Overview of EtherCAT Couplers
An EtherCAT coupler is required in order to connect EtherCAT Terminals with E-bus-communication (series ELxxxx, ESxxxx, EMxxxx) to an EtherCAT network. This coupler relays the communication from the higher-level EtherCAT network to the terminals, or functions as a master itself and generates telegrams. Beckhoff offers different components for different application scenarios.
The selection of the correct coupler depends on the following criteria:
- is a local small controller needed?
- is the coupler to be connected via copper cable or optical fiber cable?
- is the coupler to be addressed via IP or is it located in the unswitched network?
- is the coupler to be controlled via EAP (EtherCAT Automation Protocol) or EtherCAT Device Protocol?
- required protection class: IP20 or higher?
- is the coupler to be plugged in at different places at the network using the HotConnect technique?
A coupler connects the added terminals to the right; it can be connected to the higher level network to the left. Couplers that support the EtherCAT Device Protocol ‘to the left’ must be connected there to an EtherCAT master.
Fig.4: EtherCAT coupler communication diagramComparative overview of Beckhoff EtherCAT Couplers
|
|
|
|
|
|
The following tables show a comparative overview of Beckhoff EtherCAT Couplers. An up-to-date, complete product overview can be found on the Beckhoff homepage.
Notice | ||
![]() | Device documentation is solely authoritative The indications may be shortened extracts from the respective documentation, which is decisive and recommended for detailed analysis. | |
EtherCAT Coupler | ||
|---|---|---|
Property | EK1100 | EK1100-0008 |
Protection rating | IP20 | |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) | |
Higher-level network – max. connection length | 100 m | |
Higher-level network – connection technology | RJ45 | M8 |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | |
integrated PLC | - | |
supports HotConnect with address setting on the device | - | |
Note | "Standard" coupler for use directly on the EtherCAT master |
|
EtherCAT Coupler with ID switch | ||||
|---|---|---|---|---|
Property | EK1101 | EK1101-0008 | EK1101-0010 | EK1101-0080 |
Protection rating | IP20 | |||
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) | |||
Higher-level network – max. connection length | 100 m | 100 m | 300 m between two couplers with extended distance connection | 100 m |
Higher-level network – connection technology | RJ45
| M8 | RJ45 | RJ45 |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | |||
integrated PLC | - | |||
supports HotConnect with address setting on the device | yes | yes, Fast-Hot-Connect | ||
Note |
|
| max. 300 m length between the stations (copper, Cat. 5, 4-wire) |
|
EtherCAT P Coupler | |
|---|---|
Property | EK1300 |
Protection rating | IP20 |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) |
Higher-level network – max. connection length | 100 m |
Higher-level network – connection technology | 2 x M8 sockets, shielded, screwable, P-coded |
Higher-level network - protocol | EtherCAT device protocol (to 100BASE-TX EtherCAT P networks) |
integrated PLC | - |
supports HotConnect with address setting on the device | - |
Note | Coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCAT P networks |
Fiber optic EtherCAT Coupler with ID switch | |||
|---|---|---|---|
Property | EK1501 | EK1501-0010 | EK1501-0100 |
Protection rating | IP20 | ||
Higher-level network - technology | 100 MBit FastEthernet (100BASE-FX) | 100 Mbit FastEthernet | |
Higher-level network – max. connection length | 2 km | 20 km | 100BASE-FX: 2 km |
Higher-level network – connection technology | SC-Duplex | SC-Duplex | SC-Duplex |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | ||
integrated PLC | - | ||
supports HotConnect with address setting on the device | yes | ||
POF EtherCAT Coupler with ID switch | |
|---|---|
Property | EK1541 |
Protection rating | IP20 |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-FX) POF |
Higher-level network – max. connection length | 50 m |
Higher-level network – connection technology | Versatile Link |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) |
integrated PLC | - |
supports HotConnect with address setting on the device | yes |
Further EtherCAT Couplers | |||||
|---|---|---|---|---|---|
Property | EK18xx | EK9000 | EKx000 | EPxxxx | CX8000 |
Protection rating | IP20 | IP20 | IP20 | IP67 | IP20 |
Higher-level network - technology | 100 MBit FastEthernet (100BASE-TX) | 100 MBit FastEthernet | Various | 100 MBit FastEthernet | 100 MBit FastEthernet |
Higher-level network – max. connection length | 100 m | 100 m | see doc. | 100 m | 100 m |
Higher-level network – connection technology | RJ45 | RJ45 | see doc. | M8 | RJ45 |
Higher-level network - protocol | EtherCAT Device Protocol (formerly Direct Mode) | EAP | see doc. | EtherCAT Device Protocol (formerly Direct Mode) | EtherCAT Device Protocol (formerly Direct Mode) |
integrated PLC | - | - | - | - | yes |
supports HotConnect with address setting on the device | - | - | - | - | - |
Note | The EK18xx devices integrate a coupler for application directly at the EtherCAT master and digital inputs and outputs without additional wiring. | The EK9000 can be controlled in a switched EtherCAT network with directed IP addressing. | If the EK9000 is provided with another fieldbus connection, this gives rise to the appropriate EKx000 Coupler. | Technologically, each EP Box represents a self-contained EtherCAT Coupler with internally added I/O functions. | The CX8000 appears to the higher-level EtherCAT network as an EtherCAT slave while at the same time managing its attached I/Os as a master. |