Configuration data

Index 80p0 AI Settings (for p = 0...5, corresponding to channel 1...6)

Index (hex)

Name

Meaning

Data type

Flags

Default

80p0:0

AI Settings

Maximum subindex

UINT8

RO

> 24 <

80p0:07

Enable limit

Limit 1 enabled

BOOLEAN

RW

FALSE

80p0:0A

Enable user calibration

Enabling of the user calibration

BOOLEAN

RW

FALSE

80p0:0B

Enable vendor calibration

Enabling of the vendor calibration

BOOLEAN

RW

TRUE

80p0:13

Limit 1

First limit value for setting the status bits

INT16

RW

0dec

80p0:14

Limit 2

Second limit value for setting the status bits

INT16

RW

0dec

80p0:15

Filter settings

This object determines the digital filter settings.
The possible settings are sequentially numbered.

0: 200 Hz
1: 500 Hz
2: 1000 Hz
3: 1500 Hz
4: 2500 Hz
5: 5000 Hz
6: 15000 Hz
See note below:

UINT16

RW

2500 Hz (4)

80p0:17

User calibration offset

User calibration offset

INT16

RW

0dec

80p0:18

User calibration gain

User calibration gain

INT16

RW

16384dec

Configuration data 1:

The filter characteristics are set via index 0x8000:15

The filter frequencies are set for all channels centrally via index 0x8000:15 (channel 1). All other corresponding indices 0x80p0:15 have no parameterization function!

Index 80pF AI Vendor data (for p = 0...5, corresponding to channel 1...6)

Index (hex)

Name

Meaning

Data type

Flags

Default

80pF:0

AI Vendor data

Maximum subindex

UINT8

RO

> 2 <

80pF:01

Calibration offset

Offset (vendor calibration)

INT16

RW

-

80pF:02

Calibration gain

Gain (vendor calibration)

INT16

RW

-