Input data

Index 6000 PM Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6000:0

PM Inputs Ch.1

Largest subindex of this object

UINT8

RO

>29<

6000:01

Overvoltage

Overvoltage detected

EL3413-0000: > 415 V (L1-N)
EL3413-0001: > 360 V (L1-N)
EL3413-0120: > 130 V (L1-N)

EL3433-0000: > 288 V (L1-N)

BOOLEAN

RO

0x00 (0dec)

6000:02

Undervoltage

Undervoltage detected
Voltage < 5 V

BOOLEAN

RO

0x00 (0dec)

6000:03

Overcurrent

Overcurrent

BOOLEAN

RO

0x00 (0dec)

6000:05

Phase sequence cw

Phase sequence L1 - L2 - L3 correctly detected
(in clockwise 3-phase network)

BOOLEAN

RO

0x00 (0dec)

6000:06

Phase sequence ccw

Phase sequence L1 - L3 - L2 correctly detected
(in counter-clockwise 3-phase network)

BOOLEAN

RO

0x00 (0dec)

6000:07

Missing zero crossing

No zero crossings detected

BOOLEAN

RO

0x00 (0dec)

6000:0F

TxPDO State

TRUE in the case of frequency, amplitude or general errors

BOOLEAN

RO

0x00 (0dec)

6000:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RW

0x00 (0dec)

6000:11

Current

Current channel 1

Unit: 0.000001 A

INT32

RW

0x00000000 (0dec)

6000:12

Voltage

Voltage channel 1

Unit: 0.0001 V

INT32

RW

0x00000000 (0dec)

6000:13

Active power

Active power channel 1

Unit: 0.01 W

INT32

RW

0x00000000 (0dec)

6000:14

Index

Acknowledge for variable
output value channel 1

Index (dec)

Name

Unit

UINT8

RW

0x00 (0dec)

0

Apparent power

0.01 VA

1

Reactive power

0.01 var

2

Energy

0.001 Wh

3

Power factor λ

0.001

4

Frequency

0.1 Hz

5

Energy (negative)

0.001 Wh

6

Angle α between phase 1 and phase 1

0.01 °

20***

Active power fundamental (P1)

0.01 W

21***

Apparent power fundamental (S1)

0.01 VA

22***

Reactive power fundamental (Q1)

0.01 var

30****

Energy positive

0.001 Wh

31****

Positive energy, automatically saved

0.001 Wh

32****

Energy, automatic saved

0.001 Wh

35****

Energy negative, automatically saved

0.001 Wh

44***

Frequency average resolution

0.01 Hz

45***

Frequency high resolution

0.001 Hz

46*****

Held frequency

0.1 Hz

47*****

Held frequency average resolution

0.01 Hz

48*****

Held frequency high resolution

0.001 Hz

6000:1D

VariantValue

variable output value channel 1 (see index 0x6000:14)

INT32

RW

0x00000000 (0dec)

***) for EL3413 from firmware 08, EL3413-0120 from firmware 04, EL3413-0001/EL3433 from firmware 10
****) from firmware 10

Index 6010 PM Inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6010:0

PM Inputs Ch.2

Largest subindex of this object

UINT8

RO

>29<

6010:01

Overvoltage

Overvoltage detected

EL3413-0000: > 415 V (L1-N)
EL3413-0001: > 360 V (L1-N)
EL3413-0120: > 130 V (L1-N)

EL3433-0000: > 288 V (L1-N)

BOOLEAN

RO

0x00 (0dec)

6010:02

Undervoltage

Undervoltage detected
Voltage < 5 V

BOOLEAN

RO

0x00 (0dec)

6010:03

Overcurrent

Overcurrent

BOOLEAN

RO

0x00 (0dec)

6010:05

Phase sequence cw

Phase sequence L1 - L2 - L3 correctly detected
(in clockwise 3-phase network)

BOOLEAN

RO

0x00 (0dec)

6010:06

Phase sequence ccw

Phase sequence L1 - L3 - L2 correctly detected
(in counter-clockwise 3-phase network)

BOOLEAN

RO

0x00 (0dec)

6010:07

Missing zero crossing

No zero crossings detected

BOOLEAN

RO

0x00 (0dec)

