General technical data

Analog inputs

EL3314-0002

Number of inputs

4

Thermocouple sensor types, measured variables

Type B, C, E, J, K, L, N, R, S, T, U (default setting: type K), voltage measurement

Connection technology

2-wire

Maximum cable length to the thermocouple

30 m (without protective measures), suitable surge protection must be provided for longer cable lengths

Resolution

internal 24 bit

Sampling type

simultaneous

Ground reference

Differential

Conversion time

approx. 2.4 s to 4 ms depending on configuration and filter setting;

Preset: approx. 120 ms at 50/60 Hz

Input filter cut-off frequency

typ. 1 kHz

Software filter

2.5...4000 Hz, adjustable, notch characteristic; preset 50/60 Hz

additional low-pass filter possible

Wire break detection

yes (can be disabled)

Supports NoCoeStorage function

yes

Special features

high-precision, electrical isolation

Voltage measurement

EL3314-0002

Measuring ranges

± 78 mV

± 2.5 V

Resolution

1 µV per digit

Measurement uncertainty

See Measurement ±78 mV...±2.5 V

Temperature measurement

EL3314-0002

Electrical measuring range used

± 78 mV

Measuring ranges

Type B: +200...+1820 °C

Type C: 0...+2320 °C

Type E: -270...+1000 °C

Type J: -210...+1200 °C

Type K: -270…+1372 °C (preset)

Type L: -50...+900 °C

Type N: -270...+1300 °C

Type R: -50...+1768 °C

Type S: -50...+1768 °C

Type T: -270...+400 °C

Type U: -50...+600 °C

Resolution

Temperature display 0.1/0.01/0.001 °C per digit, preset 0.01 °C

Measurement uncertainty

See Thermocouples measurement

Supply and potentials

EL3314-0002

Power supply for the electronics

via the E-bus

Current consumption via E-bus

typ. 200 mA

Electrical isolation

2.5 kV functional isolation (test voltage 7 s channel/channel and channel/fieldbus, production test)

Max. potential ±TC to ground

2.5 kV (test voltage production test)

Max. differential voltage between the ±TC inputs

±15 V continuous

Communication

EL3314-0002

Configuration

via TwinCAT System Manager

Width in the process image

max. 24 bytes input,
max. 8 bytes output

Distributed Clocks

-

Environmental conditions

EL3314-0002

Permissible temperature range during operation

0 °C... + 55 °C

Permissible temperature range during storage

-25 °C... + 85 °C

Permissible relative air humidity

95 %, no condensation

General data

EL3314-0002

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Weight

approx. 60 g

Installation

on 35 mm mounting rail, conforms to EN 60715

Installation position

To ensure enhanced measuring accuracy, the terminal must be installed in the prescribed standard position! See note!

Standards and approvals

EL3314-0002

Protection rating

IP20

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Identification / approval*)

CE, UKCA, EAC
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).

Terminal

Extended features

Electrical isolation

TwinSAFE SC

high-precision

Calibration certificate

EL3314

No

No

No

No

EL3314-0002

Yes

No

Yes

No

EL3314-0010

No

No

Yes

No

EL3314-0030

No

No

Yes

External calibration certificate (ISO17025 or DAkkS certificate)

EL3314-0090

No

Yes

No

No

EL3314-0092

Yes

Yes

Yes

No