Configuration data
Index 8000 AI Settings bridge
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
8000:0 |
AI Settings bridge |
Maximum subindex |
UINT8 |
RO |
0x18 (24dez) |
8000:01 |
User scale is active. |
BOOLEAN |
RW |
0x00 (0dec) | |
8000:02 |
0: Signed presentation 1: Absolute value with MSB as sign 2: right adjust 24 bit |
BIT3 |
RW |
0x00 (0dec) | |
8000:05 |
The S5 bits are displayed in the three low-order bits. |
BOOLEAN |
RW |
0x00 (0dec) | |
8000:06 |
Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary. |
BOOLEAN |
RW |
0x00 (0dec) | |
8000:07 |
Limit 1 enabled (this setting has no function in EL3351). |
BOOLEAN |
RW |
0x00 (0dec) | |
8000:08 |
Limit 2 enabled (this setting has no function in EL3351). |
BOOLEAN |
RW |
0x00 (0dec) | |
8000:0A |
Enabling of the user calibration |
BOOLEAN |
RW |
0x00 (0dec) | |
8000:0B |
Enabling of the vendor calibration |
BOOLEAN |
RW |
0x01 (1dec) | |
8000:11 |
User scaling offset |
INT32 |
RW |
0x00000000 (0dec) | |
8000:12 |
User scaling gain. |
INT32 |
RW |
0x00010000 (65536dec) | |
8000:15 |
This object determines the digital filter settings. 0: 50 Hz |
UINT16 |
RW |
0x0000 (0dec) | |
8000:17 |
User calibration offset |
UINT32 |
RW |
0x00000000 (0dec) | |
8000:18 |
User calibration gain |
UINT32 |
RW |
0x007FFFFF (8388607dec) |
Index 8010 AI Settings supply
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
8010:0 |
AI Settings supply |
Maximum subindex |
UINT8 |
RO |
0x18 (24dec) |
8010:01 |
1: User scaling is active. |
BOOLEAN |
RW |
0x00 (0dec) | |
8010:02 |
0: Signed presentation 1: Absolute value with MSB as sign 2: right adjust 24 bit |
BIT3 |
RW |
0x00000000 (0dec) | |
8010:05 |
The S5 bits are displayed in the three low-order bits. |
BOOLEAN |
RW |
0x00 (0dec) | |
8010:06 |
Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary |
BOOLEAN |
RW |
0x00 (0dec) | |
8010:07 |
Limit 1 enabled |
BOOLEAN |
RW |
0x00 (0dec) | |
8010:08 |
Limit 2 enabled |
BOOLEAN |
RW |
0x00 (0dec) | |
8010:0A |
Enabling of the user calibration |
BOOLEAN |
RW |
0x00 (0dec) | |
8010:0B |
Enabling of the vendor calibration |
BOOLEAN |
RW |
0x01 (1dec) | |
8010:11 |
User scaling offset |
INT32 |
RW |
0x00000000 (0dec) | |
8010:12 |
User scaling gain. |
INT32 |
RW |
0x00010000 (65536dec) | |
8010:15 |
This object determines the digital filter settings. 0: 50 Hz |
UINT32 |
RW |
0x00000000 (0dec) | |
8010:17 |
User calibration offset |
UINT32 |
RW |
0x00000000 (0dec) | |
8010:18 |
User calibration gain |
UINT32 |
RW |
0x007FFFFF (8388607dec) |