Output data
Index 0x7pp0 DOX Outputs (Ch.1, pp=00; Ch.2, pp=01)
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
7pp0:0 | DOX Outputs |
| UINT8 | RO | 0x13 (19dec) |
7pp0:02 | Output | activates the output stage | BOOLEAN | RO | 0x00 (0dec) |
7pp0:03 | Tristate | Switches the output stage to tristate | BOOLEAN | RO | 0x00 (0dec) |
7pp0:04 | PWM | switches PWM through to the output stage | BOOLEAN | RO | 0x00 (0dec) |
7pp0:08 | Reset | all errors that may have occurred are reset by setting this bit (rising edge) | BOOLEAN | RO | 0x00 (0dec) |
7pp0:11 | Duty cycle | PWM duty factor (see also DOX settings) | UINT8 | RO | 0x00 (0dec) |
7pp0:13 | PWM Tperiod | Period duration of the PWM output via PDO (in ms). If the PDO value = 0, then the configured value is taken from the CoE. | UINT16 | RW | 0x0000 (0dec) |
Index 0x7pp1 MTO Outputs (Ch.1, pp=02; Ch.2, pp=03)
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
7pp1:0 | MTO outputs Ch.p |
| UINT8 | RO | 0x4A (74dec) |
7pp1:01 | Output buffer reset | Clear events in the output buffer | BOOLEAN | RO | 0x00 (0dec) |
7pp0:02 | Manual output state | Set the output permanently to this value (must be activated in CoE) | BOOLEAN | RO | 0x00 (0dec) |
7pp1:03 | Force order | Already expired events are also output | BOOLEAN | RO | 0x00 (0dec) |
7pp1:04 | Enable manual operation | If this bit is activated, the output is overwritten with the value in "Manual output state". | BOOLEAN | RO | 0x00 (0dec) |
7pp1:09 | Output order counter | Incrementation of this value indicates to the terminal that there are new values in the PDO | UINT8 | RO | 0x00 (0dec) |
7pp1:11 | No of output events | Number of events deposited in the PDO | UINT8 | RO | 0x00 (0dec) |
7pp0:21 | Output event state 1 | Output value at the time of the nth time stamp | BOOLEAN | RO | 0x00 (0dec) |
…. | …. | …. | …. | …. | ….. |
7pp1:2A | Output event state 10 |
| BOOLEAN | RO | 0x00 (0dec) |
7pp1:41 | Output event time 1 | Time stamp of the nth event | UINT32 | RO | 0x00000000 (0dec) |
…. | …. | …. | …. | …… | ….. |
7pp1:4A | Output event time 10 |
| UINT32 | RO | 0x00000000 (0dec) |