Configuration data
Index 80p0 AI Settings (for p = 0...5, corresponding to channel 1...6)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80p0:0 |
AI Settings |
Maximum subindex |
UINT8 |
RO |
> 24 < |
|
80p0:07 |
Limit 1 enabled |
BOOLEAN |
RW |
FALSE | |
|
80p0:0A |
Enabling of the user calibration |
BOOLEAN |
RW |
FALSE | |
|
80p0:0B |
Enabling of the vendor calibration |
BOOLEAN |
RW |
TRUE | |
|
80p0:13 |
First limit value for setting the status bits |
INT16 |
RW |
0dec | |
|
80p0:14 |
Second limit value for setting the status bits |
INT16 |
RW |
0dec | |
|
80p0:15 |
This object determines the digital filter settings. |
UINT16 |
RW |
2500 Hz (4) | |
|
80p0:17 |
User calibration offset |
INT16 |
RW |
0dec | |
|
80p0:18 |
User calibration gain |
INT16 |
RW |
16384dec |
![]() | The filter characteristics are set via index 0x8000:15 The filter frequencies are set for all channels centrally via index 0x8000:15 (channel 1). All other corresponding indices 0x80p0:15 have no parameterization function! |
Index 80pF AI Vendor data (for p = 0...5, corresponding to channel 1...6)
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
80pF:0 |
AI Vendor data |
Maximum subindex |
UINT8 |
RO |
> 2 < |
|
80pF:01 |
Calibration offset |
Offset (vendor calibration) |
INT16 |
RW |
- |
|
80pF:02 |
Calibration gain |
Gain (vendor calibration) |
INT16 |
RW |
- |