Standard objects
Index 1000 Device type
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1000:0  | Device type  | Device type of the EtherCAT slave: The Lo-Word contains the CoE profile used (5001). The Hi-Word contains the module profile according to the modular device profile.  | UINT32  | RO  | 0x00001389 (5001dec)  | 
Index 1008 Device name
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1008:0  | Device name  | Device name of the EtherCAT slave  | STRING  | RO  | EJ7411  | 
Index 1009 Hardware version
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1009:0  | Hardware version  | Hardware version of the EtherCAT slave  | STRING  | RO  | 
  | 
Index 100A Software version
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
100A:0  | Software version  | Firmware version of the EtherCAT slave  | STRING  | RO  | 01  | 
Index 100B Bootloader version
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
100B:0  | Bootloader version  | Bootloader version  | STRING  | RO  | 
  | 
Index 1018 Identity
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1018:0  | Identity  | Information for identifying the slave  | UINT8  | RO  | 0x04 (4dec)  | 
1018:01  | Vendor ID  | Vendor ID of the EtherCAT slave  | UINT32  | RO  | 0x00000002 (2dec)  | 
1018:02  | Product code  | Product code of the EtherCAT slave  | UINT32  | RO  | 0x1CF32852 (485697618dec)  | 
1018:03  | Revision  | Revision number of the EtherCAT slave; the Low Word (bit 0-15) indicates the special device number, the High Word (bit 16-31) refers to the device description  | UINT32  | RO  | 0x00000000 (0dec)  | 
1018:04  | Serial number  | Serial number of the EtherCAT slave; the Low Byte (bit 0-7) of the Low Word contains the year of production, the High Byte (bit 8-15) of the Low Word contains the week of production, the High Word (bit 16-31) is 0  | UINT32  | RO  | 0x00000000 (0dec)  | 
Index 10E2 Manufacturer-specific Identification Code
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
10E2:0  | Manufacturer-specific identification code  | 
  | UINT8  | RO  | 0x01 (1dec)  | 
10E2:01  | SubIndex 001  | 
  | STRING  | RO  | 
  | 
Index 10F0 Backup parameter handling
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
10F0:0  | Backup parameter handling  | Information for standardized loading and saving of backup entries  | UINT8  | RO  | 0x01 (1dec)  | 
10F0:01  | Checksum  | Checksum across all backup entries of the EtherCAT slave  | UINT32  | RO  | 0x00000000 (0dec)  | 
Index 10F3 Diagnosis History
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
10F3:0  | Diagnosis History  | Maximum subindex  | UINT8  | RO  | 0x37 (55dec)  | 
10F3:01  | Maximum Messages  | Maximum number of stored messages. A maximum of 50 messages can be stored  | UINT8  | RO  | 0x00 (0dec)  | 
10F3:02  | Newest Message  | Subindex of the latest message  | UINT8  | RO  | 0x00 (0dec)  | 
10F3:03  | Newest Acknowledged Message  | Subindex of the last confirmed message  | UINT8  | RW  | 0x00 (0dec)  | 
10F3:04  | New Messages Available  | Indicates that a new message is available  | BOOLEAN  | RO  | 0x00 (0dec)  | 
10F3:05  | Flags  | not used  | UINT16  | RW  | 0x0000 (0dec)  | 
10F3:06  | Diagnosis Message 001  | Message 1  | OCTET-STRING[28]  | RO  | {0}  | 
...  | ...  | ...  | ...  | ...  | ...  | 
10F3:37  | Diagnosis Message 050  | Message 50  | OCTET-STRING[28]  | RO  | {0}  | 
Index 10F8 Actual Time Stamp
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
10F8:0  | Actual Time Stamp  | Timestamp  | UINT64  | RO  | 
  | 
Index 1600 DRV RxPDO-map control word
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1600:0  | DRV RxPDO-map control word  | PDO Mapping RxPDO 1  | UINT8  | RO  | 0x01 (1dec)  | 
1600:01  | SubIndex 001  | 1. PDO mapping entry (object 0x7010 (DRV outputs), entry 0x01 (control word))  | UINT32  | RO  | 0x7010:01, 16  | 
Index 1601 DRV RxPDO-map target velocity
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1601:0  | DRV RxPDO-map target velocity  | PDO Mapping RxPDO 2  | UINT8  | RO  | 0x01 (1dec)  | 
1601:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x7010 (DRV Outputs), entry 0x06 (Target velocity))  | UINT32  | RO  | 0x7010:06, 32  | 
Index 1602 DRV RxPDO-Map Target torque
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1602:0  | DRV RxPDO-Map Target torque  | PDO Mapping RxPDO 3  | UINT8  | RO  | 0x01 (1dec)  | 
1602:01  | SubIndex 001  | 1. PDO mapping entry (object 0x7010 (DRV outputs), entry 0x09 (target torque))  | UINT32  | RO  | 0x7010:09, 16  | 
Index 1603 DRV RxPDO-map commutation angle
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1603:0  | DRV RxPDO-map commutation angle  | PDO Mapping RxPDO 4  | UINT8  | RO  | 0x01 (1dec)  | 
1603:01  | SubIndex 001  | 1. PDO mapping entry (object 0x7010 (DRV outputs), entry 0x0E (commutation angle))  | UINT32  | RO  | 0x7010:0E, 16  | 
