Default setting
The EL3204-0162 can be used for direct temperature or resistance measurements.
The relationship between temperature and resistance of a PT100/PT1000 sensor is shown below:
Temperature | typical resistance, approx. |
|---|---|
850 °C | PT1000: 3.9 kΩ PT100: 390 Ω |
320 °C | PT1000: 2.2 kΩ PT100: 220 Ω |
-200 °C | PT1000: 180 Ω PT100: 18 Ω |
Characteristic sensor curves are available from the sensor manufacturers.
You can obtain further information in the chapters Object description and parameterization and Process data and operating modes.
| EL3204-0162 |
|---|---|
Default/factory setting | |
Area of application | The terminal is calibrated in the measuring range "1/16 Ω" (10 Ω ... 4 kΩ) and can be used in this resistance range. |
Note regarding Resistance Measurement mode
In Resistance Measurement mode the measured value is always displayed unsigned, irrespective of the Presentation setting (CoE 0x80n00:02), as 0..xFFFF with the respective valence.
1/16 Ω -> ~62 mΩ/digit
1/64 Ω -> ~15 mΩ/digit