Configuration data
Index 8000 ENC Settings
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 8000:0 | ENC Settings | Maximum subindex | UINT8 | RO | 0x1F (31dec) | 
| 8000:01 | Enable C reset | The counter is reset via the C input. | BOOLEAN | RW | 0x00 (0dec) | 
| 8000:0E | Reversion of rotation | Activates reversion of rotation | BOOLEAN | RW | 0x00 (0dec) | 
| 8000:0F | Frequency window base | Basic unit of the "frequency window" (index 0x8000:11) | BIT1 | RW | 0x00 (0dec) | 
| 8000:11 | Frequency window | This is the time used for determining the frequency. The number of periods and the analog part (the period resolution) in the timeframe is measured and then divided by the timeframe size. | UINT16 | RW | 0x2710 (10000dec) | 
| 8000:1D | Frequency numerator | Frequency counter value, frequency scaling | UINT32 | RW | 0x00000064 (100dec) | 
| 8000:1E | Frequency denominator | frequency counter value, used for scaling the frequency and the velocity calculation (increments / unit). | UINT32 | RW | 0x00000001 (1dec) | 
| 8000:1F | IIR filter permitted values: | UINT16 | RW | 0x0000 (0dec) | |
| 0: None | |||||
| 1: IIR1 | |||||
| 2: IIR 2 | |||||
| 3: IIR 3 | |||||
| 4: IIR 4 | |||||
| 5: IIR 5 | |||||
| 6: IIR 6 | |||||
| 7: IIR 7 | |||||
| 8: IIR 8 | 
Index 8001 ENC SinCos settings
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 8001:0 | ENC SinCos settings | Maximum subindex | UINT8 | RO | 0x11 (17dec) | 
| 8001:01 | Enable frequency error | Activates the "frequency error" counter | BOOLEAN | RW | 0x01 (1dec) | 
| 8001:02 | Enable amplitude error | Activates the "amplitude error" counter | BOOLEAN | RW | 0x01 (1dec) | 
| 8001:11 | Analog resolution | Period resolution in bits (default: 10 bits) | UINT8 | RW | 0x0A (10dec) | 
Index 8010 TSC Settings (EL5021-0090 only)
| Index (hex) | Name | Meaning | Data type | Flags | Default | 
|---|---|---|---|---|---|
| 8010:0 | TSC Settings | Maximum subindex | UINT8 | RO | 0x02 (2dec) | 
| 8010:01 | Address | TwinSAFE SC address | UINT16 | RW | 0x0000 (0dec) | 
| 8010:02 | Connection Mode | Selection of TwinSAFE SC CRC | UINT32 | RO | 0x00000000 (0dec) |