Index 1604 DRV RxPDO-map torque limitation
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1604:0  | DRV RxPDO-map torque limitation  | PDO Mapping RxPDO 5  | UINT8  | RO  | 0x01 (1dec)  | 
1604:01  | SubIndex 001  | 1. PDO mapping entry (object 0x7010 (DRV outputs), entry 0x0B (torque limitation))  | UINT32  | RO  | 0x7010:0B, 16  | 
Index 1606 DRV RxPDO-Map Target position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1606:0  | DRV RxPDO-Map Target position  | PDO Mapping RxPDO 7  | UINT8  | RO  | 0x01 (1dec)  | 
1606:01  | SubIndex 001  | 1. PDO mapping entry (object 0x7010 (DRV outputs), entry 0x05 (target position))  | UINT32  | RO  | 0x7010:05, 32  | 
Index 1607 FB RxPDO-Map Touch probe control
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1607:0  | FB RxPDO-Map Touch probe control  | PDO Mapping RxPDO 8  | UINT8  | RO  | 0x0C (12dec)  | 
1607:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x01 (TP1 Enable))  | UINT32  | RO  | 0x7001:01, 1  | 
1607:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x02 (TP1 Continous))  | UINT32  | RO  | 0x7001:02, 1  | 
1607:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x03 (TP1 Trigger mode))  | UINT32  | RO  | 0x7001:03, 2  | 
1607:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x05 (TP1 Enable pos edge))  | UINT32  | RO  | 0x7001:05, 1  | 
1607:05  | SubIndex 005  | 5. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x06 (TP1 Enable neg edge))  | UINT32  | RO  | 0x7001:06, 1  | 
1607:06  | SubIndex 006  | 6. PDO Mapping entry (2 bits align)  | UINT32  | RO  | 0x0000:00, 2  | 
1607:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x09 (TP2 Enable))  | UINT32  | RO  | 0x7001:09, 1  | 
1607:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x0A (TP2 Continous))  | UINT32  | RO  | 0x7001:0A, 1  | 
1607:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x0B (TP2 Trigger mode))  | UINT32  | RO  | 0x7001:0B, 2  | 
1607:0A  | SubIndex 010  | 10. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x0D (TP2 Enable pos edge))  | UINT32  | RO  | 0x7001:0D, 1  | 
1607:0B  | SubIndex 011  | 11. PDO Mapping entry (object 0x7001 (FB Touch probe outputs), entry 0x0E (TP2 Enable neg edge))  | UINT32  | RO  | 0x7001:0E, 1  | 
1607:0C  | SubIndex 012  | 12. PDO Mapping entry (2 bits align)  | UINT32  | RO  | 0x0000:00, 2  | 
Index 1640 DMC RxPDO-Map Outputs
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1640:0  | DMC RxPDO-Map Outputs  | DMC RxPDO-Map Outputs  | UINT8  | RO  | 0x12 (18dec)  | 
1640:01  | SubIndex 001  | 1. PDO Mapping entry (1 bit align)  | UINT32  | RO  | 0x0000:00, 1  | 
1640:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x02 (DMC_FeedbackControl__Enable latch extern on positive edge))  | UINT32  | RO  | 0x7040:02, 1  | 
1640:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x03 (DMC_FeedbackControl__Set counter))  | UINT32  | RO  | 0x7040:03, 1  | 
1640:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x04 (DMC__FeedbackControl__Enable latch extern on negative edge))  | UINT32  | RO  | 0x7040:04, 1  | 
1640:05  | SubIndex 005  | 5. PDO Mapping entry (12 bits align)  | UINT32  | RO  | 0x0000:00, 12  | 
1640:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x11 (DMC__DriveControl__Enable))  | UINT32  | RO  | 0x7040:11, 1  | 
1640:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x12 (DMC__DriveControl__Reset))  | UINT32  | RO  | 0x7040:12, 1  | 
1640:08  | SubIndex 008  | 8. PDO Mapping entry (14 bits align)  | UINT32  | RO  | 0x0000:00, 14  | 
1640:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x21 (DMC__PositioningControl__Execute))  | UINT32  | RO  | 0x7040:21, 1  | 
1640:0A  | SubIndex 010  | 10. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x22 (DMC__PositioningControl__Emergency stop))  | UINT32  | RO  | 0x7040:22, 1  | 
1640:0B  | SubIndex 011  | 11. PDO Mapping entry (14 bits align)  | UINT32  | RO  | 0x0000:00, 14  | 
1640:0C  | SubIndex 012  | 12. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x31 (DMC__Set counter value))  | UINT32  | RO  | 0x7040:31, 64  | 
1640:0D  | SubIndex 013  | 13. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x32 (DMC__Target position))  | UINT32  | RO  | 0x7040:32, 64  | 
1640:0E  | SubIndex 014  | 14. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x33 (DMC__Target velocity))  | UINT32  | RO  | 0x7040:33, 16  | 
1640:0F  | SubIndex 015  | 15. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x34 (DMC__Start type))  | UINT32  | RO  | 0x7040:34, 16  | 
1640:10  | SubIndex 016  | 16. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x35 (DMC__Target acceleration))  | UINT32  | RO  | 0x7040:35, 16  | 
1640:11  | SubIndex 017  | 17. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x36 (DMC__Target deceleration))  | UINT32  | RO  | 0x7040:36, 16  | 
