Technical data

Device functions

EL2596

EL2596-0010

Application recommendation

Standard terminal for the vision application on lighting up to 24 V DC

Standard terminal for the vision application on lighting up to 48 V DC

Connection technology

2-wire

Number of outputs

1

Input voltage UIN

24 VDC (-15 %/+20 %)

Use only a regulated power supply unit for the supply of power

48 VDC (-15 %/+20 %)

Use only a regulated power supply unit for the supply of power

Load type

LED (ohmic), potential-free

Special features

Operation modes: Constant voltage, constant current, PWM; extensive real-time diagnostics; voltage divider connection option, TriggerOut; LED continuous operation possible, operation of a multi-color Common Anode LED

LED output

EL2596

EL2596-0010

Output voltage UOUT

Continuous light: 0 ... (UIN - 0.5 V)

Pulsed mode (0 ... 2 A): 0 ... (UIN – 2 V)

Pulsed mode (3 A*): 0 ... (UIN – 3 V)

*linear behavior of the maximum output voltage between 2 A and 3 A

Output current IOUT

In pulse mode: 0 mA ... 3 A (depending on output voltage and duty cycle)

In continuous light mode: 0 mA …1.2 A

For EL2596-0010 only for operation with fan (ZB8610).

Output power POut

max. 14.4 W

Control accuracy of output current IOUT

< ±3 mA in Current Control and Current Control PWM mode

corresponds to < ±0.1% of the output end value 3 A

Pulse duration at the LED output

> 25 µs .. 10 s (lower values on request)

Switching times

TON: < 1 µs typ., TOFF: < 1 µs typ.

Trigger input (from camera)

EL2596

EL2596-0010

Number

1

Type

Electrically isolated,
3 mA typ.,
0 … 30 VDC,
Sensitivity of the trigger level can be switched in the CoE:
High = 10 V, Low = 5 V (from HW02: 4 V)

Maximum input frequency at the trigger input

20 kHz

Input filter of trigger input

5 µs

Blind time of the trigger input

0 µs (< FW04) or 20 µs…65535 µs (from FW04)

Trigger output (to the camera)

EL2596

EL2596-0010

Number

1

Type

Electrically isolated,
max. 10 mA push-pull,
10 … 24 VDC (voltage can be changed by externally connectable voltage divider)

Pulse duration at trigger output

25 µs ... 10 s

Pulse delay in relation to the trigger input

2 µs … 10 s

Supply and potentials

EL2596

EL2596-0010

Power supply for the electronics

via the E-bus

Current consumption via E-bus

typ. 240 mA

typ. 265 mA

Electrical isolation

500 V (E-bus/field voltage)

Current consumption power contacts

- (Power contacts are only passed through)

Communication

EL2596

EL2596-0010

Configuration

via TwinCAT System Manager

Distributed clocks

yes

Accuracy Distributed Clocks

<< 1 µs

min. cycle time in distributed clocks mode

200 µs

Environmental conditions

EL2596

EL2596-0010

Permissible ambient temperature range during operation

0°C ... + 55°C

Permissible ambient temperature range during storage

-25°C ... + 85°C

Permissible relative air humidity

95 %, no condensation

General data

EL2596

EL2596-0010

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Weight

approx. 57 g

Mounting

on 35 mm mounting rail according to EN 60715

Installation position

see Prescribed installation position

Standards and approvals

EL2596

EL2596-0010

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Approvals/markings*)

CE, EAC, UKCA

*) Real applicable approvals/markings see type plate on the side (product marking).