
1A40:3A |
SubIndex 058 |
58. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x3A (Slave 8 Inputs__Slave 8A, DI1)) |
UINT32 |
RO |
0xF600:3A, 1 |
|
1A40:3B |
SubIndex 059 |
59. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x3B (Slave 8 Inputs__Slave 8A, DI2)) |
UINT32 |
RO |
0xF600:3B, 1 |
|
1A40:3C |
SubIndex 060 |
60. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x3C (Slave 8 Inputs__Slave 8A, DI3)) |
UINT32 |
RO |
0xF600:3C, 1 |
|
1A40:3D |
SubIndex 061 |
61. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x3D (Slave 8 Inputs__Slave 8B, DI0)) |
UINT32 |
RO |
0xF600:3D, 1 |
|
1A40:3E |
SubIndex 062 |
62. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x3E (Slave 8 Inputs__Slave 8B, DI1)) |
UINT32 |
RO |
0xF600:3E, 1 |
|
1A40:3F |
SubIndex 063 |
63. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x3F (Slave 8 Inputs__Slave 8B, DI2)) |
UINT32 |
RO |
0xF600:3F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:40 |
SubIndex 064 |
64. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x40 (Slave 8 Inputs__Slave 8B, DI3)) |
UINT32 |
RO |
0xF600:40, 1 |
|
1A40:41 |
SubIndex 065 |
65. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x41 (Slave 9 Inputs__Slave 9A, DI0)) |
UINT32 |
RO |
0xF600:41, 1 |
|
1A40:42 |
SubIndex 066 |
66. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x42 (Slave 9 Inputs__Slave 9A, DI1)) |
UINT32 |
RO |
0xF600:42, 1 |
|
1A40:43 |
SubIndex 067 |
67. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x43 (Slave 9 Inputs__Slave 9A, DI2)) |
UINT32 |
RO |
0xF600:43, 1 |
|
1A40:44 |
SubIndex 068 |
68. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x44 (Slave 9 Inputs__Slave 9A, DI3)) |
UINT32 |
RO |
0xF600:44, 1 |
|
1A40:45 |
SubIndex 069 |
69. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x45 (Slave 9 Inputs__Slave 9B, DI0)) |
UINT32 |
RO |
0xF600:45, 1 |
|
1A40:46 |
SubIndex 070 |
70. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x46 (Slave 9 Inputs__Slave 9B, DI1)) |
UINT32 |
RO |
0xF600:46, 1 |
|
1A40:47 |
SubIndex 071 |
71. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x47 (Slave 9 Inputs__Slave 9B, DI2)) |
UINT32 |
RO |
0xF600:47, 1 |
|
1A40:48 |
SubIndex 072 |
72. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x48 (Slave 9 Inputs__Slave 9B, DI3)) |
UINT32 |
RO |
0xF600:48, 1 |
|
1A40:49 |
SubIndex 073 |
73. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x49 (Slave 10 Inputs__Slave 10A, DI0)) |
UINT32 |
RO |
0xF600:49, 1 |
|
1A40:4A |
SubIndex 074 |
74. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x4A (Slave 10 Inputs__Slave 10A, DI1)) |
UINT32 |
RO |
0xF600:4A, 1 |
|
1A40:4B |
SubIndex 075 |
75. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x4B (Slave 10 Inputs__Slave 10A, DI2)) |
UINT32 |
RO |
0xF600:4B, 1 |
|
1A40:4C |
SubIndex 076 |
76. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x4C (Slave 10 Inputs__Slave 10A, DI3)) |
UINT32 |
RO |
0xF600:4C, 1 |
|
1A40:4D |
SubIndex 077 |
77. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x4D (Slave 10 Inputs__Slave 10B, DI0)) |
UINT32 |
RO |
0xF600:4D, 1 |
|
1A40:4E |
SubIndex 078 |
78. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x4E (Slave 10 Inputs__Slave 10B, DI1)) |
UINT32 |
RO |
0xF600:4E, 1 |
|
1A40:4F |
SubIndex 079 |
79. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x4F (Slave 10 Inputs__Slave 10B, DI2)) |
UINT32 |
RO |
0xF600:4F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:50 |
SubIndex 080 |
80. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x50 (Slave 10 Inputs__Slave 10B, DI3)) |
UINT32 |
RO |
0xF600:50, 1 |
|
1A40:51 |
SubIndex 081 |
81. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x51 (Slave 11 Inputs__Slave 11A, DI0)) |
UINT32 |
RO |
0xF600:51, 1 |
|
1A40:52 |
SubIndex 082 |
82. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x52 (Slave 11 Inputs__Slave 11A, DI1)) |
UINT32 |
RO |
0xF600:52, 1 |
|
1A40:53 |
SubIndex 083 |
83. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x53 (Slave 11 Inputs__Slave 11A, DI2)) |
UINT32 |
RO |
0xF600:53, 1 |
|
1A40:54 |
SubIndex 084 |
84. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x54 (Slave 11 Inputs__Slave 11A, DI3)) |
UINT32 |
RO |
0xF600:54, 1 |
|
1A40:55 |
SubIndex 085 |
85. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x55 (Slave 11 Inputs__Slave 11B, DI0)) |
UINT32 |
RO |
0xF600:55, 1 |
|
1A40:56 |
SubIndex 086 |
86. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x56 (Slave 11 Inputs__Slave 11B, DI1)) |
UINT32 |
RO |
0xF600:56, 1 |
|
1A40:57 |
SubIndex 087 |
87. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x57 (Slave 11 Inputs__Slave 11B, DI2)) |
UINT32 |
RO |
0xF600:57, 1 |
|
1A40:58 |
SubIndex 088 |
88. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x58 (Slave 11 Inputs__Slave 11B, DI3)) |
UINT32 |
RO |
0xF600:58, 1 |
|
1A40:59 |
SubIndex 089 |
89. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x59 (Slave 12 Inputs__Slave 12A, DI0)) |
UINT32 |
RO |
0xF600:59, 1 |
|
1A40:5A |
SubIndex 090 |
90. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x5A (Slave 12 Inputs__Slave 12A, DI1)) |
UINT32 |
RO |
0xF600:5A, 1 |
|
1A40:5B |
SubIndex 091 |
91. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x5B (Slave 12 Inputs__Slave 12A, DI2)) |
UINT32 |
RO |
0xF600:5B, 1 |
|
1A40:5C |
SubIndex 092 |
92. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x5C (Slave 12 Inputs__Slave 12A, DI3)) |
UINT32 |
RO |
0xF600:5C, 1 |
|
1A40:5D |
SubIndex 093 |
93. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x5D (Slave 12 Inputs__Slave 12B, DI0)) |
UINT32 |
RO |
0xF600:5D, 1 |
|
1A40:5E |
SubIndex 094 |
94. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x5E (Slave 12 Inputs__Slave 12B, DI1)) |
UINT32 |
RO |
0xF600:5E, 1 |
|
1A40:5F |
SubIndex 095 |
95. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x5F (Slave 12 Inputs__Slave 12B, DI2)) |
UINT32 |
RO |
0xF600:5F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:60 |
SubIndex 096 |
96. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x60 (Slave 12 Inputs__Slave 12B, DI3)) |
UINT32 |
RO |
0xF600:60, 1 |
|
1A40:61 |
SubIndex 097 |
97. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x61 (Slave 13 Inputs__Slave 13A, DI0)) |
UINT32 |
RO |
0xF600:61, 1 |
|
1A40:62 |
SubIndex 098 |
98. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x62 (Slave 13 Inputs__Slave 13A, DI1)) |
UINT32 |
RO |
0xF600:62, 1 |
|
1A40:63 |
SubIndex 099 |
99. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x63 (Slave 13 Inputs__Slave 13A, DI2)) |
UINT32 |
RO |
0xF600:63, 1 |
|
1A40:64 |
SubIndex 100 |
100. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x64 (Slave 13 Inputs__Slave 13A, DI3)) |
UINT32 |
RO |
0xF600:64, 1 |
|
1A40:65 |
SubIndex 101 |
101. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x65 (Slave 13 Inputs__Slave 13B, DI0)) |
UINT32 |
RO |
0xF600:65, 1 |
|
1A40:66 |
SubIndex 102 |
102. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x66 (Slave 13 Inputs__Slave 13B, DI1)) |
UINT32 |
RO |
0xF600:66, 1 |
|
1A40:67 |
SubIndex 103 |
103. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x67 (Slave 13 Inputs__Slave 13B, DI2)) |
UINT32 |
RO |
0xF600:67, 1 |
|
1A40:68 |
SubIndex 104 |
104. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x68 (Slave 13 Inputs__Slave 13B, DI3)) |
UINT32 |
RO |
0xF600:68, 1 |
|
1A40:69 |
SubIndex 105 |
105. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x69 (Slave 14 Inputs__Slave 14A, DI0)) |
UINT32 |
RO |
0xF600:69, 1 |
|
1A40:6A |
SubIndex 106 |
106. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x6A (Slave 14 Inputs__Slave 14A, DI1)) |
UINT32 |
RO |
0xF600:6A, 1 |
|
1A40:6B |
SubIndex 107 |
107. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x6B (Slave 14 Inputs__Slave 14A, DI2)) |
UINT32 |
RO |
0xF600:6B, 1 |
|
1A40:6C |
SubIndex 108 |
108. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x6C (Slave 14 Inputs__Slave 14A, DI3)) |
UINT32 |
RO |
0xF600:6C, 1 |
|
1A40:6D |
SubIndex 109 |
109. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x6D (Slave 14 Inputs__Slave 14B, DI0)) |
UINT32 |
RO |
0xF600:6D, 1 |
|
1A40:6E |
SubIndex 110 |
110. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x6E (Slave 14 Inputs__Slave 14B, DI1)) |
UINT32 |
RO |
0xF600:6E, 1 |
|
1A40:6F |
SubIndex 111 |
111. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x6F (Slave 14 Inputs__Slave 14B, DI2)) |
UINT32 |
RO |
