Standard objects
Standard objects (0x1000-0x1FFF)
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000 Device type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1000:0 |
Device type |
Device type of the EtherCAT slave: the Lo-Word contains the profile used (5001). |
UINT32 |
RO |
0x01541389 |
Index 1008 Device name
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1008:0 |
Device name |
Device name of the EtherCAT slave |
STRING |
RO |
EL3403 |
Index 1009 Hardware version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1009:0 |
Hardware version |
Hardware version of the EtherCAT slave |
STRING |
RO |
01 |
Index 100A Software version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
100A:0 |
Software version |
Firmware version of the EtherCAT slave |
STRING |
RO |
01 |
Index 1018 Identity
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1018:0 |
Identity |
Length of this object |
UINT8 |
RO |
4 |
|
1018:01 |
Vendor ID |
Vendor ID of the EtherCAT slave |
UINT32 |
RO |
2 |
|
1018:02 |
Product code |
Product code of the EtherCAT slave |
UINT32 |
RO |
0x0D4B3052 (223031378dec) |
|
1018:03 |
Revision |
Revision number of the EtherCAT slave; the low word (bit 0-15) indicates the special terminal number, the high word (bit 16-31) refers to the device description |
UINT32 |
RO |
0x00100000 (1048576dec) |
|
1018:04 |
Serial number |
Serial number of the EtherCAT slave; the low byte (bit 0-7) of the low word contains the year of production, the high byte (bit 8-15) of the low word contains the week of production, the high word (bit 16-31) is 0 |
UINT32 |
RO |
e.g. 0x00001E06 (KW 30/2006) |
Index 10F0 Backup parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
10F0:0 |
Backup parameter |
Length of this object |
UINT8 |
RO |
0x01 |
|
10F0:01 |
Checksum |
Checksum |
UINT32 |
RW |
0x00000000 (0dec) |
Index 1600 RxPDO-Map Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1600:0 |
RxPDO-Map Ch.1 |
PDO mapping of RxPDO 1 |
UINT8 |
RO |
0x01 |
|
1600:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7000 (PM Outputs Ch.1), entry 0x01 (Index)) |
UINT32 |
RW |
0x7000:01, 8 |
Index 1601 RxPDO-Map Ch.2
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1601:0 |
RxPDO-Map Ch.2 |
PDO mapping of RxPDO 2 |
UINT8 |
RO |
0x01 (1dec) |
|
1601:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7010 (PM Outputs Ch.2), entry 0x01 (Index)) |
UINT32 |
RW |
0x7010:01, 8 |
Index 1602 RxPDO-Map Ch.3
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1602:0 |
RxPDO-Map Ch.3 |
PDO mapping of RxPDO 3 |
UINT8 |
RO |
0x01 (1dec) |
|
1602:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7020 (PM Outputs Ch.3), entry 0x01 (Index)) |
UINT32 |
RW |
0x7020:01, 8 |
Index 1A00 TxPDO-Map Ch.1
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A00:0 |
TxPDO-Map Ch.1 |
PDO Mapping of TxPDO 1 |
UINT8 |
RO |
0x0A (10dec) |
|
1A00:01 |
SubIndex 001 |
1. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 13 |
|
1A00:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x1C32 (SM output parameter), entry 0x20 (Sync error)) |
UINT32 |
RW |
0x1C32:20, 1 |
|
1A00:03 |
SubIndex 003 |
3. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 1 |
|
1A00:04 |
SubIndex 004 |
4. PDO Mapping entry () |
UINT32 |
RW |
0x1800:09, 1 |
|
1A00:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6000 (PM Inputs Ch.1), entry 0x11 (Current)) |
UINT32 |
RW |
0x6000:11, 32 |
|
1A00:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6000 (PM Inputs Ch.1), entry 0x12 (Voltage)) |
UINT32 |
RW |
0x6000:12, 32 |
|
1A00:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6000 (PM Inputs Ch.1), entry 0x13 (Active power)) |
UINT32 |
RW |
0x6000:13, 32 |
|
1A00:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6000 (PM Inputs Ch.1), entry 0x14 (Index)) |
UINT32 |
RW |
0x6000:14, 8 |
|
1A00:09 |
SubIndex 009 |
9. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 8 |
|
1A00:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0x6000 (PM Inputs Ch.1), entry 0x1D (VariantValue)) |
UINT32 |
RW |
0x6000:1D, 32 |
Index 1A01 TxPDO-Map Ch.2
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A01:0 |
TxPDO-Map Ch.2 |
PDO Mapping of TxPDO 2 |
UINT8 |
RO |
0x0A (10dec) |
|
1A01:01 |
SubIndex 001 |
1. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 13 |