1640:12  | SubIndex 018  | 18. PDO Mapping entry (80 bits align)  | UINT32  | RO  | 0x0000:00, 80  | 
Index 1641 DMC RxPDO-Map Outputs 32 Bit
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1641:0  | DMC RxPDO-Map Outputs 32 Bit  | PDO Mapping RxPDO 66  | UINT8  | RO  | 0x14 (20dec)  | 
1641:01  | SubIndex 001  | 1. PDO Mapping entry (1 bit align)  | UINT32  | RO  | 0x0000:00, 1  | 
1641:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x02 (DMC__FeedbackControl__Enable latch extern on positive edge))  | UINT32  | RO  | 0x7040:02, 1  | 
1641:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x03 (DMC__FeedbackControl__Set counter))  | UINT32  | RO  | 0x7040:03, 1  | 
1641:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x04 (DMC__FeedbackControl__Enable latch extern on negative edge))  | UINT32  | RO  | 0x7040:04, 1  | 
1641:05  | SubIndex 005  | 5. PDO Mapping entry (12 bits align)  | UINT32  | RO  | 0x0000:00, 12  | 
1641:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x11 (DMC__DriveControl__Enable))  | UINT32  | RO  | 0x7040:11, 1  | 
1641:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x12 (DMC__DriveControl__Reset))  | UINT32  | RO  | 0x7040:12, 1  | 
1641:08  | SubIndex 008  | 8. PDO Mapping entry (14 bits align)  | UINT32  | RO  | 0x0000:00, 14  | 
1641:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x21 (DMC__PositioningControl__Execute))  | UINT32  | RO  | 0x7040:21, 1  | 
1641:0A  | SubIndex 010  | 10. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x22 (DMC__PositioningControl__Emergency stop))  | UINT32  | RO  | 0x7040:22, 1  | 
1641:0B  | SubIndex 011  | 11. PDO Mapping entry (14 bits align)  | UINT32  | RO  | 0x0000:00, 14  | 
1641:0C  | SubIndex 012  | 12. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x31 (DMC__Set counter value))  | UINT32  | RO  | 0x7040:31, 32  | 
1641:0D  | SubIndex 013  | 13. PDO Mapping entry (32 bits align)  | UINT32  | RO  | 0x0000:00, 32  | 
1641:0E  | SubIndex 014  | 14. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x32 (DMC__Target position))  | UINT32  | RO  | 0x7040:32, 32  | 
1641:0F  | SubIndex 015  | 15. PDO Mapping entry (32 bits align)  | UINT32  | RO  | 0x0000:00, 32  | 
1641:10  | SubIndex 016  | 16. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x33 (DMC__Target velocity))  | UINT32  | RO  | 0x7040:33, 16  | 
1641:11  | SubIndex 017  | 17. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x34 (DMC__Start type))  | UINT32  | RO  | 0x7040:34, 16  | 
1641:12  | SubIndex 018  | 18. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x35 (DMC__Target acceleration))  | UINT32  | RO  | 0x7040:35, 16  | 
1641:13  | SubIndex 019  | 19. PDO Mapping entry (object 0x7040 (DMC Outputs), entry 0x36 (DMC__Target deceleration))  | UINT32  | RO  | 0x7040:36, 16  | 
1641:14  | SubIndex 020  | 20. PDO Mapping entry (80 bits align)  | UINT32  | RO  | 0x0000:00, 80  | 
Index 1A00 FB TxPDO-Map Position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A00:0  | FB TxPDO-Map Position  | PDO Mapping TxPDO 1  | UINT8  | RO  | 0x01 (1dec)  | 
1A00:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6000 (FB Inputs), entry 0x11 (Position))  | UINT32  | RO  | 0x6000:11, 32  | 
Index 1A01 DRV TxPDO-Map Statusword
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A01:0  | DRV TxPDO-Map Statusword  | PDO Mapping TxPDO 2  | UINT8  | RO  | 0x01 (1dec)  | 
1A01:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x01 (Statusword))  | UINT32  | RO  | 0x6010:01, 16  | 
Index 1A02 DRV TxPDO-Map Velocity actual value
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A02:0  | DRV TxPDO-Map Velocity actual value  | PDO Mapping TxPDO 3  | UINT8  | RO  | 0x01 (1dec)  | 
1A02:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x07 (Velocity actual value))  | UINT32  | RO  | 0x6010:07, 32  | 
Index 1A03 DRV TxPDO-Map Torque actual value
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A03:0  | DRV TxPDO-Map Torque actual value  | PDO Mapping TxPDO 4  | UINT8  | RO  | 0x01 (1dec)  | 
1A03:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x08 (Torque actual value))  | UINT32  | RO  | 0x6010:08, 16  | 
Index 1A04 DRV TxPDO-Map Info data 1
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A04:0  | DRV TxPDO-Map Info data 1  | PDO Mapping TxPDO 5  | UINT8  | RO  | 0x01 (1dec)  | 
1A04:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x12 (Info data 1))  | UINT32  | RO  | 0x6010:12, 16  | 
Index 1A05 DRV TxPDO-Map Info data 2
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A05:0  | DRV TxPDO-Map Info data 2  | PDO Mapping TxPDO 6  | UINT8  | RO  | 0x01 (1dec)  | 
1A05:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x13 (Info data 2))  | UINT32  | RO  | 0x6010:13, 16  | 
Index 1A06 DRV TxPDO-Map Following error actual value
