Standard objects
Standard objects (1000-1FFF)
Index 1000 Device type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1000:0 |
Device type |
Device type of the EtherCAT slave: the Lo-Word contains the CoE profile used (5001). The Hi-Word contains the module profile according to the modular device profile. |
UINT32 |
RO |
0x01181389 (18355081dec) |
Index 1008 Device name
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1008:0 |
Device name |
Device name of the EtherCAT slave |
STRING |
RO |
EL2819 |
Index 1009 Hardware version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1009:0 |
Hardware version |
Hardware version of the EtherCAT slave |
STRING |
RO |
|
Index 100A Software version
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
100A:0 |
Software version |
Firmware version of the EtherCAT slave |
STRING |
RO |
01 |
Index 1018 Identity
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1018:0 | Identity | Information for identifying the slave | UINT8 | RO | 0x04 (4dec) |
1018:01 | Vendor ID | Vendor ID of the EtherCAT slave | UINT32 | RO | 0x00000002 (2dec) |
1018:02 | Product code | Product code of the EtherCAT slave | UINT32 | RO | 0x07FC3052 (133967954dec) |
1018:03 | Revision | Revision number of the EtherCAT slave; the Low Word (bit 0-15) indicates the special terminal number, the High Word (bit 16-31) refers to the device description | UINT32 | RO | 0x00000000 (0dec) |
1018:04 | Serial number | Serial number of the EtherCAT slave; the Low Byte (bit 0-7) of the Low Word contains the year of production, the High Byte (bit 8-15) of the Low Word contains the week of production, the High Word (bit 16-31) is 0 | UINT32 | RO | 0x00000000 (0dec) |
Index 10F0 Backup parameter handling
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
10F0:0 |
Backup parameter handling |
Information for standardized loading and saving of backup entries |
UINT8 |
RO |
0x01 (1dec) |
|
10F0:01 |
Checksum |
Checksum across all backup entries of the EtherCAT slave |
UINT32 |
RO |
0x00000000 (0dec) |
Index 1600 DIG RxPDO-Map Outputs
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1600:0 |
DIG RxPDO-Map Oputputs |
PDO Mapping RxPDO 1 |
UINT8 |
RO |
0x10 (16dec) |
|
1600:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x7000 (DIG Outputs Ch.01), entry 0x01 (Output)) |
UINT32 |
RO |
0x7000:01, 1 |
|
1600:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x7010 (DIG Outputs Ch.02), entry 0x01 (Output)) |
UINT32 |
RO |
0x7010:01, 1 |
|
1600:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x7020 (DIG Outputs Ch.03), entry 0x01 (Output)) |
UINT32 |
RO |
0x7020:01, 1 |
|
1600:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x7030 (DIG Outputs Ch.04), entry 0x01 (Output)) |
UINT32 |
RO |
0x7030:01, 1 |
|
1600:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x7040 (DIG Outputs Ch.05), entry 0x01 (Output)) |
UINT32 |
RO |
0x7040:01, 1 |
|
1600:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x7050 (DIG Outputs Ch.06), entry 0x01 (Output)) |
UINT32 |
RO |
0x7050:01, 1 |
|
1600:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x7060 (DIG Outputs Ch.07), entry 0x01 (Output)) |
UINT32 |
RO |
0x7060:01, 1 |
|
1600:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x7070 (DIG Outputs Ch.08), entry 0x01 (Output)) |
UINT32 |
RO |
0x7070:01, 1 |
|
1600:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0x7080 (DIG Outputs Ch.09), entry 0x01 (Output)) |
UINT32 |
RO |
0x7080:01, 1 |
|