0xF600:6F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:70 |
SubIndex 112 |
112. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x70 (Slave 14 Inputs__Slave 14B, DI3)) |
UINT32 |
RO |
0xF600:70, 1 |
|
1A40:71 |
SubIndex 113 |
113. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x71 (Slave 15 Inputs__Slave 15A, DI0)) |
UINT32 |
RO |
0xF600:71, 1 |
|
1A40:72 |
SubIndex 114 |
114. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x72 (Slave 15 Inputs__Slave 15A, DI1)) |
UINT32 |
RO |
0xF600:72, 1 |
|
1A40:73 |
SubIndex 115 |
115. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x73 (Slave 15 Inputs__Slave 15A, DI2)) |
UINT32 |
RO |
0xF600:73, 1 |
|
1A40:74 |
SubIndex 116 |
116. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x74 (Slave 15 Inputs__Slave 15A, DI3)) |
UINT32 |
RO |
0xF600:74, 1 |
|
1A40:75 |
SubIndex 117 |
117. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x75 (Slave 15 Inputs__Slave 15B, DI0)) |
UINT32 |
RO |
0xF600:75, 1 |
|
1A40:76 |
SubIndex 118 |
118. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x76 (Slave 15 Inputs__Slave 15B, DI1)) |
UINT32 |
RO |
0xF600:76, 1 |
|
1A40:77 |
SubIndex 119 |
119. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x77 (Slave 15 Inputs__Slave 15B, DI2)) |
UINT32 |
RO |
0xF600:77, 1 |
|
1A40:78 |
SubIndex 120 |
120. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x78 (Slave 15 Inputs__Slave 15B, DI3)) |
UINT32 |
RO |
0xF600:78, 1 |
|
1A40:79 |
SubIndex 121 |
121. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x79 (Slave 16 Inputs__Slave 16A, DI0)) |
UINT32 |
RO |
0xF600:79, 1 |
|
1A40:7A |
SubIndex 122 |
122. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x7A (Slave 16 Inputs__Slave 16A, DI1)) |
UINT32 |
RO |
0xF600:7A, 1 |
|
1A40:7B |
SubIndex 123 |
123. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x7B (Slave 16 Inputs__Slave 16A, DI2)) |
UINT32 |
RO |
0xF600:7B, 1 |
|
1A40:7C |
SubIndex 124 |
124. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x7C (Slave 16 Inputs__Slave 16A, DI3)) |
UINT32 |
RO |
0xF600:7C, 1 |
|
1A40:7D |
SubIndex 125 |
125. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x7D (Slave 16 Inputs__Slave 16B, DI0)) |
UINT32 |
RO |
0xF600:7D, 1 |
|
1A40:7E |
SubIndex 126 |
126. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x7E (Slave 16 Inputs__Slave 16B, DI1)) |
UINT32 |
RO |
0xF600:7E, 1 |
|
1A40:7F |
SubIndex 127 |
127. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x7F (Slave 16 Inputs__Slave 16B, DI2)) |
UINT32 |
RO |
0xF600:7F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:80 |
SubIndex 128 |
128. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x80 (Slave 16 Inputs__Slave 16B, DI3)) |
UINT32 |
RO |
0xF600:80, 1 |
|
1A40:81 |
SubIndex 129 |
129. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x81 (Slave 17 Inputs__Slave 17A, DI0)) |
UINT32 |
RO |
0xF600:81, 1 |
|
1A40:82 |
SubIndex 130 |
130. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x82 (Slave 17 Inputs__Slave 17A, DI1)) |
UINT32 |
RO |
0xF600:82, 1 |
|
1A40:83 |
SubIndex 131 |
131. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x83 (Slave 17 Inputs__Slave 17A, DI2)) |
UINT32 |
RO |
0xF600:83, 1 |
|
1A40:84 |
SubIndex 132 |
132. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x84 (Slave 17 Inputs__Slave 17A, DI3)) |
UINT32 |
RO |
0xF600:84, 1 |
|
1A40:85 |
SubIndex 133 |
133. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x85 (Slave 17 Inputs__Slave 17B, DI0)) |
UINT32 |
RO |
0xF600:85, 1 |
|
1A40:86 |
SubIndex 134 |
134. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x86 (Slave 17 Inputs__Slave 17B, DI1)) |
UINT32 |
RO |
0xF600:86, 1 |
|
1A40:87 |
SubIndex 135 |
135. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x87 (Slave 17 Inputs__Slave 17B, DI2)) |
UINT32 |
RO |
0xF600:87, 1 |
|
1A40:88 |
SubIndex 136 |
136. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x88 (Slave 17 Inputs__Slave 17B, DI3)) |
UINT32 |
RO |
0xF600:88, 1 |
|
1A40:89 |
SubIndex 137 |
137. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x89 (Slave 18 Inputs__Slave 18A, DI0)) |
UINT32 |
RO |
0xF600:89, 1 |
|
1A40:8A |
SubIndex 138 |
138. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x8A (Slave 18 Inputs__Slave 18A, DI1)) |
UINT32 |
RO |
0xF600:8A, 1 |
|
1A40:8B |
SubIndex 139 |
139. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x8B (Slave 18 Inputs__Slave 18A, DI2)) |
UINT32 |
RO |
0xF600:8B, 1 |
|
1A40:8C |
SubIndex 140 |
140. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x8C (Slave 18 Inputs__Slave 18A, DI3)) |
UINT32 |
RO |
0xF600:8C, 1 |
|
1A40:8D |
SubIndex 141 |
141. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x8D (Slave 18 Inputs__Slave 18B, DI0)) |
UINT32 |
RO |
0xF600:8D, 1 |
|
1A40:8E |
SubIndex 142 |
142. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x8E (Slave 18 Inputs__Slave 18B, DI1)) |
UINT32 |
RO |
0xF600:8E, 1 |
|
1A40:8F |
SubIndex 143 |
143. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x8F (Slave 18 Inputs__Slave 18B, DI2)) |
UINT32 |
RO |
0xF600:8F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:90 |
SubIndex 144 |
144. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x90 (Slave 18 Inputs__Slave 18B, DI3)) |
UINT32 |
RO |
0xF600:90, 1 |
|
1A40:91 |
SubIndex 145 |
145. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x91 (Slave 19 Inputs__Slave 19A, DI0)) |
UINT32 |
RO |
0xF600:91, 1 |
|
1A40:92 |
SubIndex 146 |
146. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x92 (Slave 19 Inputs__Slave 19A, DI1)) |
UINT32 |
RO |
0xF600:92, 1 |
|
1A40:93 |
SubIndex 147 |
147. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x93 (Slave 19 Inputs__Slave 19A, DI2)) |
UINT32 |
RO |
0xF600:93, 1 |
|
1A40:94 |
SubIndex 148 |
148. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x94 (Slave 19 Inputs__Slave 19A, DI3)) |
UINT32 |
RO |
0xF600:94, 1 |
|
1A40:95 |
SubIndex 149 |
149. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x95 (Slave 19 Inputs__Slave 19B, DI0)) |
UINT32 |
RO |
0xF600:95, 1 |
|
1A40:96 |
SubIndex 150 |
150. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x96 (Slave 19 Inputs__Slave 19B, DI1)) |
UINT32 |
RO |
0xF600:96, 1 |
|
1A40:97 |
SubIndex 151 |
151. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x97 (Slave 19 Inputs__Slave 19B, DI2)) |
UINT32 |
RO |
0xF600:97, 1 |
|
1A40:98 |
SubIndex 152 |
152. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x98 (Slave 19 Inputs__Slave 19B, DI3)) |
UINT32 |
RO |
0xF600:98, 1 |
|
1A40:99 |
SubIndex 153 |
153. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x99 (Slave 20 Inputs__Slave 20A, DI0)) |
UINT32 |
RO |
0xF600:99, 1 |
|
1A40:9A |
SubIndex 154 |
154. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x9A (Slave 20 Inputs__Slave 20A, DI1)) |
UINT32 |
RO |
0xF600:9A, 1 |
|
1A40:9B |
SubIndex 155 |
155. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x9B (Slave 20 Inputs__Slave 20A, DI2)) |
UINT32 |
RO |
0xF600:9B, 1 |
|
1A40:9C |
SubIndex 156 |
156. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x9C (Slave 20 Inputs__Slave 20A, DI3)) |
UINT32 |
RO |
0xF600:9C, 1 |
|
1A40:9D |
SubIndex 157 |
157. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x9D (Slave 20 Inputs__Slave 20B, DI0)) |
UINT32 |
RO |
0xF600:9D, 1 |
|
1A40:9E |
SubIndex 158 |
158. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x9E (Slave 20 Inputs__Slave 20B, DI1)) |
UINT32 |
RO |
0xF600:9E, 1 |
|
1A40:9F |
SubIndex 159 |
159. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0x9F (Slave 20 Inputs__Slave 20B, DI2)) |
UINT32 |
RO |
0xF600:9F, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:A0 |
SubIndex 160 |
160. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA0 (Slave 20 Inputs__Slave 20B, DI3)) |
UINT32 |
RO |
0xF600:A0, 1 |
|
1A40:A1 |
SubIndex 161 |
161. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA1 (Slave 21 Inputs__Slave 21A, DI0)) |
UINT32 |
RO |
0xF600:A1, 1 |
|
1A40:A2 |
SubIndex 162 |
162. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA2 (Slave 21 Inputs__Slave 21A, DI1)) |
UINT32 |
RO |
0xF600:A2, 1 |
|
1A40:A3 |
SubIndex 163 |
163. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA3 (Slave 21 Inputs__Slave 21A, DI2)) |
UINT32 |
RO |
0xF600:A3, 1 |
|
1A40:A4 |
SubIndex 164 |
164. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA4 (Slave 21 Inputs__Slave 21A, DI3)) |
UINT32 |
RO |
0xF600:A4, 1 |
|
1A40:A5 |
SubIndex 165 |
165. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA5 (Slave 21 Inputs__Slave 21B, DI0)) |
UINT32 |
RO |
0xF600:A5, 1 |
|
1A40:A6 |
SubIndex 166 |
166. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA6 (Slave 21 Inputs__Slave 21B, DI1)) |
UINT32 |
RO |
0xF600:A6, 1 |
|
1A40:A7 |
SubIndex 167 |
167. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA7 (Slave 21 Inputs__Slave 21B, DI2)) |
UINT32 |
RO |
0xF600:A7, 1 |
|
1A40:A8 |
SubIndex 168 |
168. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA8 (Slave 21 Inputs__Slave 21B, DI3)) |
UINT32 |
RO |
0xF600:A8, 1 |
|
1A40:A9 |
SubIndex 169 |
169. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xA9 (Slave 22 Inputs__Slave 22A, DI0)) |
UINT32 |
RO |
0xF600:A9, 1 |
|
1A40:AA |
SubIndex 170 |
170. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xAA (Slave 22 Inputs__Slave 22A, DI1)) |
UINT32 |
RO |
0xF600:AA, 1 |
|
1A40:AB |
SubIndex 171 |
171. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xAB (Slave 22 Inputs__Slave 22A, DI2)) |
UINT32 |
RO |
0xF600:AB, 1 |
|
1A40:AC |
SubIndex 172 |
172. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xAC (Slave 22 Inputs__Slave 22A, DI3)) |
UINT32 |
RO |
0xF600:AC, 1 |
|
1A40:AD |
SubIndex 173 |
173. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xAD (Slave 22 Inputs__Slave 22B, DI0)) |
UINT32 |
RO |
0xF600:AD, 1 |
|
1A40:AE |
SubIndex 174 |
174. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xAE (Slave 22 Inputs__Slave 22B, DI1)) |
UINT32 |
RO |
0xF600:AE, 1 |
|
1A40:AF |
SubIndex 175 |
175. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xAF (Slave 22 Inputs__Slave 22B, DI2)) |
UINT32 |
RO |
0xF600:AF, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:B0 |
SubIndex 176 |
176. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB0 (Slave 22 Inputs__Slave 22B, DI3)) |
UINT32 |
RO |
0xF600:B0, 1 |
|
1A40:B1 |
SubIndex 177 |
177. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB1 (Slave 23 Inputs__Slave 23A, DI0)) |
UINT32 |
RO |
0xF600:B1, 1 |
|
1A40:B2 |
SubIndex 178 |
178. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB2 (Slave 23 Inputs__Slave 23A, DI1)) |
UINT32 |
RO |
0xF600:B2, 1 |
|
1A40:B3 |
SubIndex 179 |
179. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB3 (Slave 23 Inputs__Slave 23A, DI2)) |
UINT32 |
RO |
0xF600:B3, 1 |
|
1A40:B4 |
SubIndex 180 |
180. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB4 (Slave 23 Inputs__Slave 23A, DI3)) |
UINT32 |
RO |
0xF600:B4, 1 |
|
1A40:B5 |
SubIndex 181 |
181. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB5 (Slave 23 Inputs__Slave 23B, DI0)) |
UINT32 |
RO |
0xF600:B5, 1 |
|
1A40:B6 |
SubIndex 182 |
182. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB6 (Slave 23 Inputs__Slave 23B, DI1)) |
UINT32 |
RO |
0xF600:B6, 1 |
|
1A40:B7 |
SubIndex 183 |
183. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB7 (Slave 23 Inputs__Slave 23B, DI2)) |
UINT32 |
RO |
0xF600:B7, 1 |
|
1A40:B8 |
SubIndex 184 |
184. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB8 (Slave 23 Inputs__Slave 23B, DI3)) |
UINT32 |
RO |
0xF600:B8, 1 |
|
1A40:B9 |
SubIndex 185 |
185. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xB9 (Slave 24 Inputs__Slave 24A, DI0)) |
UINT32 |
RO |
0xF600:B9, 1 |
|
1A40:BA |
SubIndex 186 |
186. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xBA (Slave 24 Inputs__Slave 24A, DI1)) |
UINT32 |
RO |
0xF600:BA, 1 |
|
1A40:BB |
SubIndex 187 |
187. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xBB (Slave 24 Inputs__Slave 24A, DI2)) |
UINT32 |
RO |
0xF600:BB, 1 |
|
1A40:BC |
SubIndex 188 |
188. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xBC (Slave 24 Inputs__Slave 24A, DI3)) |
UINT32 |
RO |
0xF600:BC, 1 |
|
1A40:BD |
SubIndex 189 |
189. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xBD (Slave 24 Inputs__Slave 24B, DI0)) |
UINT32 |
RO |
0xF600:BD, 1 |
|
1A40:BE |
SubIndex 190 |
190. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xBE (Slave 24 Inputs__Slave 24B, DI1)) |
UINT32 |
RO |
0xF600:BE, 1 |
|
1A40:BF |
SubIndex 191 |
191. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xBF (Slave 24 Inputs__Slave 24B, DI2)) |
UINT32 |
RO |
0xF600:BF, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:C0 |
SubIndex 192 |
192. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC0 (Slave 24 Inputs__Slave 24B, DI3)) |
UINT32 |
RO |
0xF600:C0, 1 |
|
1A40:C1 |
SubIndex 193 |
193. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC1 (Slave 25 Inputs__Slave 25A, DI0)) |
UINT32 |
RO |
0xF600:C1, 1 |
|
1A40:C2 |
SubIndex 194 |
194. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC2 (Slave 25 Inputs__Slave 25A, DI1)) |
UINT32 |
RO |
0xF600:C2, 1 |
|
1A40:C3 |
SubIndex 195 |
195. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC3 (Slave 25 Inputs__Slave 25A, DI2)) |
UINT32 |
RO |
0xF600:C3, 1 |
|
1A40:C4 |
SubIndex 196 |
196. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC4 (Slave 25 Inputs__Slave 25A, DI3)) |
UINT32 |
RO |
0xF600:C4, 1 |
|
1A40:C5 |
SubIndex 197 |
197. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC5 (Slave 25 Inputs__Slave 25B, DI0)) |
UINT32 |
RO |
0xF600:C5, 1 |
|
1A40:C6 |
SubIndex 198 |
198. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC6 (Slave 25 Inputs__Slave 25B, DI1)) |
UINT32 |
RO |
0xF600:C6, 1 |
|
1A40:C7 |
SubIndex 199 |
199. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC7 (Slave 25 Inputs__Slave 25B, DI2)) |
UINT32 |
RO |
0xF600:C7, 1 |
|
1A40:C8 |
SubIndex 200 |
200. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC8 (Slave 25 Inputs__Slave 25B, DI3)) |
UINT32 |
RO |
0xF600:C8, 1 |
|
1A40:C9 |
SubIndex 201 |
201. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xC9 (Slave 26 Inputs__Slave 26A, DI0)) |
UINT32 |
RO |
0xF600:C9, 1 |
|
1A40:CA |
SubIndex 202 |
202. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xCA (Slave 26 Inputs__Slave 26A, DI1)) |
UINT32 |
RO |
0xF600:CA, 1 |
|
1A40:CB |
SubIndex 203 |
203. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xCB (Slave 26 Inputs__Slave 26A, DI2)) |
UINT32 |
RO |
0xF600:CB, 1 |
|
1A40:CC |
SubIndex 204 |
204. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xCC (Slave 26 Inputs__Slave 26A, DI3)) |
UINT32 |
RO |
0xF600:CC, 1 |
|
1A40:CD |
SubIndex 205 |
205. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xCD (Slave 26 Inputs__Slave 26B, DI0)) |
UINT32 |
RO |
0xF600:CD, 1 |
|
1A40:CE |
SubIndex 206 |
206. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xCE (Slave 26 Inputs__Slave 26B, DI1)) |
UINT32 |
RO |
0xF600:CE, 1 |
|
1A40:CF |
SubIndex 207 |
207. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xCF (Slave 26 Inputs__Slave 26B, DI2)) |
UINT32 |
RO |
0xF600:CF, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:D0 |
SubIndex 208 |
208. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD0 (Slave 26 Inputs__Slave 26B, DI3)) |
UINT32 |
RO |
0xF600:D0, 1 |
|
1A40:D1 |
SubIndex 209 |
209. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD1 (Slave 27 Inputs__Slave 27A, DI0)) |
UINT32 |
RO |
0xF600:D1, 1 |
|
1A40:D2 |
SubIndex 210 |
210. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD2 (Slave 27 Inputs__Slave 27A, DI1)) |
UINT32 |
RO |
0xF600:D2, 1 |
|
1A40:D3 |
SubIndex 211 |
211. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD3 (Slave 27 Inputs__Slave 27A, DI2)) |
UINT32 |
RO |
0xF600:D3, 1 |
|
1A40:D4 |
SubIndex 212 |
212. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD4 (Slave 27 Inputs__Slave 27A, DI3)) |
UINT32 |
RO |
0xF600:D4, 1 |
|
1A40:D5 |
SubIndex 213 |
213. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD5 (Slave 27 Inputs__Slave 27B, DI0)) |
UINT32 |
RO |
0xF600:D5, 1 |
|
1A40:D6 |
SubIndex 214 |
214. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD6 (Slave 27 Inputs__Slave 27B, DI1)) |
UINT32 |
RO |
0xF600:D6, 1 |
|
1A40:D7 |
SubIndex 215 |
215. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD7 (Slave 27 Inputs__Slave 27B, DI2)) |
UINT32 |
RO |
0xF600:D7, 1 |
|
1A40:D8 |
SubIndex 216 |
216. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD8 (Slave 27 Inputs__Slave 27B, DI3)) |
UINT32 |
RO |
0xF600:D8, 1 |
|
1A40:D9 |
SubIndex 217 |
217. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xD9 (Slave 28 Inputs__Slave 28A, DI0)) |
UINT32 |
RO |
0xF600:D9, 1 |
|
1A40:DA |
SubIndex 218 |
218. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xDA (Slave 28 Inputs__Slave 28A, DI1)) |
