Technical data

Technical data

EL3621-0020

Number of inputs

1

Resolution

24 bit (incl. sign)

Sampling type

simultaneous

Ground reference

differential

Signal current

4 ... 20 mA

Max. input frequency

3 kHz

Conversion time

1…400 ms configurable

Measuring error

< ±0.01 %
(Initial accuracy**) at 25°C, 50 Hz filter, relative to full scale value)

Internal resistance

85 Ω type. + diode voltage

Common-mode voltage Ucm

10 V max.

Crosstalk attenuation

> 60 dB

Power supply for electronics

via the E-bus

Current consumption via E-bus

typ. 190 mA

Electrical isolation

500 V (E-bus/signal voltage)

Configuration

via TwinCAT System Manager

Special features

various filter times, limit evaluation, high precision, with calibration certificate

Weight

approx. 60 g

Permissible ambient temperature range during operation

-25 °C ... +60 °C (extended temperature range)

Permissible ambient temperature range during storage

-40 °C ... +85 °C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, EAC, UKCA

*) Real applicable approvals/markings see type plate on the side (product marking).

**) Notes concerning ageing effects on request