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A06:0  | DRV TxPDO-Map Following error actual value  | PDO Mapping TxPDO 7  | UINT8  | RO  | 0x01 (1dec)  | 
1A06:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x06 (Following error actual value))  | UINT32  | RO  | 0x6010:06, 32  | 
Index 1A07 FB TxPDO-Map Touch probe status
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A07:0  | FB TxPDO-Map Touch probe status  | PDO Mapping TxPDO 8  | UINT8  | RO  | 0x0A (10dec)  | 
1A07:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x01 (TP1 Enable))  | UINT32  | RO  | 0x6001:01, 1  | 
1A07:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x02 (TP1 pos. value stored))  | UINT32  | RO  | 0x6001:02, 1  | 
1A07:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x03 (TP1 Neg. value stored))  | UINT32  | RO  | 0x6001:03, 1  | 
1A07:04  | SubIndex 004  | 4. PDO Mapping entry (4 bits align)  | UINT32  | RO  | 0x0000:00, 4  | 
1A07:05  | SubIndex 005  | 5. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x08 (TP1 Input))  | UINT32  | RO  | 0x6001:08, 1  | 
1A07:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x09 (TP2 Enable))  | UINT32  | RO  | 0x6001:09, 1  | 
1A07:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x0A (TP2 pos value stored))  | UINT32  | RO  | 0x6001:0A, 1  | 
1A07:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x0B (TP2 neg value stored))  | UINT32  | RO  | 0x6001:0B, 1  | 
1A07:09  | SubIndex 009  | 9. PDO Mapping entry (4 bits align)  | UINT32  | RO  | 0x0000:00, 4  | 
1A07:0A  | SubIndex 009  | 8. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x10 (TP2 Input))  | UINT32  | RO  | 0x6001:10, 1  | 
Index 1A08 FB TxPDO-Map Touch probe 1 pos position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A08:0  | FB TxPDO-Map Touch probe 1 pos position  | PDO Mapping TxPDO 9  | UINT8  | RO  | 0x01 (1dec)  | 
1A08:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6001 (FP Touch probe inputs), entry 0x11 (TP1 Pos position))  | UINT32  | RO  | 0x6001:11, 32  | 
Index 1A09 FB TxPDO-Map Touch probe 1 neg position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A09:0  | FB TxPDO-Map Touch probe 1 neg position  | PDO Mapping TxPDO 10  | UINT8  | RO  | 0x01 (1dec)  | 
1A09:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x12 (TP1 Neg position))  | UINT32  | RO  | 0x6001:12, 32  | 
Index 1A0A FB TxPDO-Map Touch probe 2 pos position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A0A:0  | FB TxPDO-Map Touch probe 2 pos position  | PDO Mapping TxPDO 11  | UINT8  | RO  | 0x01 (1dec)  | 
1A0A:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x13 (TP2 Pos position))  | UINT32  | RO  | 0x6001:13, 32  | 
Index 1A0B FB TxPDO-Map Touch probe 2 neg position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A0B:0  | FB TxPDO-Map Touch probe 2 neg position  | PDO Mapping TxPDO 12  | UINT8  | RO  | 0x01 (1dec)  | 
1A0B:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6001 (FB Touch probe inputs), entry 0x14 (TP2 neg position))  | UINT32  | RO  | 0x6001:14, 32  | 
Index 1A0D DRV TxPDO-Map Info data 3
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A0D:0  | DRV TxPDO-Map Info data 3  | PDO Mapping TxPDO 13  | UINT8  | RO  | 0x01 (1dec)  | 
1A0D:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6010 (DRV Inputs), entry 0x14 (Info data 3))  | UINT32  | RO  | 0x6010:14, 16  | 
Index 1A0E FB TxPDO-Map Enc Position
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A0E:0  | FB TxPDO-Map Enc Position  | PDO Mapping TxPDO 14  | UINT8  | RO  | 0x01 (1dec)  | 
1A0E:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6000 (FB Inputs), entry 0x12 (Enc Position))  | UINT32  | RO  | 0x6000:12, 32  | 
Index 1A10 DI TxPDO-Map Inputs
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A10:0  | DI TxPDO-Map Inputs  | PDO Mapping TxPDO 13  | UINT8  | RO  | 0x0D (13dec)  | 
1A10:01  | SubIndex 001  | 1. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x01 (Input 1))  | UINT32  | RO  | 0x6020:01, 1  | 
1A10:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x02 (Input 2))  | UINT32  | RO  | 0x6020:02, 1  | 
1A10:03  | SubIndex 003  | 3. PDO Mapping entry (2 bits align)  | UINT32  | RO  | 0x0000:00, 2  | 
1A10:04  | SubIndex 004  | 4. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x05 (Encoder A))  | UINT32  | RO  | 0x6020:05, 1  | 
1A10:05  | SubIndex 005  | 5. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x06 (Encoder B))  | UINT32  | RO  | 0x6020:06, 1  | 
1A10:06  | SubIndex 006  | 6. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x06 (Encoder C))  | UINT32  | RO  | 0x6020:07, 1  | 
1A10:07  | SubIndex 007  | 7. PDO Mapping entry (1 bits align)  | UINT32  | RO  | 0x0000:00, 1  | 
1A10:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x09 (Hall A))  | UINT32  | RO  | 0x6020:09, 1  | 
1A10:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x0A (Hall B))  | UINT32  | RO  | 0x6020:0A, 1  | 