UINT32 |
RO |
0xF600:DA, 1 |
|
1A40:DB |
SubIndex 219 |
219. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xDB (Slave 28 Inputs__Slave 28A, DI2)) |
UINT32 |
RO |
0xF600:DB, 1 |
|
1A40:DC |
SubIndex 220 |
220. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xDC (Slave 28 Inputs__Slave 28A, DI3)) |
UINT32 |
RO |
0xF600:DC, 1 |
|
1A40:DD |
SubIndex 221 |
221. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xDD (Slave 28 Inputs__Slave 28B, DI0)) |
UINT32 |
RO |
0xF600:DD, 1 |
|
1A40:DE |
SubIndex 222 |
222. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xDE (Slave 28 Inputs__Slave 28B, DI1)) |
UINT32 |
RO |
0xF600:DE, 1 |
|
1A40:DF |
SubIndex 223 |
223. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xDF (Slave 28 Inputs__Slave 28B, DI2)) |
UINT32 |
RO |
0xF600:DF, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:E0 |
SubIndex 224 |
224. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE0 (Slave 28 Inputs__Slave 28B, DI3)) |
UINT32 |
RO |
0xF600:E0, 1 |
|
1A40:E1 |
SubIndex 225 |
225. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE1 (Slave 29 Inputs__Slave 29A, DI0)) |
UINT32 |
RO |
0xF600:E1, 1 |
|
1A40:E2 |
SubIndex 226 |
226. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE2 (Slave 29 Inputs__Slave 29A, DI1)) |
UINT32 |
RO |
0xF600:E2, 1 |
|
1A40:E3 |
SubIndex 227 |
227. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE3 (Slave 29 Inputs__Slave 29A, DI2)) |
UINT32 |
RO |
0xF600:E3, 1 |
|
1A40:E4 |
SubIndex 228 |
228. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE4 (Slave 29 Inputs__Slave 29A, DI3)) |
UINT32 |
RO |
0xF600:E4, 1 |
|
1A40:E5 |
SubIndex 229 |
229. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE5 (Slave 29 Inputs__Slave 29B, DI0)) |
UINT32 |
RO |
0xF600:E5, 1 |
|
1A40:E6 |
SubIndex 230 |
230. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE6 (Slave 29 Inputs__Slave 29B, DI1)) |
UINT32 |
RO |
0xF600:E6, 1 |
|
1A40:E7 |
SubIndex 231 |
231. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE7 (Slave 29 Inputs__Slave 29B, DI2)) |
UINT32 |
RO |
0xF600:E7, 1 |
|
1A40:E8 |
SubIndex 232 |
232. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE8 (Slave 29 Inputs__Slave 29B, DI3)) |
UINT32 |
RO |
0xF600:E8, 1 |
|
1A40:E9 |
SubIndex 233 |
233. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xE9 (Slave 30 Inputs__Slave 30A, DI0)) |
UINT32 |
RO |
0xF600:E9, 1 |
|
1A40:EA |
SubIndex 234 |
234. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xEA (Slave 30 Inputs__Slave 30A, DI1)) |
UINT32 |
RO |
0xF600:EA, 1 |
|
1A40:EB |
SubIndex 235 |
235. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xEB (Slave 30 Inputs__Slave 30A, DI2)) |
UINT32 |
RO |
0xF600:EB, 1 |
|
1A40:EC |
SubIndex 236 |
236. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xEC (Slave 30 Inputs__Slave 30A, DI3)) |
UINT32 |
RO |
0xF600:EC, 1 |
|
1A40:ED |
SubIndex 237 |
237. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xED (Slave 30 Inputs__Slave 30B, DI0)) |
UINT32 |
RO |
0xF600:ED, 1 |
|
1A40:EE |
SubIndex 238 |
238. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xEE (Slave 30 Inputs__Slave 30B, DI1)) |
UINT32 |
RO |
0xF600:EE, 1 |
|
1A40:EF |
SubIndex 239 |
239. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xEF (Slave 30 Inputs__Slave 30B, DI2)) |
UINT32 |
RO |
0xF600:EF, 1 |
Index 1A40 ASI TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A40:F0 |
SubIndex 240 |
240. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF0 (Slave 30 Inputs__Slave 30B, DI3)) |
UINT32 |
RO |
0xF600:F0, 1 |
|
1A40:F1 |
SubIndex 241 |
241. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF1 (Slave 31 Inputs__Slave 31A, DI0)) |
UINT32 |
RO |
0xF600:F1, 1 |
|
1A40:F2 |
SubIndex 242 |
242. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF2 (Slave 31 Inputs__Slave 31A, DI1)) |
UINT32 |
RO |
0xF600:F2, 1 |
|
1A40:F3 |
SubIndex 243 |
243. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF3 (Slave 31 Inputs__Slave 31A, DI2)) |
UINT32 |
RO |
0xF600:F3, 1 |
|
1A40:F4 |
SubIndex 244 |
244. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF4 (Slave 31 Inputs__Slave 31A, DI3)) |
UINT32 |
RO |
0xF600:F4, 1 |
|
1A40:F5 |
SubIndex 245 |
245. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF5 (Slave 31 Inputs__Slave 31B, DI0)) |
UINT32 |
RO |
0xF600:F5, 1 |
|
1A40:F6 |
SubIndex 246 |
246. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF6 (Slave 31 Inputs__Slave 31B, DI1)) |
UINT32 |
RO |
0xF600:F6, 1 |
|
1A40:F7 |
SubIndex 247 |
247. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF7 (Slave 31 Inputs__Slave 31B, DI2)) |
UINT32 |
RO |
0xF600:F7, 1 |
|
1A40:F8 |
SubIndex 248 |
248. PDO Mapping entry (object 0xF600 (ASI Digital Inputs), entry 0xF8 (Slave 31 Inputs__Slave 31B, DI3)) |
UINT32 |
RO |
0xF600:F8, 1 |
Index 1A80 ASI TxPDO-Map Status
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A80:0 |
ASI TxPDO-Map Status |
PDO Mapping TxPDO 129 |
UINT8 |
RO |
0x0D (13dec) |
|
1A80:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x01 (Configuration okay)) |
UINT32 |
RO |
0xF100:01, 1 |
|
1A80:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x02 (Power Fail)) |
UINT32 |
RO |
0xF100:02, 1 |
|
1A80:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x03 (Auto addressing mode enabled)) |
UINT32 |
RO |
0xF100:03, 1 |
|
1A80:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x04 (Auto addressing mode available)) |
UINT32 |
RO |
0xF100:04, 1 |
|
1A80:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x05 (Protected mode active)) |
UINT32 |
RO |
0xF100:05, 1 |
|
1A80:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x06 (Slave with address 0 found)) |
UINT32 |
RO |
0xF100:06, 1 |
|
1A80:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x07 (Offline Ready)) |
UINT32 |
RO |
0xF100:07, 1 |
|
1A80:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x08 (Normal Operation)) |
UINT32 |
RO |
0xF100:08, 1 |
|
1A80:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x09 (ASI phase)) |
UINT32 |
RO |
0xF100:09, 3 |
|
1A80:0A |
SubIndex 010 |
10. PDO Mapping entry (2 bits align) |
UINT32 |
RO |
0x0000:00, 2 |
|
1A80:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x0E (Sync error)) |
UINT32 |
RO |
0xF100:0E, 1 |
|
1A80:0C |
SubIndex 012 |
12. PDO Mapping entry (1 bits align) |
UINT32 |
RO |
0x0000:00, 1 |
|
1A80:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0xF100 (ASI Status), entry 0x10 (TxPDO Toggle)) |
UINT32 |
RO |
0xF100:10, 1 |
Index 1A81 ASI TxPDO-Map LDS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A81:0 |
ASI TxPDO-Map LDS |
PDO Mapping TxPDO 130 |
UINT8 |
RO |
0x40 (64dec) |
|
1A81:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x01 (Slave 0)) |
UINT32 |
RO |
0xF101:01, 1 |
|
1A81:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x02 (Slave 1A)) |
UINT32 |
RO |
0xF101:02, 1 |
|
1A81:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x03 (Slave 2A)) |
UINT32 |
RO |
0xF101:03, 1 |
|
1A81:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x04 (Slave 3A)) |
UINT32 |
RO |
0xF101:04, 1 |
|
1A81:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x05 (Slave 4A)) |
UINT32 |
RO |
0xF101:05, 1 |
|
1A81:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x06 (Slave 5A)) |
UINT32 |
RO |
0xF101:06, 1 |
|
1A81:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x07 (Slave 6A)) |
UINT32 |
RO |
0xF101:07, 1 |
|
1A81:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x08 (Slave 7A)) |
UINT32 |
RO |
0xF101:08, 1 |
|
1A81:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x09 (Slave 8A)) |
UINT32 |
RO |
0xF101:09, 1 |
|
1A81:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x0A (Slave 9A)) |
UINT32 |
RO |
0xF101:0A, 1 |
|
1A81:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x0B (Slave 10A)) |
UINT32 |
RO |
0xF101:0B, 1 |
|
1A81:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x0C (Slave 11A)) |
UINT32 |
RO |
0xF101:0C, 1 |
|
1A81:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x0D (Slave 12A)) |
UINT32 |
RO |
0xF101:0D, 1 |
|
1A81:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x0E (Slave 13A)) |
UINT32 |
RO |
0xF101:0E, 1 |
|
1A81:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x0F (Slave 14A)) |
UINT32 |
RO |
0xF101:0F, 1 |
Index 1A81 ASI TxPDO-Map LDS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A81:10 |
SubIndex 016 |
16. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x10 (Slave 15A)) |
