Excitation frequency (0x80n1:14), excitation voltage (0x80n1:15)

Notice

Setting and activating the excitation frequency and excitation voltage

  • Check the supply to the power contacts (see chapter EL5072 – Diagnostics).
  • Set the excitation frequency index 0x8001:14 "Excitation frequency" and excitation voltage index 0x8001:15 "Excitation voltage" centrally via the first channel. These settings are then valid for both channels.
  • Before switching, make sure that both sensors support the set range!
  • The excitation voltage is switched off in the delivery state and must be switched on by setting index 0x8000:08 "Enable excitation" to TRUE.

Excitation frequency (index 0x8001:14)

The EL5072 provides a high-frequency alternating voltage for sensor excitation. Predefined excitation or carrier frequencies are provided for this purpose. Since it is a joint excitation source for both channels, the settings must be made in channel 1.

Index 0x8001:14 "Excitation frequency"

Setting

Meaning

1000dec

1 kHz

2000dec

2 kHz

2500dec

2.5 kHz

4000dec

4 kHz

5000dec

5 kHz

7500dec

7.5 kHz

10000dec

10 kHz

12500dec

12.5 kHz

13000dec

13 kHz

15000dec

15 kHz

19400dec

19.4 kHz

20000dec

20 kHz

Excitation voltage (index 0x8001:15)

The following excitation voltages are provided as RMS values:

Index 0x8001:15 "Excitation voltage"

Setting

Meaning

500dec

0.5 Vrms

1000dec

1 Vrms

1500dec

1.5 Vrms

2000dec

2 Vrms

2500dec

2.5 Vrms

3000dec

3 Vrms

3500dec

3.5 Vrms

4000dec

4 Vrms

4500dec

4.5 Vrms

5000dec

5 Vrms

5500dec

5.5 Vrms

6000dec

6 Vrms

6500dec

6.5 Vrms

7000dec

7 Vrms