1A10:0A  | SubIndex 010  | 10. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x0B (Hall C))  | UINT32  | RO  | 0x6020:0B, 1  | 
1A10:0B  | SubIndex 011  | 11. PDO Mapping entry (1 bits align)  | UINT32  | RO  | 0x0000:00, 1  | 
1A10:0C  | SubIndex 012  | 12. PDO Mapping entry (object 0x6020 (DI Inputs), entry 0x0D (Level of ENA input))  | UINT32  | RO  | 0x6020:0D, 1  | 
1A10:0D  | SubIndex 013  | 13. PDO Mapping entry (3 bits align)  | UINT32  | RO  | 0x0000:00, 3  | 
Index 1A40 DMC TxPDO-Map Inputs
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A40:0  | DMC TxPDO-Map Inputs  | PDO Mapping TxPDO 65  | UINT8  | RO  | 0x26 (38dec)  | 
1A40:01  | SubIndex 001  | 1. PDO Mapping entry (1 bit align)  | UINT32  | RO  | 0x0000:00, 1  | 
1A40:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x02 (DMC__FeedbackStatus__Latch extern valid))  | UINT32  | RO  | 0x6040:02, 1  | 
1A40:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x03 (DMC__FeedbackStatus__Set counter done))  | UINT32  | RO  | 0x6040:03, 1  | 
1A40:04  | SubIndex 004  | 4. PDO Mapping entry (9 bits align)  | UINT32  | RO  | 0x0000:00, 9  | 
1A40:05  | SubIndex 005  | 5. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x0D (DMC__FeedbackStatus__Status of extern latch))  | UINT32  | RO  | 0x6040:0D, 1  | 
1A40:06  | SubIndex 006  | 6. PDO Mapping entry (3 bits align)  | UINT32  | RO  | 0x0000:00, 3  | 
1A40:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x11 (DMC__DriveStatus__Ready to enable))  | UINT32  | RO  | 0x6040:11, 1  | 
1A40:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x12 (DMC__DriveStatus__Ready))  | UINT32  | RO  | 0x6040:12, 1  | 
1A40:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x13 (DMC__DriveStatus__Warning))  | UINT32  | RO  | 0x6040:13, 1  | 
1A40:0A  | SubIndex 010  | 10. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x14 (DMC__DriveStatus__Error))  | UINT32  | RO  | 0x6040:14, 1  | 
1A40:0B  | SubIndex 011  | 11. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x15 (DMC__DriveStatus__Moving positive))  | UINT32  | RO  | 0x6040:15, 1  | 
1A40:0C  | SubIndex 012  | 12. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x16 (DMC__DriveStatus__Moving negative))  | UINT32  | RO  | 0x6040:16, 1  | 
1A40:0D  | SubIndex 013  | 13. PDO Mapping entry (5 bits align)  | UINT32  | RO  | 0x0000:00, 5  | 
1A40:0E  | SubIndex 014  | 14. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x1C (DMC__DriveStatus__Digital input 1))  | UINT32  | RO  | 0x6040:1C, 1  | 
1A40:0F  | SubIndex 015  | 15. PDO Mapping entry  | UINT32  | RO  | 0x6040:1D, 1  | 
1A40:10  | SubIndex 016  | 16. PDO Mapping entry (3 bits align)  | UINT32  | RO  | 0x0000:00, 3  | 
1A40:11  | SubIndex 017  | 17. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x21 (DMC__PositioningStatus__Busy))  | UINT32  | RO  | 0x6040:21, 1  | 
1A40:12  | SubIndex 018  | 18. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x22 (DMC__PositioningStatus__In-Target))  | UINT32  | RO  | 0x6040:22, 1  | 
1A40:13  | SubIndex 019  | 19. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x23 (DMC__PositioningStatus__Warning))  | UINT32  | RO  | 0x6040:23, 1  | 
1A40:14  | SubIndex 020  | 20. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x24 (DMC__PositioningStatus__Error))  | UINT32  | RO  | 0x6040:24, 1  | 
1A40:15  | SubIndex 021  | 21. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x25 (DMC__PositioningStatus__Calibrated))  | UINT32  | RO  | 0x6040:25, 1  | 
1A40:16  | SubIndex 022  | 22. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x26 (DMC__PositioningStatus__Accelerate))  | UINT32  | RO  | 0x6040:26, 1  | 
1A40:17  | SubIndex 023  | 23. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x27 (DMC__PositioningStatus__Decelerate))  | UINT32  | RO  | 0x6040:27, 1  | 
1A40:18  | SubIndex 024  | 24. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x28 (DMC__PositioningStatus__Ready to execute))  | UINT32  | RO  | 0x6040:28, 1  | 
1A40:19  | SubIndex 025  | 25. PDO Mapping entry (8 bits align)  | UINT32  | RO  | 0x0000:00, 8  | 
1A40:1A  | SubIndex 026  | 26. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x31 (DMC__Set position))  | UINT32  | RO  | 0x6040:31, 64  | 
1A40:1B  | SubIndex 027  | 27. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x32 (DMC__Set velocity))  | UINT32  | RO  | 0x6040:32, 16  | 
1A40:1C  | SubIndex 028  | 28. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x33 (DMC__Actual drive time))  | UINT32  | RO  | 0x6040:33, 32  | 
1A40:1D  | SubIndex 029  | 29. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x34 (DMC__Actual position lag))  | UINT32  | RO  | 0x6040:34, 64  | 
1A40:1E  | SubIndex 030  | 30. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x35 (DMC__Actual velocity))  | UINT32  | RO  | 0x6040:35, 16  | 