1600:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0x7090 (DIG Outputs Ch.10), entry 0x01 (Output)) |
UINT32 |
RO |
0x7090:01, 1 |
|
1600:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0x70A0 (DIG Outputs Ch.11), entry 0x01 (Output)) |
UINT32 |
RO |
0x70A0:01, 1 |
|
1600:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0x70B0 (DIG Outputs Ch.12), entry 0x01 (Output)) |
UINT32 |
RO |
0x70B0:01, 1 |
|
1600:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0x70C0 (DIG Outputs Ch.13), entry 0x01 (Output)) |
UINT32 |
RO |
0x70C0:01, 1 |
|
1600:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0x70D0 (DIG Outputs Ch.14), entry 0x01 (Output)) |
UINT32 |
RO |
0x70D0:01, 1 |
|
1600:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0x70E0 (DIG Outputs Ch.15), entry 0x01 (Output)) |
UINT32 |
RO |
0x70E0:01, 1 |
|
1600:10 |
SubIndex 016 |
16. PDO Mapping entry (object 0x70F0 (DIG Outputs Ch.16), entry 0x01 (Output)) |
UINT32 |
RO |
0x70F0:01, 1 |
Index 1A00 DIG TxPDO-Map Diag Inputs
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1A00:0 |
DIG TxPDO-Map Diag Inputs |
PDO Mapping TxPDO 1 |
UINT8 |
RO |
0x40 (64dec) |
|
1A00:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0x6001 (DIG Inputs Ch.01), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6001:01, 1 |
|
1A00:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0x6001 (DIG Inputs Ch.01), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6001:02, 1 |
|
1A00:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0x6001 (DIG Inputs Ch.01), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6001:03, 1 |
|
1A00:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0x6001 (DIG Inputs Ch.01), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6001:04, 1 |
|
1A00:05 |
SubIndex 005 |
5. PDO Mapping entry (object 0x6011 (DIG Inputs Ch.02), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6011:01, 1 |
|
1A00:06 |
SubIndex 006 |
6. PDO Mapping entry (object 0x6011 (DIG Inputs Ch.02), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6011:02, 1 |
|
1A00:07 |
SubIndex 007 |
7. PDO Mapping entry (object 0x6011 (DIG Inputs Ch.02), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6011:03, 1 |
|
1A00:08 |
SubIndex 008 |
8. PDO Mapping entry (object 0x6011 (DIG Inputs Ch.02), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6011:04, 1 |
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1A00:09 |
SubIndex 009 |
9. PDO Mapping entry (object 0x6021 (DIG Inputs Ch.03), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6021:01, 1 |
|
1A00:0A |
SubIndex 010 |
10. PDO Mapping entry (object 0x6021 (DIG Inputs Ch.03), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6021:02, 1 |
|
1A00:0B |
SubIndex 011 |
11. PDO Mapping entry (object 0x6021 (DIG Inputs Ch.03), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6021:03, 1 |
|
1A00:0C |
SubIndex 012 |
12. PDO Mapping entry (object 0x6021 (DIG Inputs Ch.03), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6021:04, 1 |
|
1A00:0D |
SubIndex 013 |
13. PDO Mapping entry (object 0x6031 (DIG Inputs Ch.04), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6031:01, 1 |
|
1A00:0E |
SubIndex 014 |
14. PDO Mapping entry (object 0x6031 (DIG Inputs Ch.04), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6031:02, 1 |
|
1A00:0F |
SubIndex 015 |
15. PDO Mapping entry (object 0x6031 (DIG Inputs Ch.04), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6031:03, 1 |
|
1A00:10 |
Subindex 016 |
