Filter

In the COE (object 0x80n0:21) the EL3692 has a filter setting option for each channel. The principle is as follows:

This process results in a notch characteristic as shown Fig. Filter characteristic. The filter frequency entered corresponds to the smallest blocked frequency. All multiples of the specified frequency are also blocked. The default setting "10 Hz" blocks 50 Hz and 60 Hz interference.

The filter setting has therefore direct influence on the conversion time of the respective channel.

Filter 1:Fig.140: Filter characteristic