Notes on commissioning

Observe the following notes before commissioning:

Notice

Application from FW02/Revision0017

The documentation applies to the EL2596 only from firmware 02 with the revision -0017. With all older software revisions it is mandatory to perform a firmware update EL/ES/ELM/EM/EPxxxx and to update the ESI files in TwinCAT.

Time behavior in continuous light mode

The time behavior in continuous light mode is illustrated in the following figure.

Notes on commissioning 3:
Fig.142: Timing - Continuous light

Time behavior in pulse mode

The time behavior in a pulse mode is illustrated in the following figure.

Notes on commissioning 4:
Fig.143: Timing - Pulse

The time behavior in pulse mode with an external trigger signal is illustrated in the following figure. Two different cases of the output of a pulse by trigger input are shown.

Notes on commissioning 5:
Fig.144: Timing - External trigger

In order to set the LED output, Input trigger enable must be activated in addition to the Output bit in order to enable the trigger function.

Case 1 – no delay:

Case 2 – with delay: