EL5101-00x0 - LEDs and Connection

EL5101-00x0 - LEDs and Connection 1:
EL5101

Notice

Encoder supply via the terminal

The encoder supply voltage, can be taken from the terminal points 1’(5 V) and 5`(0 V).

Notice

Single-ended connection for TTL encoder

For information on the single-ended connection for TTL encoders, please refer to chapter "Single-Ended Connection for TTL Encoders ("Normal Operating Mode" or "Enhanced Operating Mode").

  • No Single-ended connection is possible for the terminals EL5101-0010 and EL5101-0011.

Connection

Terminal point

No.

Comment

A

1

Encoder input A

B

2

Encoder input B

C

3

Encoder input C

Latch 24 V

4

Latch input

¬A

5

Encoder input A

¬B

6

Encoder input B

¬C

7

Encoder input C

Gate 24 V

8

Gate input

Ue = +5 V

1'

+5 V encoder supply

+24 V

2'

+24 V (internally connected to terminal point 6' and positive power contact)

0 V

3'

0 V (internally connected to terminal point 7' and negative power contact)

Input 1

4'

Status input 1
Alarm input from rotary encoder. Internally connected to 5 V via pull-up. Switching to negative potential, i.e. connection to GND leads to error bit and LED display. If externally supplied (not recommended) 5 V max. against GND is permitted.

Uo = 0 V

5'

0 V encoder supply

+24 V

6'

+24 V (internally connected to terminal point 2' and positive power contact)

0 V

7'

0 V (internally connected to terminal point 3' and negative power contact)

Shield

8'

Screen

LEDs

EL5101-00x0 - LEDs and Connection 2:
EL5101-00x0 - LEDs

LED

Color

Meaning

INPUT A, B, C

green

indicates TRUE level

INPUT 1

red

is lit, if INPUT 1 is connected to GND
[INPUT 1 is connected to an internal 5 V HIGH level though internal pull-up (default)]

LATCH

green

is lit, if a signal (+24 V) is connected to the latch input

GATE

green

is lit, if a signal (+24 V) is connected to the gate input

RUN

green

This LED indicates the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates of the terminal

flashing

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

single flash

State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

POWER 5 V

green

Operating voltage display for incremental encoder power supply