6010:0F

TxPDO State

TRUE in the case of frequency, amplitude or general errors

BOOLEAN

RO

0x00 (0dec)

6010:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RW

0x00 (0dec)

6010:11

Current

Current channel 2

Unit: 0.000001 A

INT32

RW

0x00000000 (0dec)

6010:12

Voltage

Voltage channel 2

Unit: 0.0001 V

INT32

RW

0x00000000 (0dec)

6010:13

Active power

Active power channel 2

Unit: 0.01 W

INT32

RW

0x00000000 (0dec)

6010:14

Index

Acknowledge for variable
output value channel 2

Index (dec)

Name

Unit

UINT8

RW

0x00 (0dec)

0

Apparent power

0.01 VA

1

Reactive power

0.01 var

2

Energy

0.001 Wh

3

Power factor

0.001

4

Frequency

0.1 Hz

5

Energy (negative)

0.001 Wh

6

Angle α between phase 2 and phase 1

0.01 °

20***

Active power fundamental (P1)

0.01 W

21***

Apparent power fundamental (S1)

0.01 VA

22***

Reactive power fundamental (Q1)

0.01 var

30****

Energy positive

0.001 Wh

31****

Positive energy, automatically saved

0.001 Wh

32****

Energy, automatic saved

0.001 Wh

35****

Energy negative, automatically saved

0.001 Wh

44***

Frequency average resolution

0.01 Hz

45***

Frequency high resolution

0.001 Hz

46*****

Held frequency

0.1 Hz

47*****

Held frequency average resolution

0.01 Hz

48*****

Held frequency high resolution

0.001 Hz

6010:1D

VariantValue

variable output value channel 2 (see index 0x6010:14)

INT32

RW

0x00000000 (0dec)

***) for EL3413 from firmware 08, EL3413-120 from firmware 04, EL3413-1/EL3433 from firmware 10
****) from firmware 10

Index 6020 PM Inputs Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

6020:0

PM Inputs Ch.3

Largest subindex of this object

UINT8

RO

>29<

6020:01

Overvoltage

Overvoltage detected

EL3413-0000: > 415 V (L1-N)
EL3413-0001: > 360 V (L1-N)
EL3413-0120: > 130 V (L1-N)

EL3433-0000: > 288 V (L1-N)

BOOLEAN

RO

0x00 (0dec)

6020:02

Undervoltage

Undervoltage detected
Voltage < 5 V

BOOLEAN

RO

0x00 (0dec)

6020:03

Overcurrent

Overcurrent

BOOLEAN

RO

0x00 (0dec)

6020:05

Phase sequence cw

Phase sequence L1 - L2 - L3 correctly detected
(in clockwise 3-phase network)

BOOLEAN

RO

0x00 (0dec)

6020:06

Phase sequence ccw

Phase sequence L1 - L3 - L2 correctly detected
(in counter-clockwise 3-phase network)

BOOLEAN

RO

0x00 (0dec)

6020:07

Missing zero crossing

No zero crossings detected

BOOLEAN

RO

0x00 (0dec)

6020:0F

TxPDO State

TRUE in the case of frequency, amplitude or general errors

BOOLEAN

RO

0x00 (0dec)

6020:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RW

0x00 (0dec)

6020:11

Current

Current channel 3

Unit: 0.000001 A

INT32

RW

0x00000000 (0dec)

6020:12

Voltage

Voltage channel 3

Unit: 0.0001 V

INT32

RW

0x00000000 (0dec)

6020:13

Active power

Active power channel 3

Unit: 0.01 W

INT32

RW

0x00000000 (0dec)

6020:14

Index

Acknowledge for variable
output value channel 3

Index (dec)

Name

Unit

UINT8

RW

0x00 (0dec)

0

Apparent power

0.01 VA

1

Reactive power

0.01 var

2

Energy

0.001 Wh

3

Power factor

0.001

4

Frequency

0.1 Hz

5

Energy (negative)

0.001 Wh

6

Angle α between phase 3 and phase 1

0.01 °

20***

Active power fundamental (P1)

0.01 W

21***

Apparent power fundamental (S1)

0.01 VA

22***

Reactive power fundamental (Q1)

