Filter, Sampling rate
Filter (CoE Index 0x8000:04)
The terminal measures with a sampling rate of 62.5 ms (16 sps).
The terminal's firmware can calculate a simple 8-fold mean value filter. The filter is enabled by default.
Fig.148: CoE Index 0x8000:04, Enable Filter- Enable filter = TRUE: filter averages the last 8 values and forwards the result every 500 ms (2 sps). If the measuring range is changed the filter is reset.
- Enable filter = FALSE: Each measured value is passed on internally immediately, the sampling rate is 16 sps.
Example:
Fig.149: Sine signal, 0/5 V, 1 HzSine signal, 0/5 V, 1 Hz, at the beginning filter "disabled" (sampling time 62.5 ms), after approx. 5 s the filter is "enabled" and an alias signal is generated (sampling time 500 ms)
The filter time is reset if the measuring range is changed via Autorange or by the user during the filter period.