Safe state in the event of a bus error (watchdog)
The setting in index 0x80n0:05 "Watchdog" fixes whether the output should assume a safe state in the event of a bus error. The following options are available (n = 0 for channel 1, n = 1 for channel 2):
Desired state | Default in 0x80n0:05 "Watchdog" |
|---|---|
set to specified value | 0: default watchdog value |
Retain current value | 2: Last value |
Notice | |
Watchdog parameterization can trigger unintended actions! Please refer to chapter "Notes for setting the watchdog"! |