Measurement 3.6…21 mA (NAMUR NE43)

Measurement mode

3.6…21 mA (NAMUR NE43)

Measuring range, nominal

4…20 mA

Measuring range, end value (full scale value)

20 mA

Measuring range, technically usable

3.6…21 mA

Fuse protection

Internal overload limiting, continuous current resistant

PDO resolution

24 Bit

PDO LSB (Extended Range)

2.048 nA

PDO LSB (Legacy Range)

n.a.

Common-mode voltage Vcm

max. +/- 10V

related to -Uv (internal ground)

Basic accuracy: Measuring deviation at 23°C, with averaging

< ±0.01%FSV = ±100 ppmFSV

Offset/Zero Point deviation (at 23°C)

EOffset

< 65 ppmFSV

Gain/scale/amplification deviation (at 23°C)

EGain

< 50 ppm

Non-linearity over the whole measuring range

ELin

< 40 ppmFSV

Repeatability

ERep

< 40 ppmFSV

Noise (without filtering)

ENoise, PtP

< 100 ppmFSV

< 781 [digits]

ENoise, RMS

< 18 ppmFSV

< 141 [digits]

Max. SNR

> 94.9 dB

Noisedensity@1kHz

< 5.09 Measurement 3.6…21 mA (NAMUR NE43) 1:

Noise (with 50Hz FIR filtering)

ENoise, PtP

< 10 ppmFSV

< 78 [digits]

ENoise, RMS

< 2.0 ppmFSV

< 16 [digits]

Max. SNR

> 114.0 dB

Temperature coefficient

TcGain

< 15 ppm/K typ.

TcOffset

< 5 ppmFSV/K typ.

Common-mode rejection ratio (without filtering)

DC: < 3 nA/V typ.

50 Hz: < 5  nA/V typ.

1 kHz: < 80  nA/V typ.

Common-mode rejection ratio (with 50Hz FIR filtering)

DC: < 3 nA/V typ.

50 Hz: < 3 nA/V typ.

1 kHz: < 3 nA/V typ.

Largest short-term deviation during a specified electrical interference test

±0.05%FSV = ±500 ppmFSV typ.

Input impedance ±Input 1

(Internal resistance)

Differential 200 Ω || 11 nF typ.

CommonMode 1 MΩ || 40 nF typ.

Methodology: Resistor against -UV, capacitance against SGND

Input impedance ±Input 2

No usage of this input in this mode

Current measuring range 3.6…21 mA (NAMUR)

Measurement 3.6…21 mA (NAMUR NE43) 2:Fig.39: Chart: current measuring range 3.6…21 mA (NAMUR)
Measurement 3.6…21 mA (NAMUR NE43) 3:

Only Extended Range mode for measuring range 4 mA NAMUR

Legacy Range mode is not available for this measurement range. The Extended Range Mode will be set automatically and although a corresponding write access to the CoE Object 0x8000:2E (Scaler) is not declined, the parameter is not changed.

Measurement 3.6…21 mA (NAMUR NE43) 4:Fig.34: Frequency response 20 mA measurement range, fsampling = 10 kHz, integrated filter 1/2 deactivated