|
1A01:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x1C32 (SM output parameter), entry 0x20 (Sync error)) |
UINT32 |
RW |
0x1C32:20, 1 |
|
1A01:03 |
SubIndex 003 |
3. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 1 |
|
1A01:04 |
SubIndex 004 |
4. PDO Mapping entry () |
UINT32 |
RW |
0x1801:09, 1 |
|
1A01:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6010 (PM Inputs Ch.2), entry 0x11 (Current)) |
UINT32 |
RW |
0x6010:11, 32 |
|
1A01:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6010 (PM Inputs Ch.2), entry 0x12 (Voltage)) |
UINT32 |
RW |
0x6010:12, 32 |
|
1A01:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6010 (PM Inputs Ch.2), entry 0x13 (Active power)) |
UINT32 |
RW |
0x6010:13, 32 |
|
1A01:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6010 (PM Inputs Ch.2), entry 0x14 (Index)) |
UINT32 |
RW |
0x6010:14, 8 |
|
1A01:09 |
SubIndex 009 |
9. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 8 |
|
1A01:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0x6010 (PM Inputs Ch.2), entry 0x1D (VariantValue)) |
UINT32 |
RW |
0x6010:1D, 32 |
Index 1A02 TxPDO-Map Ch.3
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A02:0 |
TxPDO-Map Ch.3 |
PDO Mapping of TxPDO 3 |
UINT8 |
RO |
0x0A (10dec) |
|
1A02:01 |
SubIndex 001 |
1. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 13 |
|
1A02:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x1C32 (SM output parameter), entry 0x20 (Sync error)) |
UINT32 |
RW |
0x1C32:20, 1 |
|
1A02:03 |
SubIndex 003 |
3. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 1 |
|
1A02:04 |
SubIndex 004 |
4. PDO Mapping entry () |
UINT32 |
RW |
0x1802:09, 1 |
|
1A02:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6020 (PM Inputs Ch.3), entry 0x11 (Current)) |
UINT32 |
RW |
0x6020:11, 32 |
|
1A02:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6020 (PM Inputs Ch.3), entry 0x12 (Voltage)) |
UINT32 |
RW |
0x6020:12, 32 |
|
1A02:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6020 (PM Inputs Ch.3), entry 0x13 (Active power)) |
UINT32 |
RW |
0x6020:13, 32 |
|
1A02:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6020 (PM Inputs Ch.3), entry 0x14 (Index)) |
UINT32 |
RW |
0x6020:14, 8 |
|
1A02:09 |
SubIndex 009 |
9. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 8 |
|
1A02:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0x6020 (PM Inputs Ch.3), entry 0x1D (VariantValue)) |
UINT32 |
RW |
0x6020:1D, 32 |
Index 1A03 TxPDO-Map Status
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A03:0 |
TxPDO-Map Status |
PDO Mapping of TxPDO 4 |
UINT8 |
RO |
0x09 (9dec) |
|
1A03:01 |
SubIndex 001 |
1. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 3 |
|
1A03:02 |
SubIndex 002 |
2. PDO Mapping entry () |
UINT32 |
RW |
0xF130:04, 1 |
|
1A03:03 |
SubIndex 003 |
3. PDO Mapping entry () |
UINT32 |
RW |
0xF130:05, 1 |
|
1A03:04 |
SubIndex 004 |
4. PDO Mapping entry () |
UINT32 |
RW |
0xF130:06, 1 |
|
1A03:05 |
SubIndex 005 |
5. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 2 |
|
1A03:06 |
SubIndex 006 |
6. PDO Mapping entry () |
UINT32 |
RW |
0xF130:09, 1 |
|
1A03:07 |
SubIndex 007 |
7. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 4 |
|
1A03:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x1C32 (SM output parameter), entry 0x20 (Sync error)) |
UINT32 |
RW |
0x1C32:20, 1 |
|
1A03:09 |
SubIndex 009 |
9. PDO Mapping entry (Align) |
UINT32 |
RW |
0x0000:00, 2 |
Index 1C00 Sync manager type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C00:0 |
Sync manager type |
Length of this object |
UINT8 |
RO |
0x04 (4dec) |
|
1C00:01 |
SubIndex 001 |
Sync-Manager Type Channel 1: Mailbox Write |
UINT8 |
RW |
0x01 (1dec) |
|
1C00:02 |
SubIndex 002 |
Sync-Manager Type Channel 2: Mailbox Read |
UINT8 |
RW |
0x02 (2dec) |
|
1C00:03 |
SubIndex 003 |
Sync-Manager Type Channel 3: Process Data Write (Outputs) |
UINT8 |
RW |
0x03 (3dec) |
|
1C00:04 |
SubIndex 004 |
Sync-Manager Type Channel 4: Process Data Read (Inputs) |
UINT8 |
RW |
0x04 (4dec) |
Index 1C12 RxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C12:0 |
RxPDO assign |
PDO Assign of Outputs |
UINT8 |
RO |
0x03 (3dec) |
|
1C12:01 |
Subindex 001 |
1. assigned PDO (RxPDO-Map Ch.1 (RxPDO 1)) |
UINT16 |
RW |
0x1600 (5632dec) |
|
1C12:02 |
Subindex 002 |