1A40:1F  | SubIndex 031  | 31. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x36 (DMC__Actual position))  | UINT32  | RO  | 0x6040:36, 64  | 
1A40:20  | SubIndex 032  | 32. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x37 (DMC__Error id))  | UINT32  | RO  | 0x6040:37, 32  | 
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A40:21  | SubIndex 033  | 33. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x38 (DMC__Input cycle counter))  | UINT32  | RO  | 0x6040:38, 8  | 
1A40:22  | SubIndex 034  | 34. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x39 (DMC__Channel id))  | UINT32  | RO  | 0x6040:39, 8  | 
1A40:23  | SubIndex 035  | 35. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x3A (DMC__Latch value))  | UINT32  | RO  | 0x6040:3A, 64  | 
1A40:24  | SubIndex 036  | 36. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x3B (DMC__Cyclic info data 1))  | UINT32  | RO  | 0x6040:3B, 16  | 
1A40:25  | SubIndex 037  | 37. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x3C (DMC__Cyclic info data 2))  | UINT32  | RO  | 0x6040:3C, 16  | 
1A40:26  | SubIndex 038  | 38. PDO Mapping entry (64 bits align)  | UINT32  | RO  | 0x0000:00, 64  | 
Index 1A41 DMC TxPDO-Map Inputs 32 Bit
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | |
|---|---|---|---|---|---|---|
1A41:0  | DMC TxPDO-Map Inputs 32 Bit  | PDO Mapping TxPDO 66  | UINT8  | RO  | 0x2A (42dec)  | |
1A41:01  | SubIndex 001  | 1. PDO Mapping entry (1 bit align)  | UINT32  | RO  | 0x0000:00, 1  | |
1A41:02  | SubIndex 002  | 2. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x02 (DMC__FeedbackStatus__Latch extern valid))  | UINT32  | RO  | 0x6040:02, 1  | |
1A41:03  | SubIndex 003  | 3. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x03 (DMC__FeedbackStatus__Set counter done))  | UINT32  | RO  | 0x6040:03, 1  | |
1A41:04  | SubIndex 004  | 4. PDO Mapping entry (9 bits align)  | UINT32  | RO  | 0x0000:00, 9  | |
1A41:05  | SubIndex 005  | 5. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x0D (DMC__FeedbackStatus__Status of extern latch))  | UINT32  | RO  | 0x6040:0D, 1  | |
1A41:06  | SubIndex 006  | 6. PDO Mapping entry (3 bits align)  | UINT32  | RO  | 0x0000:00, 3  | |
1A41:07  | SubIndex 007  | 7. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x11 (DMC__DriveStatus__Ready to enable))  | UINT32  | RO  | 0x6040:11, 1  | |
1A41:08  | SubIndex 008  | 8. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x12 (DMC__DriveStatus__Ready))  | UINT32  | RO  | 0x6040:12, 1  | |
1A41:09  | SubIndex 009  | 9. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x13 (DMC__DriveStatus__Warning))  | UINT32  | RO  | 0x6040:13, 1  | |
1A41:0A  | SubIndex 010  | 10. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x14 (DMC__DriveStatus__Error))  | UINT32  | RO  | 0x6040:14, 1  | |
1A41:0B  | SubIndex 011  | 11. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x15 (DMC__DriveStatus__Moving positive))  | UINT32  | RO  | 0x6040:15, 1  | |
1A41:0C  | SubIndex 012  | 12. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x16 (DMC__DriveStatus__Moving negative))  | UINT32  | RO  | 0x6040:16, 1  | |
1A41:0D  | SubIndex 013  | 13. PDO Mapping entry (5 bits align)  | UINT32  | RO  | 0x0000:00, 5  | |
1A41:0E  | SubIndex 014  | 14. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x1C (DMC__DriveStatus__Digital input 1))  | UINT32  | RO  | 0x6040:1C, 1  | |
1A41:0F  | SubIndex 015  | 15. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x1D (DMC__DriveStatus__Digital input 2))  | UINT32  | RO  | 0x6040:1D, 1  | |
1A41:10  | SubIndex 016  | 16. PDO Mapping entry (3 bits align)  | UINT32  | RO  | 0x0000:00, 3  | |
1A41:11  | SubIndex 017  | 17. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x21 (DMC__PositioningStatus__Busy))  | UINT32  | RO  | 0x6040:21, 1  | |
1A41:12  | SubIndex 018  | 18. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x22 (DMC__PositioningStatus__In-Target))  | UINT32  | RO  | 0x6040:22, 1  | |
1A41:13  | SubIndex 019  | 19. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x23 (DMC__PositioningStatus__Warning))  | UINT32  | RO  | 0x6040:23, 1  | |
1A41:14  | SubIndex 020  | 20. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x24 (DMC__PositioningStatus__Error))  | UINT32  | RO  | 0x6040:24, 1  | |
1A41:15  | SubIndex 021  | 21. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x25 (DMC__PositioningStatus__Calibrated))  | UINT32  | RO  | 0x6040:25, 1  | |
1A41:16  | SubIndex 022  | 22. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x26 (DMC__PositioningStatus__Accelerate))  | UINT32  | RO  | 0x6040:26, 1  | |
1A41:17  | SubIndex 023  | 23. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x27 (DMC__PositioningStatus__Decelerate))  | UINT32  | RO  | 0x6040:27, 1  | |