16. PDO Mapping entry (object 0x6031 (DIG Inputs Ch.04), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6031:04, 1 |
|
1A00:11 |
Subindex 017 |
17. PDO Mapping entry (object 0x6041 (DIG Inputs Ch.05), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6041:01, 1 |
|
1A00:12 |
Subindex 018 |
18. PDO Mapping entry (object 0x6041 (DIG Inputs Ch.05), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6041:02, 1 |
|
1A00:13 |
Subindex 019 |
19. PDO Mapping entry (object 0x6041 (DIG Inputs Ch.05), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6041:03, 1 |
|
1A00:14 |
Subindex 020 |
20. PDO Mapping entry (object 0x6041 (DIG Inputs Ch.05), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6041:04, 1 |
|
1A00:15 |
Subindex 021 |
21. PDO Mapping entry (object 0x6051 (DIG Inputs Ch.06), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6051:01, 1 |
|
1A00:16 |
Subindex 022 |
22. PDO Mapping entry (object 0x6051 (DIG Inputs Ch.06), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6051:02, 1 |
|
1A00:17 |
Subindex 023 |
23. PDO Mapping entry (object 0x6051 (DIG Inputs Ch.06), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6051:03, 1 |
|
1A00:18 |
Subindex 024 |
24. PDO Mapping entry (object 0x6051 (DIG Inputs Ch.06), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6061:04, 1 |
|
1A00:19 |
Subindex 025 |
25. PDO Mapping entry (object 0x6061 (DIG Inputs Ch.07), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6061:01, 1 |
|
1A00:1A |
Subindex 026 |
26. PDO Mapping entry (object 0x6061 (DIG Inputs Ch.07), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6061:02, 1 |
|
1A00:1B |
Subindex 027 |
27. PDO Mapping entry (object 0x6061 (DIG Inputs Ch.07), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6061:03, 1 |
|
1A00:1C |
Subindex 028 |
28. PDO Mapping entry (object 0x6061 (DIG Inputs Ch.07), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6061:04, 1 |
|
1A00:1D |
Subindex 029 |
29. PDO Mapping entry (object 0x6071 (DIG Inputs Ch.08), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6071:01, 1 |
|
1A00:1E |
Subindex 030 |
30. PDO Mapping entry (object 0x6071 (DIG Inputs Ch.08), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6071:02, 1 |
|
1A00:1F |
Subindex 031 |
31. PDO Mapping entry (object 0x6071 (DIG Inputs Ch.08), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6071:03, 1 |
|
1A00:20 |
Subindex 032 |
32. PDO Mapping entry (object 0x6071 (DIG Inputs Ch.08), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6071:04, 1 |
|
1A00:21 |
Subindex 033 |
33. PDO Mapping entry (object 0x6081 (DIG Inputs Ch.09), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6081:01, 1 |
|
1A00:22 |
Subindex 034 |
34. PDO Mapping entry (object 0x6081 (DIG Inputs Ch.09), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6081:02, 1 |
|
1A00:23 |
Subindex 035 |
35. PDO Mapping entry (object 0x6081 (DIG Inputs Ch.09), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6081:03, 1 |
|
1A00:24 |
Subindex 036 |
36. PDO Mapping entry (object 0x6081 (DIG Inputs Ch.09), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6081:04, 1 |
|
1A00:25 |
Subindex 037 |
37. PDO Mapping entry (object 0x6091 (DIG Inputs Ch.10), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x6091:01, 1 |
|
1A00:26 |
Subindex 038 |
38. PDO Mapping entry (object 0x6091 (DIG Inputs Ch.10), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x6091:02, 1 |
|
1A00:27 |
Subindex 039 |
39. PDO Mapping entry (object 0x6091 (DIG Inputs Ch.10), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x6091:03, 1 |
