Lock counter value

The “Latch” and “Gate” inputs each combine gate and latch functions in a single input and are therefore referred to below as gate/latch combination inputs.

The gate function enables locking of the counter “Counter value” (0x60n0:11).
The counter is locked at the first pulse at the gate/latch combination input. Subsequent pulses have no influence on the counter value. This allows a timeframe to be defined in which counting signals are acquired. The gate function can be triggered by:

The gate/latch combination input may be used as a second latch input “Latch extern 2”.

Lock counter value via a positive/negative edge at the gate/latch combination input (Enable pos./neg. gate)

Lock counter value 1:

Activation of gate and latch functions via the same edge at the gate/latch combination input in 2-channel mode 2xAB

When the gate function and a latch function is activated via the same edge at the gate/latch combination input, the latch function is always executed first, after which the counter value is locked via the gate function.

Example:

Index 0x80n0:04 “Gate polarity” (1 = “Enable pos. gate”) and

Index 0x80n0:02 “Enable extern reset” = 1 with 0x80n0:10 “Extern reset polarity” = 1 (reset on a positive edge at the gate/latch combination input)

With a positive edge at the gate/latch combination input the current counter value is first set to zero (reset). After that, the counter value is locked.

The same applies to the use of index 0x80n0:04 “Gate polarity” (2 = “Enable neg. gate”) and the simultaneous activation of index 0x80n0:02 “Enable extern reset” with 0x80n0:10 “Extern reset polarity” = 0 (reset on a negative edge at the gate/latch combination input).

Lock counter value via a PLC variable (Set software gate)

The counter value can be locked from the PLC application.