1A41:18  | SubIndex 024  | 24. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x28 (DMC__PositioningStatus__Ready to execute))  | UINT32  | RO  | 0x6040:28, 1  | |
1A41:19  | SubIndex 025  | 25. PDO Mapping entry (8 bits align)  | UINT32  | RO  | 0x0000:00, 8  | |
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1A41:1A  | SubIndex 026  | 26. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x31 (DMC__Set position))  | UINT32  | RO  | 0x6040:31, 32  | 
1A41:1B  | SubIndex 027  | 27. PDO Mapping entry (32 bits align)  | UINT32  | RO  | 0x0000:00, 32  | 
1A41:1C  | SubIndex 028  | 28. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x32 (DMC__Set velocity))  | UINT32  | RO  | 0x6040:32, 16  | 
1A41:1D  | SubIndex 029  | 29. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x33 (DMC__Actual drive time))  | UINT32  | RO  | 0x6040:33, 32  | 
1A41:1E  | SubIndex 030  | 30. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x34 (DMC__Actual position lag))  | UINT32  | RO  | 0x6040:34, 32  | 
1A41:1F  | SubIndex 031  | 31. PDO Mapping entry (32 bits align)  | UINT32  | RO  | 0x0000:00, 32  | 
1A41:20  | SubIndex 032  | 32. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x35 (DMC__Actual velocity))  | UINT32  | RO  | 0x6040:35, 16  | 
1A41:21  | SubIndex 033  | 33. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x36 (DMC__Actual position))  | UINT32  | RO  | 0x6040:36, 32  | 
1A41:22  | SubIndex 034  | 34. PDO Mapping entry (32 bits align)  | UINT32  | RO  | 0x0000:00, 32  | 
1A41:23  | SubIndex 035  | 35. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x37 (DMC__Error id))  | UINT32  | RO  | 0x6040:37, 32  | 
1A41:24  | SubIndex 036  | 36. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x38 (DMC__Input cycle counter))  | UINT32  | RO  | 0x6040:38, 8  | 
1A41:25  | SubIndex 037  | 37. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x39 (DMC__Channel id))  | UINT32  | RO  | 0x6040:39, 8  | 
1A41:26  | SubIndex 038  | 38. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x3A (DMC__Latch value))  | UINT32  | RO  | 0x6040:3A, 32  | 
1A41:27  | SubIndex 039  | 39. PDO Mapping entry (32 bits align)  | UINT32  | RO  | 0x0000:00, 32  | 
1A41:28  | SubIndex 040  | 40. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x3B (DMC__Cyclic info data 1))  | UINT32  | RO  | 0x6040:3B, 16  | 
1A41:29  | SubIndex 041  | 41. PDO Mapping entry (object 0x6040 (DMC Inputs), entry 0x3C (DMC__Cyclic info data 2))  | UINT32  | RO  | 0x6040:3C, 16  | 
1A41:2A  | SubIndex 042  | 42. PDO Mapping entry (64 bits align)  | UINT32  | RO  | 0x0000:00, 64  | 
Index 1C00 Sync manager type
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C00:0  | Sync manager type  | Using the Sync Managers  | UINT8  | RO  | 0x04 (4dec)  | 
1C00:01  | SubIndex 001  | Sync-Manager Type Channel 1: Mailbox Write  | UINT8  | RO  | 0x01 (1dec)  | 
1C00:02  | SubIndex 002  | Sync-Manager Type Channel 2: Mailbox Read  | UINT8  | RO  | 0x02 (2dec)  | 
1C00:03  | SubIndex 003  | Sync-Manager Type Channel 3: Process Data Write (Outputs)  | UINT8  | RO  | 0x03 (3dec)  | 
1C00:04  | SubIndex 004  | Sync-Manager Type Channel 4: Process Data Read (Inputs)  | UINT8  | RO  | 0x04 (4dec)  | 
Index 1C12 RxPDO assign
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C12:0  | RxPDO assign  | PDO Assign Outputs  | UINT8  | RW  | 0x02 (2dec)  | 
1C12:01  | Subindex 001  | 1. allocated RxPDO (contains the index of the associated RxPDO mapping object)  | UINT16  | RW  | 0x1600 (5632dec)  | 
1C12:02  | Subindex 002  | 2. allocated RxPDO (contains the index of the associated RxPDO mapping object)  | UINT16  | RW  | 0x1606 (5638dec)  | 
Index 1C13 TxPDO assign
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C13:0  | TxPDO assign  | PDO Assign Inputs  | UINT8  | RW  | 0x03 (3dec)  | 
1C13:01  | Subindex 001  | 1. allocated TxPDO (contains the index of the associated TxPDO mapping object)  | UINT16  | RW  | 0x1A00 (6656dec)  | 
1C13:02  | Subindex 002  | 2. allocated TxPDO (contains the index of the associated TxPDO mapping object)  | UINT16  | RW  | 0x1A01 (6657dec)  | 
1C13:03  | Subindex 003  | 3. allocated TxPDO (contains the index of the associated TxPDO mapping object)  | UINT16  | RW  | 0x1A06 (6662dec)  | 
Index 1C32 SM output parameter
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C32:0  | SM output parameter  | Synchronization parameters for the outputs  | UINT8  | RO  | 0x20 (32dec)  | 
1C32:01  | Sync mode  | Current synchronization mode: 
  | UINT16  | RW  | 0x0000 (0dec)  | 
1C32:02  | Cycle time  | Cycle time (in ns): 
  | UINT32  | RW  | 0x00000000 (0dec)  | 
1C32:03  | Shift time  | Time between SYNC0 event and output of the outputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C32:04  | Sync modes supported  | Supported synchronization modes: 
  | UINT16  | RO  | 0x0000 (0dec)  | 