|
1A00:28 |
Subindex 040 |
40. PDO Mapping entry (object 0x6091 (DIG Inputs Ch.10), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x6091:04, 1 |
|
1A00:29 |
Subindex 041 |
41. PDO Mapping entry (object 0x60A1 (DIG Inputs Ch.11), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x60A1:01, 1 |
|
1A00:2A |
Subindex 042 |
42. PDO Mapping entry (object 0x60A1 (DIG Inputs Ch.11), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x60A1:02, 1 |
|
1A00:2B |
Subindex 043 |
43. PDO Mapping entry (object 0x60A1 (DIG Inputs Ch.11), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x60A1:03, 1 |
|
1A00:2C |
Subindex 044 |
44. PDO Mapping entry (object 0x60A1 (DIG Inputs Ch.11), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x60A1:04, 1 |
|
1A00:2D |
Subindex 045 |
45. PDO Mapping entry (object 0x60B1 (DIG Inputs Ch.12), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x60B1:01, 1 |
|
1A00:2E |
Subindex 046 |
46. PDO Mapping entry (object 0x60B1 (DIG Inputs Ch.12), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x60B1:02, 1 |
|
1A00:2F |
Subindex 047 |
47. PDO Mapping entry (object 0x60B1 (DIG Inputs Ch.12), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x60B1:03, 1 |
|
1A00:30 |
Subindex 048 |
48. PDO Mapping entry (object 0x60B1 (DIG Inputs Ch.12), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x60B1:04, 1 |
|
1A00:31 |
Subindex 049 |
49. PDO Mapping entry (object 0x60C1 (DIG Inputs Ch.13), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x60C1:01, 1 |
|
1A00:32 |
Subindex 050 |
50. PDO Mapping entry (object 0x60C1 (DIG Inputs Ch.13), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x60C1:02, 1 |
|
1A00:33 |
Subindex 051 |
51. PDO Mapping entry (object 0x60C1 (DIG Inputs Ch.13), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x60C1:03, 1 |
|
1A00:34 |
Subindex 052 |
52. PDO Mapping entry (object 0x60C1 (DIG Inputs Ch.13), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x60C1:04, 1 |
|
1A00:35 |
Subindex 053 |
53. PDO Mapping entry (object 0x60D1 (DIG Inputs Ch.14), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x60D1:01, 1 |
|
1A00:36 |
Subindex 054 |
54. PDO Mapping entry (object 0x60D1 (DIG Inputs Ch.14), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x60D1:02, 1 |
|
1A00:37 |
Subindex 055 |
55. PDO Mapping entry (object 0x60D1 (DIG Inputs Ch.14), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x60D1:03, 1 |
|
1A00:38 |
Subindex 056 |
56. PDO Mapping entry (object 0x60D1 (DIG Inputs Ch.14), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x60D1:04, 1 |
|
1A00:39 |
Subindex 057 |
57. PDO Mapping entry (object 0x60E1 (DIG Inputs Ch.15), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x60E1:01, 1 |
|
1A00:3A |
Subindex 058 |
58. PDO Mapping entry (object 0x60E1 (DIG Inputs Ch.15), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x60E1:02, 1 |
|
1A00:3B |
Subindex 059 |
59. PDO Mapping entry (object 0x60E1 (DIG Inputs Ch.15), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x60E1:03, 1 |
|
1A00:3C |
Subindex 060 |
60. PDO Mapping entry (object 0x60E1 (DIG Inputs Ch.15), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x60E1:04, 1 |
|
1A00:3D |
Subindex 061 |
61. PDO Mapping entry (object 0x60F1 (DIG Inputs Ch.16), entry 0x01 (Overtemperature)) |
UINT32 |
RO |
0x60F1:01, 1 |
|
1A00:3E |
Subindex 062 |
62. PDO Mapping entry (object 0x60F1 (DIG Inputs Ch.16), entry 0x02 (Wire Break)) |
UINT32 |
RO |
0x60F1:02, 1 |
|
1A00:3F |