2. assigned PDO (RxPDO-Map Ch.2 (RxPDO 2)) |
UINT16 |
RW |
0x1601 (5633dec) |
|
1C12:03 |
Subindex 003 |
3. assigned PDO (RxPDO-Map Ch.3 (RxPDO 3)) |
UINT16 |
RW |
0x1602 (5634dec) |
Index 1C13 TxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:0 |
TxPDO assign |
PDO Assign of Inputs |
UINT8 |
RO |
0x04 (4dec) |
|
1C13:01 |
Subindex 001 |
1. assigned PDO (TxPDO-Map Ch.1 (TxPDO 1)) |
UINT16 |
RW |
0x1A00 (6656dec) |
|
1C13:02 |
Subindex 002 |
2. assigned PDO (TxPDO-Map Ch.2 (TxPDO 2)) |
UINT16 |
RW |
0x1A01 (6657dec) |
|
1C13:03 |
Subindex 003 |
3. assigned PDO (TxPDO-Map Ch.3 (TxPDO 3)) |
UINT16 |
RW |
0x1A02 (6658dec) |
|
1C13:04 |
Subindex 004 |
4. assigned PDO (TxPDO-Map Status (TxPDO 4)) |
UINT16 |
RW |
0x1A03 (6659dec) |
Index 1C32 SM output parameter
|
Index |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C32:0 |
SM output parameter |
Synchronization parameters for the outputs |
UINT8 |
RO |
0x14 (20dec) |
|
1C32:01 |
Sync mode |
Current synchronization mode: 0: Free Run |
UINT16 |
RW |
0x0001 (1dec) |
|
1C32:02 |
Cycle time |
Cycle time (in ns): Free Run: Cycle time of the local timer Synchron with SM 2 Event: Master cycle time DC mode: SYNC0/SYNC1 Cycle Time |
UINT32 |
RW |
0x000AAE60 (700000dec) |
|
1C32:03 |
Shift time |
Time between SYNC0 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C32:04 |
Sync modes supported |
Supported synchronization modes: Bit 0 = 1: free run is supported |
UINT16 |
RW |
0x8007 (32775dec) |
|
1C32:05 |
Minimum cycle time |
Minimum cycle time (in ns) |
UINT32 |
RW |
0x000AAE60 (700000dec) |
|
1C32:06 |
Calc and copy time |
Minimum time between SYNC0 and SYNC1 event (in ns, DC mode only) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C32:08 |
Command |
0: Measurement of the local cycle time is stopped 1: Measurement of the local cycle time is started 0x1C32:033, 0x1C32:05, 0x1C32:06, 0x1C32:09, 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values. |
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:09 |
Delay time |
Time between SYNC1 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C32:0B |
SM event missed counter |
Number of missed SM events in OPERATIONAL (DC mode only) |
UINT166 |
RW |
0x0000 (0dec) |
|
1C32:0C |
Cycle exceeded counter |
Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:0D |
Shift too short counter |
Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only) |
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:20 |
Sync error |
The synchronization was not correct in the last cycle (outputs were output too late; DC mode only) |
BOOLEAN |
RW |
0x00 (0dec) |
Index 1C33 SM input parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C33:0 |
SM input parameter |
Synchronization parameters for the inputs |
UINT8 |
RO |
0x14 (20dec) |
|
1C33:01 |
Sync mode |
Current synchronization mode: 0: Free Run |
UINT16 |
RW |
0x0022 (34dec) |
|
1C33:02 |
Cycle time |
as 0x1C32:02 |
UINT32 |
RW |
0x000AAE60 (700000dec) |
|
1C33:03 |
Shift time |
Time between SYNC0 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C33:04 |
Sync modes supported |
Supported synchronization modes: Bit 0: free run is supported Bit 1: Synchron with SM 2 Event is supported (outputs available) Bit 1: Synchron with SM 3 Event is supported (no outputs available) Bit 2-3 = 01: DC mode is supported Bit 4-5 = 01: input shift through local event (outputs available) Bit 4-5 = 10: input shift with SYNC1 event (no outputs available) Bit 14 = 1: dynamic times (measurement through writing of 0x1C32:08 or 0x1C33:08) |
UINT16 |
RW |
0x8007 (32775dec) |
|
1C33:05 |
Minimum cycle time |
as 0x1C32:05 |
UINT32 |
RW |
0x000AAE60 (700000dec) |
|
1C33:06 |
Calc and copy time |
Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C33:08 |
Command |
as 0x1C32:08 |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:09 |
Delay time |
Time between SYNC1 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RW |
0x00000000 (0dec) |
|
1C33:0B |
SM event missed counter |
as 0x1C32:0B |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:0C |
Cycle exceeded counter |
as 0x1C32:0C |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:0D |
Shift too short counter |
as 0x1C32:0D |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:20 |
Sync error |
as 0x1C32:20 |
BOOLEAN |
RWW |
0x00 (0dec) |