UINT32 |
RO |
0xF101:10, 1 |
|
1A81:11 |
SubIndex 017 |
17. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x11 (Slave 16A)) |
UINT32 |
RO |
0xF101:11, 1 |
|
1A81:12 |
SubIndex 018 |
18. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x12 (Slave 17A)) |
UINT32 |
RO |
0xF101:12, 1 |
|
1A81:13 |
SubIndex 019 |
19. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x13 (Slave 18A)) |
UINT32 |
RO |
0xF101:13, 1 |
|
1A81:14 |
SubIndex 020 |
20. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x14 (Slave 19A)) |
UINT32 |
RO |
0xF101:14, 1 |
|
1A81:15 |
SubIndex 021 |
21. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x15 (Slave 20A)) |
UINT32 |
RO |
0xF101:15, 1 |
|
1A81:16 |
SubIndex 022 |
22. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x16 (Slave 21A)) |
UINT32 |
RO |
0xF101:16, 1 |
|
1A81:17 |
SubIndex 023 |
23. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x17 (Slave 22A)) |
UINT32 |
RO |
0xF101:17, 1 |
|
1A81:18 |
SubIndex 024 |
24. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x18 (Slave 23A)) |
UINT32 |
RO |
0xF101:18, 1 |
|
1A81:19 |
SubIndex 025 |
25. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x19 (Slave 24A)) |
UINT32 |
RO |
0xF101:19, 1 |
|
1A81:1A |
SubIndex 026 |
26. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x1A (Slave 25A)) |
UINT32 |
RO |
0xF101:1A, 1 |
|
1A81:1B |
SubIndex 027 |
27. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x1B (Slave 26A)) |
UINT32 |
RO |
0xF101:1B, 1 |
|
1A81:1C |
SubIndex 028 |
28. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x1C (Slave 27A)) |
UINT32 |
RO |
0xF101:1C, 1 |
|
1A81:1D |
SubIndex 029 |
29. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x1D (Slave 28A)) |
UINT32 |
RO |
0xF101:1D, 1 |
|
1A81:1E |
SubIndex 030 |
30. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x1E (Slave 29A)) |
UINT32 |
RO |
0xF101:1E, 1 |
|
1A81:1F |
SubIndex 031 |
31. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x1F (Slave 30A)) |
UINT32 |
RO |
0xF101:1F, 1 |
Index 1A81 ASI TxPDO-Map LDS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A81:20 |
SubIndex 032 |
32. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x20 (Slave 31A)) |
UINT32 |
RO |
0xF101:20, 1 |
|
1A81:21 |
SubIndex 033 |
33. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x21 (Slave 1B)) |
UINT32 |
RO |
0xF101:21, 1 |
|
1A81:22 |
SubIndex 034 |
34. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x22 (Slave 2B)) |
UINT32 |
RO |
0xF101:22, 1 |
|
1A81:23 |
SubIndex 035 |
35. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x23 (Slave 3B)) |
UINT32 |
RO |
0xF101:23, 1 |
|
1A81:24 |
SubIndex 036 |
36. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x24 (Slave 4B)) |
UINT32 |
RO |
0xF101:24, 1 |
|
1A81:25 |
SubIndex 037 |
37. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x25 (Slave 5B)) |
UINT32 |
RO |
0xF101:25, 1 |
|
1A81:26 |
SubIndex 038 |
38. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x26 (Slave 6B)) |
UINT32 |
RO |
0xF101:26, 1 |
|
1A81:27 |
SubIndex 039 |
39. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x27 (Slave 7B)) |
UINT32 |
RO |
0xF101:27, 1 |
|
1A81:28 |
SubIndex 040 |
40. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x28 (Slave 8B)) |
UINT32 |
RO |
0xF101:28, 1 |
|
1A81:29 |
SubIndex 041 |
41. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x29 (Slave 9B)) |
UINT32 |
RO |
0xF101:29, 1 |
|
1A81:2A |
SubIndex 042 |
42. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x2A (Slave 10B)) |
UINT32 |
RO |
0xF101:2A, 1 |
|
1A81:2B |
SubIndex 043 |
43. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x2B (Slave 11B)) |
UINT32 |
RO |
0xF101:2B, 1 |
|
1A81:2C |
SubIndex 044 |
44. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x2C (Slave 12B)) |
UINT32 |
RO |
0xF101:2C, 1 |
|
1A81:2D |
SubIndex 045 |
45. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x2D (Slave 13B)) |
UINT32 |
RO |
0xF101:2D, 1 |
|
1A81:2E |
SubIndex 046 |
46. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x2E (Slave 14B)) |
UINT32 |
RO |
0xF101:2E, 1 |
|
1A81:2F |
SubIndex 047 |
47. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x2F (Slave 15B)) |
UINT32 |
RO |
0xF101:2F, 1 |
Index 1A81 ASI TxPDO-Map LDS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A81:30 |
SubIndex 048 |
48. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x30 (Slave 16B)) |
UINT32 |
RO |
0xF101:30, 1 |
|
1A81:31 |
SubIndex 049 |
49. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x31 (Slave 17B)) |
UINT32 |
RO |
0xF101:31, 1 |
|
1A81:32 |
SubIndex 050 |
50. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x32 (Slave 18B)) |
UINT32 |
RO |
0xF101:32, 1 |
|
1A81:33 |
SubIndex 051 |
51. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x33 (Slave 19B)) |
UINT32 |
RO |
0xF101:33, 1 |
|
1A81:34 |
SubIndex 052 |
52. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x34 (Slave 20B)) |
UINT32 |
RO |
0xF101:34, 1 |
|
1A81:35 |
SubIndex 053 |
53. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x35 (Slave 21B)) |
UINT32 |
RO |
0xF101:35, 1 |
|
1A81:36 |
SubIndex 054 |
54. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x36 (Slave 22B)) |
UINT32 |
RO |
0xF101:36, 1 |
|
1A81:37 |
SubIndex 055 |
55. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x37 (Slave 23B)) |
UINT32 |
RO |
0xF101:37, 1 |
|
1A81:38 |
SubIndex 056 |
56. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x38 (Slave 24B)) |
UINT32 |
RO |
0xF101:38, 1 |
|
1A81:39 |
SubIndex 057 |
57. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x39 (Slave 25B)) |
UINT32 |
RO |
0xF101:39, 1 |
|
1A81:3A |
SubIndex 058 |
58. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x3A (Slave 26B)) |
UINT32 |
RO |
0xF101:3A, 1 |
|
1A81:3B |
SubIndex 059 |
59. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x3B (Slave 27B)) |
UINT32 |
RO |
0xF101:3B, 1 |
|
1A81:3C |
SubIndex 060 |
60. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x3C (Slave 28B)) |
UINT32 |
RO |
0xF101:3C, 1 |
|
1A81:3D |
SubIndex 061 |
61. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x3D (Slave 29B)) |
UINT32 |
RO |
0xF101:3D, 1 |
|
1A81:3E |
SubIndex 062 |
62. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x3E (Slave 30B)) |
UINT32 |
RO |
0xF101:3E, 1 |
|
1A81:3F |
SubIndex 063 |
63. PDO Mapping entry (object 0xF101 (ASI LDS), entry 0x3F (Slave 31B)) |
UINT32 |
RO |
0xF101:3F, 1 |
|
1A81:40 |
SubIndex 064 |
64. PDO Mapping entry (1 bits align) |
UINT32 |
RO |
0x0000:00, 1 |
Index 1A82 ASI TxPDO-Map LAS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A82:0 |
ASI TxPDO-Map LAS |
PDO Mapping TxPDO 131 |
UINT8 |
RO |
0x40 (64dec) |
|
1A82:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x01 (Slave 0)) |
UINT32 |
RO |
0xF102:01, 1 |
|
1A82:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x02 (Slave 1A)) |
UINT32 |
RO |
0xF102:02, 1 |
|
1A82:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x03 (Slave 2A)) |
UINT32 |
RO |
0xF102:03, 1 |
|
1A82:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x04 (Slave 3A)) |
UINT32 |
RO |
0xF102:04, 1 |
|
1A82:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x05 (Slave 4A)) |
UINT32 |
RO |
0xF102:05, 1 |
|
1A82:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x06 (Slave 5A)) |
UINT32 |
RO |
0xF102:06, 1 |
|
1A82:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x07 (Slave 6A)) |
UINT32 |
RO |
0xF102:07, 1 |
|
1A82:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x08 (Slave 7A)) |
UINT32 |
RO |
0xF102:08, 1 |
|
1A82:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x09 (Slave 8A)) |
UINT32 |
RO |
0xF102:09, 1 |
|
1A82:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x0A (Slave 9A)) |
UINT32 |
RO |
0xF102:0A, 1 |
|
1A82:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x0B (Slave 10A)) |
UINT32 |
RO |
0xF102:0B, 1 |
|
1A82:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x0C (Slave 11A)) |
UINT32 |
RO |
0xF102:0C, 1 |
|
1A82:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x0D (Slave 12A)) |
UINT32 |
RO |
0xF102:0D, 1 |
|
1A82:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x0E (Slave 13A)) |
UINT32 |
RO |
0xF102:0E, 1 |
|
1A82:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x0F (Slave 14A)) |
UINT32 |
RO |
0xF102:0F, 1 |
Index 1A82 ASI TxPDO-Map LAS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A82:10 |
SubIndex 016 |
16. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x10 (Slave 15A)) |
