Configuration data

Index 8000 AI Settings Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

AI Settings Ch.1

Maximum subindex

UINT8

RO

EL3602:
0x19 (25dec)

EL3602-0002:
0x18 (24dec)

EL3602-0010:
0x1A (26dec)

EL3612,
EL3621-0020:

0x18 (24dec)

8000:01

Enable user scale

User scaling is active.

BOOLEAN

RW

0x00 (0dec)

8000:02

Presentation

0: Signed presentation

1: Absolute value with MSB as sign
Signed amount representation

2: right adjust 24 Bit
The value is output with a resolution of 24 bit

BIT3

RW

0x00000000 (0dec)

8000:05

Siemens bits

The S5 bits are displayed in the three low-order bits

BOOLEAN

RW

0x00 (0dec)

8000:06

Enable filter

The filter is always active irrespective of this setting, see note!

BOOLEAN

RW

0x00 (0dec)

8000:07

Enable limit 1

Limit 1 enabled

BOOLEAN

RW

0x00 (0dec)

8000:08

Enable limit 2

Limit 2 enabled

BOOLEAN

RW

0x00 (0dec)

8000:0A

Enable user calibration

Enabling of the user calibration

BOOLEAN

RW

0x00 (0dec)

8000:0B

Enable vendor calibration

Enabling of the vendor calibration

BOOLEAN

RW

0x01 (1dec)

8000:11

User scale offset

User scaling offset

INT32

RW

0x00000000 (0dec)

8000:12

User scale gain

User scaling gain.
The gain is represented in fixed-point format, with the factor 2-16.
The value 1 corresponds to 65535 (0x00010000)

INT32

RW

0x00010000 (65536dec)

8000:13

Limit 1

First limit value for setting the status bits

INT32

RW

0x00000000 (0dec)

8000:14

Limit 2

Second limit value for setting the status bits

INT32

RW

0x00000000 (0dec)

8000:15

Filter settings

This object determines the digital filter settings, if it is active via Enable filter (index 0x8000:06).
The possible settings are sequentially numbered.
0: 50 Hz
1: 60 Hz
2: 100 Hz
3: 500 Hz
4: 1 kHz
5: 2 kHz
6: 3.75 kHz
7: 7.5 kHz
8: 15 kHz
9: 30 kHz
10: 5 Hz
11:10 Hz

UINT32

RW

0x00000000 (0dec)

8000:17

User calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

8000:18

User calibration gain

User calibration gain

UINT32

RW

0x007FFFFF (8388607dec)

8000:19
EL3602 (EL3602-0000) only

Range

Measuring range
0: +/- 10 V
1: +/- 5 V
2: +/- 2.5 V
3: +/- 1.25 V

UINT32

RW

0x00000000 (0dec)

Index 8010 AI Settings Ch.2, EL3602 (EL3602-xxxx), EL3612 (EL3612-xxxx) only

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

AI Settings Ch.2

Maximum subindex

UINT8

RO

EL3602:
0x19 (25dec)

EL3602-0002:
0x18 (24dec)

EL3602-0010:
0x1A (26dec)

EL3612:
0x18 (24dec)

8010:01

Enable user scale

User scaling is active.

BOOLEAN

RW

0x00 (0dec)

8010:02

Presentation

0: Signed presentation

1: Absolute value with MSB as sign
Signed amount representation

2: right adjust 24Bit
The value is output with a resolution of 24 bit

BIT3

RW

0x00000000 (0dec)

8010:05

Siemens bits

The S5 bits are displayed in the three low-order bits

BOOLEAN

RW

0x00 (0dec)

8010:06

Enable filter

Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary

BOOLEAN

RW

0x00 (0dec)

8010:07

Enable limit 1

Limit 1 enabled

BOOLEAN

RW

0x00 (0dec)

8010:08

Enable limit 2

Limit 2 enabled

BOOLEAN

RW

0x00 (0dec)

8010:0A

Enable user calibration

Enabling of the user calibration

BOOLEAN

RW

0x00 (0dec)

8010:0B

Enable vendor calibration

Enabling of the vendor calibration

BOOLEAN

RW

0x01 (1dec)

8010:11

User scale offset

User scaling offset

INT32

RW

0x00000000 (0dec)

8010:12

User scale gain

User scaling gain.
The gain is represented in fixed-point format, with the factor 2-16.
The value 1 corresponds to 65535 (0x00010000)

INT32

RW

0x00010000 (65536dec)

8010:13

Limit 1

First limit value for setting the status bits

INT32

RW

0x00000000 (0dec)

8010:14

Limit 2

Second limit value for setting the status bits

INT32

RW

0x00000000 (0dec)

8010:15

Filter settings

This object determines the digital filter settings, if it is active via Enable filter (index 0x8010:06).
The possible settings are sequentially numbered.
0: 50 Hz
1: 60 Hz
2: 100 Hz
3: 500 Hz
4: 1 kHz
5: 2 kHz
6: 3.75 kHz
7: 7.5 kHz
8: 15 kHz
9: 30 kHz
10: 5 Hz
11:10 Hz

UINT32

RW

0x00000000 (0dec)

8010:17

User calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

8010:18

User calibration gain

User calibration gain

UINT32

RW

0x007FFFFF (8388607dec)

8010:19
EL3602 (EL3602-0000) only

Range

Measuring range
0: +/- 10 V
1: +/- 5 V
2: +/- 2.5 V
3: +/- 1.25 V

UINT32

RW

0x00000000 (0dec)