1C32:05  | Minimum cycle time  | Minimum cycle time (in ns)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C32:06  | Calc and copy time  | Minimum time between SYNC0 and SYNC1 event (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C32:07  | Minimum delay time  | Minimum time between SYNC1 event and output of the outputs (in ns)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C32:08  | Command  | 
 The entries 0x1C32:03, 0x1C32:05, 0x1C32:06, 0x1C32:09, 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values.  | UINT16  | RW  | 0x0000 (0dec)  | 
1C32:09  | Maximum delay time  | Time between SYNC1 event and output of the outputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C32:0B  | SM event missed counter  | Number of missed SM events in OPERATIONAL (DC mode only)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C32:0C  | Cycle exceeded counter  | Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C32:0D  | Shift too short counter  | Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C32:20  | Sync error  | The synchronization was not correct in the last cycle (outputs were output too late; DC mode only)  | BOOLEAN  | RO  | 0x00 (0dec)  | 
Index 1C33 SM input parameter
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
1C33:0  | SM input parameter  | Synchronization parameters for the inputs  | UINT8  | RO  | 0x20 (32dec)  | 
1C33:01  | Sync mode  | Current synchronization mode: 
  | UINT16  | RW  | 0x0000 (0dec)  | 
1C33:02  | Cycle time  | Cycle time (in ns): 
 DC-Mode: SYNC0/SYNC1 Cycle Time  | UINT32  | RW  | 0x00000000 (0dec)  | 
1C33:03  | Shift time  | Time between SYNC0 event and reading of the inputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:04  | Sync modes supported  | Supported synchronization modes: 
  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:05  | Minimum cycle time  | Minimum cycle time (in ns)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:06  | Calc and copy time  | Time between reading of the inputs and availability of the inputs for the master (in ns, only DC mode)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:07  | Minimum delay time  | Min. time between SYNC1 event and the reading of the inputs (in ns, DC mode only)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:08  | Command  | 
 The entries 0x1C32:03, 0x1C32:05, 0x1C32:06, 0x1C32:09, 0x1C33:03, 0x1C33:06, 0x1C33:09 are updated with the maximum measured values.  | UINT16  | RW  | 0x0000 (0dec)  | 
1C33:09  | Maximum delay time  | Time between SYNC1 event and reading of the inputs (in ns, only DC mode)  | UINT32  | RO  | 0x00000000 (0dec)  | 
1C33:0B  | SM event missed counter  | Number of missed SM events in OPERATIONAL (DC mode only)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:0C  | Cycle exceeded counter  | Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:0D  | Shift too short counter  | Number of occasions that the interval between SYNC0 and SYNC1 event was too short (DC mode only)  | UINT16  | RO  | 0x0000 (0dec)  | 
1C33:20  | Sync error  | The synchronization was not correct in the last cycle (outputs were output too late; DC mode only)  | BOOLEAN  | RO  | 0x00 (0dec)  | 
Index F000 Modular device profile
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
000F:0  | Modular device profile  | General information for the modular device profile  | UINT8  | RO  | 0x02 (2dec)  | 
000F:01  | Module index distance  | Index distance of the objects of the individual channels  | UINT16  | RO  | 0x0010 (16dec)  | 
000F:02  | Maximum number of modules  | Number of channels  | UINT16  | RO  | 0x0005 (5dec)  | 
Index F008 Code word
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
F008:0  | Code word  | reserved  | UINT32  | RW  | 0x00000000 (0dec)  | 
Index F010 Module list
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
010F:0  | Module list  | Maximum subindex  | UINT8  | RW  | 0x04 (4dec)  | 
010F:01  | SubIndex 001  | Encoder profile number DS402 / MDP 513  | UINT32  | RW  | 0x00000201 (513dec)  | 
010F:02  | SubIndex 002  | Encoder profile number DS402 / MDP 742  | UINT32  | RW  | 0x000002E6 (742dec)  | 
010F:03  | SubIndex 003  | Reserved  | UINT32  | RW  | 0x00000064 (100dec)  | 
010F:04  | SubIndex 004  | Reserved  | UINT32  | RW  | 0x00000000 (0dec)  | 
010F:05  | SubIndex 005  | Profile number drive motion control  | UINT32  | RW  | 0x000002EE (750dec)  | 
Index F081 Download revision
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
081F:0  | Download revision  | Download revision  | UINT8  | RO  | 0x01 (1dec)  | 
081F:01  | Revision number  | Revision number of the module Relevant as a startup list entry for compatibility  | UINT32  | RW  | 0x0000000 (0dec)  | 
Index F083 BTN
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
083F:0  | Download revision  | Beckhoff Traceability Number  | STRING  | RO  | 
  |