0.01 var

30****

Energy positive

0.001 Wh

31****

Positive energy, automatically saved

0.001 Wh

32****

Energy, automatic saved

0.001 Wh

35****

Energy negative, automatically saved

0.001 Wh

44***

Frequency average resolution

0.01 Hz

45***

Frequency high resolution

0.001 Hz

46*****

Held frequency

0.1 Hz

47*****

Held frequency average resolution

0.01 Hz

48*****

Held frequency high resolution

0.001 Hz

6020:1D

VariantValue

variable output value channel 3 (see index 0x6020:14)

INT32

RW

0x00000000 (0dec)

***) for EL3413 from firmware 08, EL3413-120 from firmware 04, EL3413-1/EL3433 from firmware 10
****) from firmware 10

Index 6030 PM Inputs Auxiliary 

Index (hex)

Name

Meaning

Data type

Flags

Default

6030:0

PM Inputs Ch.3

Largest subindex of this object

UINT8

RO

>19<

6030:03

Overcurrent

Overcurrent

BOOLEAN

RO

0x00 (0dec)

6030:0F

TxPDO State

TRUE for general error

BOOLEAN

RO

0x00 (0dec)

6030:10

TxPDO Toggle

The TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RW

0x00 (0dec)

6030:11

Index

Acknowledges for auxiliary variables (see following table)

UINT8

RW

0x00 (0dec)

6030:12

Channel

UINT8

RW

0x00 (0dec)

6030:13

Value

variable output value Aux channel (see index 0x6030:12)

INT32

RW

0x00000000 (0dec)

Channel (dec)

Index (dec)

Name

Unit

0

0

Neutral conductor current

0.000001 A

0

2

Sum of the energy (channel 1-3)

0.001 Wh

0

4

Frequency

0.1 Hz

0

5

Sum of the energy (negative) (channel 1-3)
(absolute value)

0.001 Wh

0

10

Sum of the active power (channel 1-3)

0.01 W

0

11

Sum of the apparent power (channel 1-3)

0.01 VA

0

12

Sum of the reactive power (channel 1-3)

0.01 var

0

20***

Active power fundamental (P1)

0.01 W

0

21***

Apparent power fundamental (S1)

0.01 VA

0

22***

Reactive power fundamental (Q1)

0.01 var

0

30****

Energy positive

0.001 Wh

0

31****

Positive energy, automatically saved

0.001 Wh

0

32****

Energy, automatic saved

0.001 Wh

0

35****

Energy negative, automatically saved
(absolute value)

0.001 Wh

0

44***

Frequency average resolution

0.01 Hz

0

45***

Frequency high resolution

0.001 Hz

0

46*****

Held frequency

0.1 Hz

0

47*****

Held frequency average resolution

0.01 Hz

0

48*****

Held frequency high resolution

0.001 Hz

0

100

ADC temperature

0.1℃

1..3

0

Calculation ongoing

 

1..21

RMS value of the xth harmonic (current)

0.000001 A

51..71

Ratio of the xth harmonic to the fundamental (current)

0.01%

100

Calculation ongoing

 

101..121

RMS value of the xth harmonic (voltage)

0.0001 V

151..171

Ratio of the xth harmonic to the fundamental (voltage)

0.01%

11..13

0

Apparent power of phase x

0.01 VA

1

Reactive power of phase x

0.01 var

2

Energy of phase x

0.001 Wh

3

Power factor of phase x

0.001

4

Frequency of phase x

0.1 Hz

5

Energy (negative) of phase x
(absolute value)

0.001 Wh

6

Angle α between phase x and phase 1

0.01 °

10

Active power of phase x

0.01 W

11

Current of phase x

0.000001 A

12

Voltage of phase x

0.0001 V

20***

Active power fundamental (P1)

0.01 W

21***

Apparent power fundamental (S1)

0.01 VA

22***

Reactive power fundamental (Q1)

0.01 var

23***

Cos Phi = Pfund / Sfund with sign from Q1

0.001

44***

Held frequency average resolution

0.01 Hz

45***

Held frequency high resolution

0.001 Hz

***) for EL3413 from firmware 08, EL3413-0120 from firmware 04, EL3413-1/EL3433 from firmware 10

****) from firmware 10

Input data 1:

Calculation of harmonics

It is not possible to calculate harmonics for more than one channel at the same time. Index 00 or 100 is returned until the harmonic calculation has been completed.