Save counter value

The latch function enables the current counter value to be stored in separate process data, independent of the cycle time. The latch function can be triggered as follows:

Index 0x80n0:22 “Enable continuous latch extern” can be used to parameterize whether the function is executed at every parameterized external edge at the latch input or only once after every activation.

Save counter value 1:

Multiple activation of the latch function

If several commands are activated simultaneously to save the counter value in the “Latch value” process data (0x60n0:12), only the command that is set first is accepted by the terminal.

  • The counter value is stored in the process data “Latch value” (0x60n0:12) at the next occurring event and confirmed with the corresponding bit.
  • All other activated events are ignored.
  • The counter value storage cannot be reactivated until all activated commands for latching the value have been deactivated. This also applies if they were activated after confirmation by the occurring event.

Save the counter value via a positive/negative edge at the latch input (Enable latch extern on positive/negative edge)

Save counter value 2:

Activation of gate and latch functions via the same edge at the gate/latch combination input in 2-channel mode 2xAB

When the gate function and a latch function is activated via the same edge at the gate/latch combination input, the latch function is always executed first, after which the counter value is locked via the gate function.

Example:

Index 0x80n0:04 “Gate polarity” (1 = “Enable pos. gate”) and

Output process data “Enable latch extern on positive edge” (0x70n0:02) = 1

When a positive edge is detected at the gate/latch combination input, the current counter value is first stored in the input process data “Latch value” (0x60n0:12). After that, the counter value is locked.

The same applies to the use of the index 0x80n0:04 “Gate polarity” (2 = “Enable neg. gate”) and the simultaneous activation of the output process data “Enable latch extern on negative edge” (0x70n0:04).