Subindex 063 |
63. PDO Mapping entry (object 0x60F1 (DIG Inputs Ch.16), entry 0x03 (Overcurrent)) |
UINT32 |
RO |
0x60F1:03, 1 |
|
1A00:40 |
Subindex 064 |
64. PDO Mapping entry (object 0x60F1 (DIG Inputs Ch.16), entry 0x04 (Short Circuit)) |
UINT32 |
RO |
0x60F1:04, 1 |
Index 1A02 DIG TxPDO-Map Inputs Device
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1A02:0 |
DIG TxPDO-Map Inputs Device |
PDO Mapping TxPDO |
UINT8 |
RO |
0x05 (5dec) |
|
1A02:01 |
SubIndex 001 |
1. PDO Mapping entry (object 0xF600 (DIG Inputs Device), entry 0x11 (Common Fault)) |
UINT32 |
RO |
0xF600:11, 1 |
|
1A02:02 |
SubIndex 002 |
2. PDO Mapping entry (object 0xF600 (DIG Inputs Device), entry 0x12 (Overtemperature Device)) |
UINT32 |
RO |
0xF600:12, 1 |
|
1A02:03 |
SubIndex 003 |
3. PDO Mapping entry (object 0xF600 (DIG Inputs Device), entry 0x13 (Undervoltage)) |
UINT32 |
RO |
0xF600:13, 1 |
|
1A02:04 |
SubIndex 004 |
4. PDO Mapping entry (object 0xF600 (DIG Inputs Device), entry 0x14 (Missing Voltage)) |
UINT32 |
RO |
0xF600:14, 1 |
|
1A02:05 |
SubIndex 005 |
5. PDO Mapping entry (4 bits align) |
UINT32 |
RO |
0x0000:00, 4 |
Index 1C00 Sync manager type
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C00:0 |
Sync manager type |
Using the sync managers |
UINT8 |
RO |
0x04 (4dec) |
|
1C00:01 |
SubIndex 001 |
Sync-Manager Type Channel 1: Mailbox Write |
UINT8 |
RO |
0x01 (1dec) |
|
1C00:02 |
SubIndex 002 |
Sync-Manager Type Channel 2: Mailbox Read |
UINT8 |
RO |
0x02 (2dec) |
|
1C00:03 |
SubIndex 003 |
Sync-Manager Type Channel 3: Process Data Write (Outputs) |
UINT8 |
RO |
0x03 (3dec) |
|
1C00:04 |
SubIndex 004 |
Sync-Manager Type Channel 4: Process Data Read (Inputs) |
UINT8 |
RO |
0x04 (4dec) |
Index 1C12 RxPDO assign
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1C12:0 | RxPDO assign | PDO Assign Outputs | UINT8 | RW | 0x10 (16dec) |
1C12:01 | SubIndex 001 | 1. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1600 (5632dec) |
1C12:02 | Subindex 002 | 2. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1610 (5648dec) |
1C12:03 | Subindex 003 | 3. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1620 (5664dec) |
1C12:04 | Subindex 004 | 4. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1630 (5680dec) |
1C12:05 | Subindex 005 | 5. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1640 (5696dec) |
1C12:06 | Subindex 006 | 6. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1650 (5712dec) |
1C12:07 | Subindex 007 | 7. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x1660 (5728dec) |
1C12:08 | Subindex 008 | 8. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16700 (5744dec) |
1C12:09 | Subindex 009 | 9. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16800 (5760dec) |
1C12:0A | Subindex 010 | 10. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16900 (5776dec) |
1C12:0B | Subindex 011 | 11. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16A00 (5792dec) |
1C12:0C | Subindex 012 | 12. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16B00 (5808dec) |
1C12:0D | Subindex 013 | 13. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16C00 (5824dec) |
1C12:0E | Subindex 014 | 14. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16D00 (5840dec) |
1C12:0F | Subindex 015 | 15. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16E00 (5856dec) |
1C12:10 | Subindex 016 | 16. allocated RxPDO (contains the index of the associated RxPDO mapping object) | UINT16 | RW | 0x16F00 (5872dec) |
Index 1C13 TxPDO assign
