Error handling and diagnostics
|
Error ** |
Underange ** |
Overrange ** |
Data invalid |
TxPDO State ** |
Range invalid |
Error description |
Remedy |
|---|---|---|---|---|---|---|---|
|
1 |
1 |
|
|
|
|
Measurement is below range |
If possible use a smaller measuring range; otherwise increase the input value |
|
1 |
|
1 |
|
|
|
Measuring range exceeded |
If possible use a larger measuring range; otherwise reduce the input value |
|
1 |
|
|
|
1 |
|
Conversion error |
automatic (ADC does not respond, automatic restart) |
|
1 |
|
|
|
|
1 |
Measuring range invalid |
Select valid measuring range; for Autorange perhaps select option "scaled" or activate SAI Range (outputs). |
|
|
|
|
1 |
|
|
Data invalid |
Wait (read ADC Zero, startup or conversion error) |
|
1 |
|
|
1 |
1 |
|
Conversion error after power-up |
Switch on again |
**) Error LED is lit, see LED description