UINT32 |
RO |
0xF102:10, 1 |
|
1A82:11 |
SubIndex 017 |
17. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x11 (Slave 16A)) |
UINT32 |
RO |
0xF102:11, 1 |
|
1A82:12 |
SubIndex 018 |
18. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x12 (Slave 17A)) |
UINT32 |
RO |
0xF102:12, 1 |
|
1A82:13 |
SubIndex 019 |
19. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x13 (Slave 18A)) |
UINT32 |
RO |
0xF102:13, 1 |
|
1A82:14 |
SubIndex 020 |
20. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x14 (Slave 19A)) |
UINT32 |
RO |
0xF102:14, 1 |
|
1A82:15 |
SubIndex 021 |
21. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x15 (Slave 20A)) |
UINT32 |
RO |
0xF102:15, 1 |
|
1A82:16 |
SubIndex 022 |
22. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x16 (Slave 21A)) |
UINT32 |
RO |
0xF102:16, 1 |
|
1A82:17 |
SubIndex 023 |
23. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x17 (Slave 22A)) |
UINT32 |
RO |
0xF102:17, 1 |
|
1A82:18 |
SubIndex 024 |
24. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x18 (Slave 23A)) |
UINT32 |
RO |
0xF102:18, 1 |
|
1A82:19 |
SubIndex 025 |
25. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x19 (Slave 24A)) |
UINT32 |
RO |
0xF102:19, 1 |
|
1A82:1A |
SubIndex 026 |
26. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x1A (Slave 25A)) |
UINT32 |
RO |
0xF102:1A, 1 |
|
1A82:1B |
SubIndex 027 |
27. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x1B (Slave 26A)) |
UINT32 |
RO |
0xF102:1B, 1 |
|
1A82:1C |
SubIndex 028 |
28. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x1C (Slave 27A)) |
UINT32 |
RO |
0xF102:1C, 1 |
|
1A82:1D |
SubIndex 029 |
29. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x1D (Slave 28A)) |
UINT32 |
RO |
0xF102:1D, 1 |
|
1A82:1E |
SubIndex 030 |
30. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x1E (Slave 29A)) |
UINT32 |
RO |
0xF102:1E, 1 |
|
1A82:1F |
SubIndex 031 |
31. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x1F (Slave 30A)) |
UINT32 |
RO |
0xF102:1F, 1 |
Index 1A82 ASI TxPDO-Map LAS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A82:20 |
SubIndex 032 |
32. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x20 (Slave 31A)) |
UINT32 |
RO |
0xF102:20, 1 |
|
1A82:21 |
SubIndex 033 |
33. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x21 (Slave 1B)) |
UINT32 |
RO |
0xF102:21, 1 |
|
1A82:22 |
SubIndex 034 |
34. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x22 (Slave 2B)) |
UINT32 |
RO |
0xF102:22, 1 |
|
1A82:23 |
SubIndex 035 |
35. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x23 (Slave 3B)) |
UINT32 |
RO |
0xF102:23, 1 |
|
1A82:24 |
SubIndex 036 |
36. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x24 (Slave 4B)) |
UINT32 |
RO |
0xF102:24, 1 |
|
1A82:25 |
SubIndex 037 |
37. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x25 (Slave 5B)) |
UINT32 |
RO |
0xF102:25, 1 |
|
1A82:26 |
SubIndex 038 |
38. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x26 (Slave 6B)) |
UINT32 |
RO |
0xF102:26, 1 |
|
1A82:27 |
SubIndex 039 |
39. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x27 (Slave 7B)) |
UINT32 |
RO |
0xF102:27, 1 |
|
1A82:28 |
SubIndex 040 |
40. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x28 (Slave 8B)) |
UINT32 |
RO |
0xF102:28, 1 |
|
1A82:29 |
SubIndex 041 |
41. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x29 (Slave 9B)) |
UINT32 |
RO |
0xF102:29, 1 |
|
1A82:2A |
SubIndex 042 |
42. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x2A (Slave 10B)) |
UINT32 |
RO |
0xF102:2A, 1 |
|
1A82:2B |
SubIndex 043 |
43. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x2B (Slave 11B)) |
UINT32 |
RO |
0xF102:2B, 1 |
|
1A82:2C |
SubIndex 044 |
44. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x2C (Slave 12B)) |
UINT32 |
RO |
0xF102:2C, 1 |
|
1A82:2D |
SubIndex 045 |
45. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x2D (Slave 13B)) |
UINT32 |
RO |
0xF102:2D, 1 |
|
1A82:2E |
SubIndex 046 |
46. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x2E (Slave 14B)) |
UINT32 |
RO |
0xF102:2E, 1 |
|
1A82:2F |
SubIndex 047 |
47. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x2F (Slave 15B)) |
UINT32 |
RO |
0xF102:2F, 1 |
Index 1A82 ASI TxPDO-Map LAS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A82:30 |
SubIndex 048 |
48. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x30 (Slave 16B)) |
UINT32 |
RO |
0xF102:30, 1 |
|
1A82:31 |
SubIndex 049 |
49. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x31 (Slave 17B)) |
UINT32 |
RO |
0xF102:31, 1 |
|
1A82:32 |
SubIndex 050 |
50. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x32 (Slave 18B)) |
UINT32 |
RO |
0xF102:32, 1 |
|
1A82:33 |
SubIndex 051 |
51. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x33 (Slave 19B)) |
UINT32 |
RO |
0xF102:33, 1 |
|
1A82:34 |
SubIndex 052 |
52. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x34 (Slave 20B)) |
UINT32 |
RO |
0xF102:34, 1 |
|
1A82:35 |
SubIndex 053 |
53. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x35 (Slave 21B)) |
UINT32 |
RO |
0xF102:35, 1 |
|
1A82:36 |
SubIndex 054 |
54. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x36 (Slave 22B)) |
UINT32 |
RO |
0xF102:36, 1 |
|
1A82:37 |
SubIndex 055 |
55. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x37 (Slave 23B)) |
UINT32 |
RO |
0xF102:37, 1 |
|
1A82:38 |
SubIndex 056 |
56. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x38 (Slave 24B)) |
UINT32 |
RO |
0xF102:38, 1 |
|
1A82:39 |
SubIndex 057 |
57. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x39 (Slave 25B)) |
UINT32 |
RO |
0xF102:39, 1 |
|
1A82:3A |
SubIndex 058 |
58. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x3A (Slave 26B)) |
UINT32 |
RO |
0xF102:3A, 1 |
|
1A82:3B |
SubIndex 059 |
59. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x3B (Slave 27B)) |
UINT32 |
RO |
0xF102:3B, 1 |
|
1A82:3C |
SubIndex 060 |
60. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x3C (Slave 28B)) |
UINT32 |
RO |
0xF102:3C, 1 |
|
1A82:3D |
SubIndex 061 |
61. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x3D (Slave 29B)) |
UINT32 |
RO |
0xF102:3D, 1 |
|
1A82:3E |
SubIndex 062 |
62. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x3E (Slave 30B)) |
UINT32 |
RO |
0xF102:3E, 1 |
|
1A82:3F |
SubIndex 063 |
63. PDO Mapping entry (object 0xF102 (ASI LAS), entry 0x3F (Slave 31B)) |
UINT32 |
RO |
0xF102:3F, 1 |
|
1A82:40 |
SubIndex 064 |
64. PDO Mapping entry (1 bits align) |
UINT32 |
RO |
0x0000:00, 1 |
Index 1A83 ASI TxPDO-Map LPS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A83:0 |
ASI TxPDO-Map LPS |
PDO Mapping TxPDO 132 |
UINT8 |
RO |
0x40 (64dec) |
|
1A83:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x01 (Slave 0)) |
UINT32 |
RO |
0xF103:01, 1 |
|
1A83:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x02 (Slave 1A)) |
UINT32 |
RO |
0xF103:02, 1 |
|
1A83:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x03 (Slave 2A)) |
UINT32 |
RO |
0xF103:03, 1 |
|
1A83:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x04 (Slave 3A)) |
UINT32 |
RO |
0xF103:04, 1 |
|
1A83:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x05 (Slave 4A)) |
UINT32 |
RO |
0xF103:05, 1 |
|
1A83:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x06 (Slave 5A)) |
UINT32 |
RO |
0xF103:06, 1 |
|
1A83:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x07 (Slave 6A)) |
UINT32 |
RO |
0xF103:07, 1 |
|
1A83:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x08 (Slave 7A)) |
UINT32 |
RO |
0xF103:08, 1 |
|
1A83:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x09 (Slave 8A)) |
UINT32 |
RO |
0xF103:09, 1 |
|
1A83:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x0A (Slave 9A)) |
UINT32 |
RO |
0xF103:0A, 1 |
|
1A83:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x0B (Slave 10A)) |
UINT32 |
RO |
0xF103:0B, 1 |
|
1A83:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x0C (Slave 11A)) |
UINT32 |
RO |
0xF103:0C, 1 |
|
1A83:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x0D (Slave 12A)) |
UINT32 |
RO |
0xF103:0D, 1 |
|
1A83:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x0E (Slave 13A)) |
UINT32 |
RO |
0xF103:0E, 1 |
|
1A83:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x0F (Slave 14A)) |
UINT32 |
RO |
0xF103:0F, 1 |
Index 1A83 ASI TxPDO-Map LPS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A83:10 |
SubIndex 016 |
16. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x10 (Slave 15A)) |
UINT32 |
RO |
0xF103:10, 1 |
|
1A83:11 |
SubIndex 017 |
17. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x11 (Slave 16A)) |
UINT32 |
RO |
0xF103:11, 1 |
|
1A83:12 |
SubIndex 018 |
18. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x12 (Slave 17A)) |
UINT32 |
RO |
0xF103:12, 1 |
|
1A83:13 |
SubIndex 019 |
19. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x13 (Slave 18A)) |
UINT32 |
RO |
0xF103:13, 1 |
|
1A83:14 |
SubIndex 020 |
20. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x14 (Slave 19A)) |
UINT32 |
RO |
0xF103:14, 1 |
|
1A83:15 |
SubIndex 021 |
21. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x15 (Slave 20A)) |
UINT32 |
RO |
0xF103:15, 1 |
|
1A83:16 |
SubIndex 022 |
22. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x16 (Slave 21A)) |
UINT32 |
RO |
0xF103:16, 1 |
|
1A83:17 |
SubIndex 023 |
23. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x17 (Slave 22A)) |
UINT32 |
RO |
0xF103:17, 1 |
|
1A83:18 |
SubIndex 024 |
24. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x18 (Slave 23A)) |
UINT32 |
RO |
0xF103:18, 1 |
|
1A83:19 |
SubIndex 025 |
25. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x19 (Slave 24A)) |
UINT32 |
RO |
0xF103:19, 1 |
|
1A83:1A |
SubIndex 026 |
26. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x1A (Slave 25A)) |
UINT32 |
RO |
0xF103:1A, 1 |
|
1A83:1B |
SubIndex 027 |
27. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x1B (Slave 26A)) |
UINT32 |
RO |
0xF103:1B, 1 |
|
1A83:1C |
SubIndex 028 |
28. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x1C (Slave 27A)) |
UINT32 |
RO |
0xF103:1C, 1 |
|
1A83:1D |
SubIndex 029 |
29. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x1D (Slave 28A)) |
UINT32 |
RO |
0xF103:1D, 1 |
|
1A83:1E |
SubIndex 030 |
30. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x1E (Slave 29A)) |
UINT32 |
RO |
0xF103:1E, 1 |
|
1A83:1F |
SubIndex 031 |
31. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x1F (Slave 30A)) |
UINT32 |
RO |
0xF103:1F, 1 |
Index 1A83 ASI TxPDO-Map LPS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A83:20 |
SubIndex 032 |
32. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x20 (Slave 31A)) |
UINT32 |
RO |
0xF103:20, 1 |
|
1A83:21 |
SubIndex 033 |
33. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x21 (Slave 1B)) |
UINT32 |
RO |
0xF103:21, 1 |
|
1A83:22 |
SubIndex 034 |
34. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x22 (Slave 2B)) |
UINT32 |
RO |
0xF103:22, 1 |
|
1A83:23 |
SubIndex 035 |
35. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x23 (Slave 3B)) |
UINT32 |
RO |
0xF103:23, 1 |
|
1A83:24 |
SubIndex 036 |
36. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x24 (Slave 4B)) |
UINT32 |
RO |
0xF103:24, 1 |
|
1A83:25 |
SubIndex 037 |
37. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x25 (Slave 5B)) |
UINT32 |
RO |
0xF103:25, 1 |
|
1A83:26 |
SubIndex 038 |
38. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x26 (Slave 6B)) |
UINT32 |
RO |
0xF103:26, 1 |
|
1A83:27 |
SubIndex 039 |
39. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x27 (Slave 7B)) |
UINT32 |
RO |
0xF103:27, 1 |
|
1A83:28 |
SubIndex 040 |
40. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x28 (Slave 8B)) |
UINT32 |
RO |
0xF103:28, 1 |
|
1A83:29 |
SubIndex 041 |
41. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x29 (Slave 9B)) |
UINT32 |
RO |
0xF103:29, 1 |
|
1A83:2A |
SubIndex 042 |
42. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x2A (Slave 10B)) |
UINT32 |
RO |
0xF103:2A, 1 |
|
1A83:2B |
SubIndex 043 |
43. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x2B (Slave 11B)) |
UINT32 |
RO |
0xF103:2B, 1 |
|
1A83:2C |
SubIndex 044 |
44. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x2C (Slave 12B)) |
UINT32 |
RO |
0xF103:2C, 1 |
|
1A83:2D |
SubIndex 045 |
45. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x2D (Slave 13B)) |
UINT32 |
RO |
0xF103:2D, 1 |
|
1A83:2E |
SubIndex 046 |
46. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x2E (Slave 14B)) |
UINT32 |
RO |
0xF103:2E, 1 |
|
1A83:2F |
SubIndex 047 |
47. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x2F (Slave 15B)) |
UINT32 |
RO |
0xF103:2F, 1 |
Index 1A83 ASI TxPDO-Map LPS
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A83:30 |
SubIndex 048 |
48. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x30 (Slave 16B)) |
UINT32 |
RO |
0xF103:30, 1 |
|
1A83:31 |
SubIndex 049 |
49. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x31 (Slave 17B)) |
UINT32 |
RO |
0xF103:31, 1 |
|
1A83:32 |
SubIndex 050 |
50. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x32 (Slave 18B)) |
UINT32 |
RO |
0xF103:32, 1 |
|
1A83:33 |
SubIndex 051 |
51. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x33 (Slave 19B)) |
UINT32 |
RO |
0xF103:33, 1 |
|
1A83:34 |
SubIndex 052 |
52. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x34 (Slave 20B)) |
UINT32 |
RO |
0xF103:34, 1 |
|
1A83:35 |
SubIndex 053 |
53. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x35 (Slave 21B)) |
UINT32 |
RO |
0xF103:35, 1 |
|
1A83:36 |
SubIndex 054 |
54. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x36 (Slave 22B)) |
UINT32 |
RO |
0xF103:36, 1 |
|
1A83:37 |
SubIndex 055 |
55. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x37 (Slave 23B)) |
UINT32 |
RO |
0xF103:37, 1 |
|
1A83:38 |
SubIndex 056 |
56. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x38 (Slave 24B)) |
UINT32 |
RO |
0xF103:38, 1 |
|
1A83:39 |
SubIndex 057 |
57. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x39 (Slave 25B)) |
UINT32 |
RO |
0xF103:39, 1 |
|
1A83:3A |
SubIndex 058 |
58. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x3A (Slave 26B)) |
UINT32 |
RO |
0xF103:3A, 1 |
|
1A83:3B |
SubIndex 059 |
59. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x3B (Slave 27B)) |
UINT32 |
RO |
0xF103:3B, 1 |
|
1A83:3C |
SubIndex 060 |
60. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x3C (Slave 28B)) |
UINT32 |
RO |
0xF103:3C, 1 |
|
1A83:3D |
SubIndex 061 |
61. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x3D (Slave 29B)) |
UINT32 |
RO |
0xF103:3D, 1 |
|
1A83:3E |
SubIndex 062 |
62. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x3E (Slave 30B)) |
UINT32 |
RO |
0xF103:3E, 1 |
|
1A83:3F |
SubIndex 063 |
63. PDO Mapping entry (object 0xF103 (ASI LPS), entry 0x3F (Slave 31B)) |
UINT32 |
RO |
0xF103:3F, 1 |
|
1A83:40 |
SubIndex 064 |
64. PDO Mapping entry (1 bits align) |
UINT32 |
RO |
0x0000:00, 1 |
Index 1C00Sync manager type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C00:0 |
Sync manager type |
Using the sync managers |
UINT8 |
RO |
0x04 (4dec) |
|
1C00:01 |
SubIndex 001 |
Sync-Manager Type Channel 1: Mailbox Write |
UINT8 |
RO |
0x01 (1dec) |
|
1C00:02 |
SubIndex 002 |
Sync-Manager Type Channel 2: Mailbox Read |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:03 |
SubIndex 003 |
Sync-Manager Type Channel 3: Process Data Write (Outputs) |
UINT8 |
RO |
0x03 (3dec) |
|
1C00:04 |
SubIndex 004 |
Sync-Manager Type Channel 4: Process Data Read (Inputs) |
UINT8 |
RO |
0x04 (4dec) |
Index 1C12 RxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C12:0 |
RxPDO assign |
PDO Assign Outputs |
UINT8 |
RW |
0x02 (2dec) |
|
1C12:01 |
SubIndex 001 |
1. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x1640 (5696dec) |
|
1C12:02 |
SubIndex 002 |
2. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x1680 (5760dec) |
|
1C12:03 |
SubIndex 003 |
3. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:04 |
SubIndex 004 |
4. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:05 |
SubIndex 005 |
5. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:06 |
SubIndex 006 |
6. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:07 |
SubIndex 007 |
7. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:08 |
SubIndex 008 |
8. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:09 |
SubIndex 009 |
9. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0A |
SubIndex 010 |
10. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0B |
SubIndex 011 |
11. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0C |
SubIndex 012 |
12. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0D |
SubIndex 013 |
13. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0E |
SubIndex 014 |
14. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:0F |
SubIndex 015 |
15. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
Index 1C12 RxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C12:10 |
SubIndex 016 |
16. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:11 |
SubIndex 017 |
17. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:12 |
SubIndex 018 |
18. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:13 |
SubIndex 019 |
19. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:14 |
SubIndex 020 |
20. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:15 |
SubIndex 021 |
21. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:16 |
SubIndex 022 |
22. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:17 |
SubIndex 023 |
23. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:18 |
SubIndex 024 |
24. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:19 |
SubIndex 025 |
25. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1A |
SubIndex 026 |
26. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1B |
SubIndex 027 |
27. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1C |
SubIndex 028 |
28. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1D |
SubIndex 029 |
29. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1E |
SubIndex 030 |
30. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:1F |
SubIndex 031 |
31. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:20 |
SubIndex 032 |
32. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:21 |
SubIndex 033 |
33. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C12:22 |
SubIndex 034 |
34. allocated RxPDO (contains the index of the associated RxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
Index 1C13 TxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:0 |
TxPDO assign |
PDO Assign Inputs |
UINT8 |
RW |
0x02 (2dec) |
|
1C13:01 |
SubIndex 001 |
1. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A40 (6720dec) |
|
1C13:02 |
SubIndex 002 |
2. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A80 (6784dec) |
|
1C13:03 |
SubIndex 003 |
3. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:04 |
SubIndex 004 |
4. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:05 |
SubIndex 005 |
5. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:06 |
SubIndex 006 |
6. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:07 |
SubIndex 007 |
7. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:08 |
SubIndex 008 |
8. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:09 |
SubIndex 009 |
9. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0A |
SubIndex 010 |
10. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0B |
SubIndex 011 |
11. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0C |
SubIndex 012 |
12. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0D |
SubIndex 013 |
13. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0E |
SubIndex 014 |
14. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:0F |
SubIndex 015 |
15. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
Index 1C13 TxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:10 |
SubIndex 016 |
16. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:11 |
SubIndex 017 |
17. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:12 |
SubIndex 018 |
18. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:13 |
SubIndex 019 |
19. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:14 |
SubIndex 020 |
20. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:15 |
SubIndex 021 |
21. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:16 |
SubIndex 022 |
22. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:17 |
SubIndex 023 |
23. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:18 |
SubIndex 024 |
24. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:19 |
SubIndex 025 |
25. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1A |
SubIndex 026 |
26. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1B |
SubIndex 027 |
27. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1C |
SubIndex 028 |
28. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1D |
SubIndex 029 |
29. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1E |
SubIndex 030 |
30. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:1F |
SubIndex 031 |
31. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:20 |
SubIndex 032 |
32. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:21 |
SubIndex 033 |
33. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:22 |
SubIndex 034 |
34. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:23 |
SubIndex 035 |
35. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:24 |
SubIndex 036 |
36. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C13:25 |
SubIndex 037 |
37. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x0000 (0dec) |
Index 1C32 SM output parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C32:0 |
SM output parameter |
Synchronization parameters for the outputs |
UINT8 |
RO |
0x20 (32dec) |
|
1C32:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:02 |
Cycle time |
Cycle time (in ns):
|
UINT32 |
RW |
0x000F4240 (1000000dec) |
|
1C32:03 |
Shift time |
Time between SYNC0 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C32:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0xC007 (49159dec) |
|
1C32:05 |
Minimum cycle time |
Minimum cycle time (in ns) |
UINT32 |
RO |
0x00002710 (10000dec) |
|
1C32:06 |
Calc and copy time |
Minimum time between SYNC0 and SYNC1 event (in ns, DC mode only) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C32:07 |
Minimum delay time |
|
UINT32 |
RO |
0x00000384 (900dec) |
|
1C32:08 |
Command |
The entries 0x1C32:03, 0x1C32:05, 0x1C32:06, 0x1C32:09, 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values. |
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:09 |
Maximum delay time |
Time between SYNC1 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C32:0B |
SM event missed counter |
Number of missed SM events in OPERATIONAL (DC mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:0C |
Cycle exceeded counter |
Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:0D |
Shift too short counter |
Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:20 |
Sync error |
The synchronization was not correct in the last cycle (outputs were output too late; DC mode only) |
BOOLEAN |
RO |
0x00 (0dec) |
Index 1C33 SM input parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C33:0 |
SM input parameter |
Synchronization parameters for the inputs |
UINT8 |
RO |
0x20 (32dec) |
|
1C33:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:02 |
Cycle time |
as 0x1C32:02 |
UINT32 |
RW |
0x000F4240 (1000000dec) |
|
1C33:03 |
Shift time |
Time between SYNC0 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C33:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0xC007 (49159dec) |
|
1C33:05 |
Minimum cycle time |
as 0x1C32:05 |
UINT32 |
RO |
0x00002710 (10000dec) |
|
1C33:06 |
Calc and copy time |
Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C33:07 |
Minimum delay time |
|
UINT32 |
RO |
0x00000384 (900dec) |
|
1C33:08 |
Command |
as 0x1C32:08 |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:09 |
Maximum delay time |
Time between SYNC1 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C33:0B |
SM event missed counter |
as 0x1C32:11 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0C |
Cycle exceeded counter |
as 0x1C32:12 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0D |
Shift too short counter |
as 0x1C32:13 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:20 |
Sync error |
as 0x1C32:32 |
BOOLEAN |
RO |
0x00 (0dec) |
Index F000 Modular device profile
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
F000:0 |
Modular device profile |
General information for the modular device profile |
UINT8 |
RO |
0x02 (2dec) |
|
F000:01 |
Module index distance |
Index distance of the objects of the individual channels |
UINT16 |
RO |
0x0010 (16dec) |
|
F000:02 |
Maximum number of modules |
Number of channels |
UINT16 |
RO |
0x0020 (32dec) |
Index F008 Code word
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
F008:0 |
Code word |
reserved |
UINT32 |
RW |
0x00000000 (0dec) |
Index F010 Module list
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
F010:0 |
Module list |
reserved |
UINT8 |
RW |
0x20 (32dec) |
|
F010:01 - 20 |
SubIndex 001 - 032 |
reserved |
UINT32 |
RW |
0x00001838 (6200dec) |