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
|---|---|---|---|---|---|
|
1C13:0 |
TxPDO assign |
PDO Assign Inputs |
UINT8 |
RW |
0x02 (2dec) |
|
1C13:01 |
SubIndex 001 |
1. allocated TxPDO (contains the index of the associated TxPDO mapping object) |
UINT16 |
RW |
0x1A00 (6656dec) |
|
1C13:02 |
Subindex 002 |
|
UINT16 |
RW |
|
|
1C13:03 |
Subindex 003 |
|
UINT16 |
RW |
|
|
1C13:04 |
Subindex 004 |
|
UINT16 |
RW |
|
|
1C13:05 |
Subindex 005 |
|
UINT16 |
RW |
|
|
1C13:06 |
Subindex 006 |
|
UINT16 |
RW |
|
|
1C13:07 |
Subindex 007 |
|
UINT16 |
RW |
|
|
1C13:08 |
Subindex 008 |
|
UINT16 |
RW |
|
|
1C13:09 |
Subindex 009 |
|
UINT16 |
RW |
|
|
1C13:0A |
Subindex 010 |
|
UINT16 |
RW |
|
|
1C13:0B |
Subindex 011 |
|
UINT16 |
RW |
|
|
1C13:0C |
Subindex 012 |
|
UINT16 |
RW |
|
|
1C13:0D |
Subindex 013 |
|
UINT16 |
RW |
|
|
1C13:0E |
Subindex 014 |
|
UINT16 |
RW |
|
|
1C13:0F |
Subindex 015 |
|
UINT16 |
RW |
|
|
1C13:10 |
Subindex 016 |
|
UINT16 |
RW |
|
|
1C13:11 |
Subindex 017 |
|
UINT16 |
RW |
|
|
1C13:12 |
Subindex 018 |
|
UINT16 |
RW |
|
|
1C13:13 |
Subindex 019 |
|
UINT16 |
RW |
|
|
1C13:14 |
Subindex 020 |
|
UINT16 |
RW |
|
|
1C13:15 |
Subindex 021 |
|
UINT16 |
RW |
|
|
1C13:16 |
Subindex 022 |
|
UINT16 |
RW |
|
|
1C13:17 |
Subindex 023 |
|
UINT16 |
RW |
|
|
1C13:18 |
Subindex 024 |
|
UINT16 |
RW |
|
|
1C13:19 |
Subindex 025 |
|
UINT16 |
RW |
|
|
1C13:1A |
Subindex 026 |
|
UINT16 |
RW |
|
|
1C13:1B |
Subindex 027 |
|
UINT16 |
RW |
|
|
1C13:1C |
Subindex 028 |
|
UINT16 |
RW |
|
|
1C13:1D |
Subindex 029 |
|
UINT16 |
RW |
|
|
1C13:1E |
Subindex 030 |
|
UINT16 |
RW |
|
|
1C13:1F |
Subindex 031 |
|
UINT16 |
RW |
|
|
1C13:20 |
Subindex 032 |
|
UINT16 |
RW |
|
|
1C13:21 |
Subindex 033 |
|
UINT16 |
RW |
|
|
1C13:22 |
Subindex 034 |
|
UINT16 |
RW |
|
Index 1C32 SM output parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1C32:0 |
SM output parameter |
Synchronization parameters for the outputs |
UINT8 |
RO |
0x20 (32dec) |
|
1C32:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0001 (1dec) |
|
1C32:02 |
Cycle time |
Cycle time (in ns):
|
UINT32 |
RW |
0x000F4240 (1000000dec) |
|
1C32:03 |
Shift time |
Time between SYNC0 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C32:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0x8002 (32770dec) |
|
1C32:05 |
Minimum cycle time |
Minimum cycle time (in ns) |
UINT32 |
RO |
0x00002710 (10000dec) |
|
1C32:06 |
Calc and copy time |
Minimum time between SYNC0 and SYNC1 event (in ns, DC mode only) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C32:07 |
Minimum delay time |
|
UINT32 |
RO |
0x00000384 (900dec) |
|
1C32:08 |
Command |
The entries 0x1C32:03, 0x1C32:05, 0x1C32:06, 0x1C32:09, 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values. |
UINT16 |
RW |
0x0000 (0dec) |
|
1C32:09 |
Maximum Delay time |
Time between SYNC1 event and output of the outputs (in ns, DC mode only) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C32:0B |
SM event missed counter |
Number of missed SM events in OPERATIONAL (DC mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:0C |
Cycle exceeded counter |
Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:0D |
Shift too short counter |
Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only) |
UINT16 |
RO |
0x0000 (0dec) |
|
1C32:20 |
Sync error |
The synchronization was not correct in the last cycle (outputs were output too late; DC mode only) |
BOOLEAN |
RO |
0x00 (0dec) |
Index 1C33 SM input parameter
|
