Error handling and diagnostics

Error **
Index 0x6000:07

Underange **
Index 0x6000:01

Overrange **
Index 0x6000:02

Data invalid
Index 0x6000:04

TxPDO State **
Index 0x6000:0F

Range invalid
Index 0x6000:05

Error description

Remedy

1

1

 

 

 

 

Measurement is below range

If possible use a smaller measuring range; otherwise increase the input value

1

 

1

 

 

 

Measuring range exceeded

If possible use a larger measuring range; otherwise reduce the input value

1

 

 

 

1

 

Conversion error

automatic (ADC does not respond, automatic restart)

1

 

 

 

 

1

Measuring range invalid

Select valid measuring range; for Autorange perhaps select option "scaled" or activate SAI Range (outputs).

 

 

 

1

 

 

Data invalid

Wait (read ADC Zero, startup or conversion error)

1

 

 

1

1

 

Conversion error after power-up

Switch on again

**) Error LED is lit, see LED description