Quick start

Connecting the terminal

Install the terminal as described in the chapter entitled Installation.

Parameterizing the terminal

  1. If provided, the current ESI (XML file) EL2595-0000-xxxx is to be installed in TwinCAT (usually under C:\TwinCAT\IO\EtherCAT\).
    Otherwise, please download the latest ESI from the Beckhoff-Website.
  2. If necessary, a firmware update is to be carried out. Check then in the online CoE.
  3. Following the firmware update you are urgently recommended to carry out a "Restore default parameter" in the CoE: enter "0x64616F6C" in CoE index 0x1011:01
  4. The key data of the intended LED must be determined:

5. Further useful CoE settings

Quick start 1:Fig.126: Representation of warning thresholds

The percentage value (e.g. here: warning: 5 for ±5%, error: 10 for ±10%) must be entered in the CoE index 0x8000:11-14.

6. For safety’s sake these CoE data can also be entered into the Startup list. If the EL2595 is exchanged later, the online CoE data are no longer available. The system manager then writes the data to the new terminal.

7. The output can now be switched on via the process data (PDO) Control.Output = TRUE or a pulse of a defined length can be output in DC mode via a timestamp.

8. The present set output current can also be specified from the controller by cyclic PDO:

Additional Notes