Overview of EtherCAT Couplers
An EtherCAT coupler is required in order to connect EtherCAT Terminals with E-bus-communication (series ELxxxx, ESxxxx, EMxxxx) to an EtherCAT network. This coupler relays the communication from the higher-level EtherCAT network to the terminals, or functions as a master itself and generates telegrams. Beckhoff offers different components for different application scenarios.
The selection of the correct coupler depends on the following criteria:
- is a local small controller needed?
- is the coupler to be connected via copper cable or optical fiber cable?
- is the coupler to be addressed via IP or is it located in the unswitched network?
- is the coupler to be controlled via EAP (EtherCAT Automation Protocol) or EtherCAT Device Protocol?
- required protection class: IP20 or higher?
- is the coupler to be plugged in at different places at the network using the HotConnect technique?
A coupler connects the added terminals to the right; it can be connected to the higher level network to the left. Couplers that support the EtherCAT Device Protocol ‘to the left’ must be connected there to an EtherCAT master.

Comparative overview of Beckhoff EtherCAT Couplers
|
|
|
|
|
|
The following tables show a comparative overview of Beckhoff EtherCAT Couplers. An up-to-date, complete product overview can be found on the Beckhoff homepage.
Notice | ||
![]() | Device documentation is solely authoritative The indications may be shortened extracts from the respective documentation, which is decisive and recommended for detailed analysis. |
EtherCAT Coupler | ||
---|---|---|
Property | EK1100 | EK1100-0008 |
Protection rating | IP20 | |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) | |
Higher-level network – max. connection length | 100 m | |
Higher-level network – connection technology | RJ45 | M8 |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | |
integrated PLC | - | |
supports HotConnect with address setting on the device | - | |
Note | "Standard" coupler for use directly on the EtherCAT master |
|
EtherCAT Coupler with ID switch | ||||
---|---|---|---|---|
Property | EK1101 | EK1101-0008 | EK1101-0010 | EK1101-0080 |
Protection rating | IP20 | |||
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) | |||
Higher-level network – max. connection length | 100 m | 100 m | 300 m between two couplers with extended distance connection | 100 m |
Higher-level network – connection technology | RJ45
| M8 | RJ45 | RJ45 |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | |||
integrated PLC | - | |||
supports HotConnect with address setting on the device | yes | yes, Fast-Hot-Connect | ||
Note |
|
| max. 300 m length between the stations (copper, Cat. 5, 4-wire) |
|
EtherCAT P Coupler | |
---|---|
Property | EK1300 |
Protection rating | IP20 |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) |
Higher-level network – max. connection length | 100 m |
Higher-level network – connection technology | 2 x M8 sockets, shielded, screwable, P-coded |
Higher-level network - protocol | EtherCAT device protocol (to 100BASE-TX EtherCAT P networks) |
integrated PLC | - |
supports HotConnect with address setting on the device | - |
Note | Coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCAT P networks |
Fiber optic EtherCAT Coupler with ID switch | |||
---|---|---|---|
Property | EK1501 | EK1501-0010 | EK1501-0100 |
Protection rating | IP20 | ||
Higher-level network - technology | 100 MBit FastEthernet (100BASE-FX) | 100 Mbit FastEthernet | |
Higher-level network – max. connection length | 2 km | 20 km | 100BASE-FX: 2 km |
Higher-level network – connection technology | SC-Duplex | SC-Duplex | SC-Duplex |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | ||
integrated PLC | - | ||
supports HotConnect with address setting on the device | yes |
POF EtherCAT Coupler with ID switch | |
---|---|
Property | EK1541 |
Protection rating | IP20 |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-FX) POF |
Higher-level network – max. connection length | 50 m |
Higher-level network – connection technology | Versatile Link |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) |
integrated PLC | - |
supports HotConnect with address setting on the device | yes |
Further EtherCAT Couplers | |||||
---|---|---|---|---|---|
Property | EK18xx | EK9000 | EKx000 | EPxxxx | CX8000 |
Protection rating | IP20 | IP20 | IP20 | IP67 | IP20 |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) | 100 MBit FastEthernet | Various | 100 MBit FastEthernet | 100 MBit FastEthernet |
Higher-level network – max. connection length | 100 m | 100 m | see doc. | 100 m | 100 m |
Higher-level network – connection technology | RJ45 | RJ45 | see doc. | M8 | RJ45 |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | EAP | see doc. | EtherCAT Device Protocol (formerly Direct Mode) | EtherCAT Device Protocol (formerly Direct Mode) |
integrated PLC | - | - | - | - | yes |
supports HotConnect with address setting on the device | - | - | - | - | - |
Note | The EK18xx devices integrate a coupler for application directly at the EtherCAT master and digital inputs and outputs without additional wiring. | The EK9000 can be controlled in a switched EtherCAT network with directed IP addressing. | If the EK9000 is provided with another fieldbus connection, this gives rise to the appropriate EKx000 Coupler. | Technologically, each EP Box represents a self-contained EtherCAT Coupler with internally added I/O functions. | The CX8000 appears to the higher-level EtherCAT network as an EtherCAT slave while at the same time managing its attached I/Os as a master. |