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default value |
|---|---|---|---|---|---|
|
1C33:0 |
SM input parameter |
Synchronization parameters for the inputs |
UINT8 |
RO |
0x20 (32dec) |
|
1C33:01 |
Sync mode |
Current synchronization mode:
|
UINT16 |
RW |
0x0022 (34dec) |
|
1C33:02 |
Cycle time |
as 0x1C32:02 |
UINT32 |
RW |
0x000F4240 (1000000dec) |
|
1C33:03 |
Shift time |
Time between SYNC0 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C33:04 |
Sync modes supported |
Supported synchronization modes:
|
UINT16 |
RO |
0x8002 (32770dec) |
|
1C33:05 |
Minimum cycle time |
as 0x1C32:05 |
UINT32 |
RO |
0x00002710 (10000dec) |
|
1C33:06 |
Calc and copy time |
Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode) |
UINT32 |
RO |
0x00000000 (0dec) |
|
1C33:07 |
Minimum delay time |
|
UINT32 |
RO |
0x00000384 (900dec) |
|
1C33:08 |
Command |
as 0x1C32:08 |
UINT16 |
RW |
0x0000 (0dec) |
|
1C33:09 |
Maximum Delay time |
Time between SYNC1 event and reading of the inputs (in ns, only DC mode) |
UINT32 |
RO |
0x00000384 (900dec) |
|
1C33:0B |
SM event missed counter |
as 0x1C32:11 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0C |
Cycle exceeded counter |
as 0x1C32:12 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:0D |
Shift too short counter |
as 0x1C32:13 |
UINT16 |
RO |
0x0000 (0dec) |
|
1C33:20 |
Sync error |
as 0x1C32:32 |
BOOLEAN |
RO |
0x00 (0dec) |
Index F000 Modular device profile
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
F000:0 | Modular device profile | General information for the modular device profile | UINT8 | RO | 0x02 (2dec) |
F000:01 | Module index distance | Index spacing of the objects of the individual channels | UINT16 | RO | 0x0010 (16dec) |
F000:02 | Maximum number of modules | Number of channels | UINT16 | RO | 0x0010 (16dec) |
Index F008 Code word
Index (hex) | Name | Meaning | Data type | Flags | Default value |
|---|---|---|---|---|---|
F008:0 | Code word | NoCoeStorage function: The input code of the code word 0x12345678 activates the NoCoeStorage function: | UINT32 | RW | 0x00000000 (0dec) |
Index F010 Module list
Index (hex) | Name | Meaning | Data type | Flags | Default value |
|---|---|---|---|---|---|
F010:0 | Module list | Maximum subindex | UINT8 | RW | 0x10 (16dec) |
F010:01 | SubIndex 001 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:02 | SubIndex 002 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:03 | SubIndex 003 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:04 | SubIndex 004 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:05 | SubIndex 005 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:06 | SubIndex 006 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:07 | SubIndex 007 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:08 | SubIndex 008 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:09 | SubIndex 009 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:0A | SubIndex 010 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:0B | SubIndex 011 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:0C | SubIndex 012 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:0D | SubIndex 013 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:0E | SubIndex 014 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:0F | SubIndex 015 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |
F010:10 | SubIndex 016 | Profil 280 (Extended Digital Input and Output with Diagnostics) | UINT32 | RW | 0x00000118 (280dec) |