Gate/Latch combination input
In 2-channel mode 2xAB, there is one external gate/latch combination input available for each channel, designed for 24 V DC signals with a minimum pulse duration of tON > 1 µs. This can be used as follows:
- Set counter value: set the counter value to a specified value using a positive or negative edge (output process data “Set counter on latch extern on positive/negative edge”)
- Reset counter value: reset the counter value to the value set in index 0x80n1:1B “Reset counter value” (default setting: zero) (index 0x80n0:02 “Enable extern reset”)
- Save counter value: save the counter value in separate process data via a positive or negative edge (output process data “Enable latch extern on positive/negative edge”)
- Lock counter value: lock the counter value via a positive or negative edge (index 0x80n0:04 “Gate polarity” = “Enable pos./neg. gate”)
![]() | Simultaneous use of gate and latch in 2-channel mode 2xAB When using the index 0x80n0:04 “Gate polarity” (1 = “Enable pos. gate”) and simultaneously activating the bit in the output process data “Enable latch extern on positive edge” (0x70n0:02), a positive edge at the gate/latch combination input causes the current counter value to be initially stored in the input process data “Latch value” (0x60n0:12). After that, the counter value is locked. The same applies to the use of index 0x80n0:04 “Gate polarity” (2 = “Enable neg. gate”) and the simultaneous activation of the bit in the output process data “Enable latch extern on negative edge” (0x70n0:04) upon a negative edge at the gate input/latch combination input. |
Setting the counter value via the gate/latch combination input (Set counter on latch extern on positive/negative edge)
The counter value can be set to a preset value during runtime via the process data by the positive or negative edge at the gate/latch combination input.
- Setting the counter value via the output process data “Set counter value” (0x70n0:11)
- Activation of the counter value setting via
- the positive edge at the external gate/latch combination input:
output process data “Set counter on latch extern on positive edge” (0x70n0:0A) - the negative edge at the external gate/latch combination input:
output process data “Set counter on latch extern on negative edge” (0x70n0:0B) - If the bit (TRUE) is set in the output process data “Set counter on latch extern on positive/negative edge” (0x70n0:0A/0B), the next positive or negative edge at the gate input/latch combination input sets the counter value in the input process data “Counter value” to the specified counter value in the output process data “Set counter value”.
- To confirm, the bit in the input process data “Set counter done” (0x60n0:03) is set to TRUE.
- The counter value setting can only be reactivated once the bit in the output process data “Set counter on latch extern on positive/negative edge” (0x70n0:0A/0B) has been set to FALSE.
Reset counter value via gate/latch combination input (Enable extern reset)
The counter value can be set to zero via the external gate/latch combination input.
- Presetting of the reset value via index 0x80n1:1B “Reset counter value”, (Default: 0)
- To activate this function set the bit in index 0x80n0:02 “Enable extern reset”.
- Index 0x80n0:10 “Extern reset polarity” can be used to specify at which edge the gate/latch combination input is active.
- 0: “Fall” - the counter is set to zero with a falling edge
- 1: “Rise” - the counter is set to zero with a rising edge
There is no status message via the process data.
Saving the counter value via a positive/negative edge at the gate/latch combination input (Enable latch extern on positive/negative edge)
- Save the counter value at the external gate/latch combination input via:
- Output process data “Enable latch extern on positive edge” (0x70n0:02) = TRUE
At the first external latch pulse with positive edge, the current counter value is stored in the input process data “Latch value” 0x60n0:12. - Output process data “Enable latch extern on negative edge” (0x70n0:04) = TRUE
At the first external latch pulse with negative edge the current counter value is stored in the input process data “Latch value” (0x60n0:12). - Simultaneous activation of the output process data “Enable latch extern on positive/negative edge” (0x70n0:02/04)
The current counter value is saved in the input process data “Latch value” (0x60n0:12) with the first external latch pulse, regardless of the polarity of the edge. - Specification whether it is necessary to reactivate the command to save the counter value via:
- “Enable continuous latch extern” Index 0x80n0:22 = FALSE
The following pulses at the gate/latch combination input have no effect on the latch value in the process data “Latch value” (0x60n0:12) when the bit in the output process data “Enable latch extern on positive edge” (0x70n0:02) or “Enable latch extern on negative edge” (0x70n0:04) is set.
Only when the bit in the input process data “Latch extern valid” (0x60n0:02) is FALSE can a new counter value be written to the gate/latch combination input in the process data “Latch value” (0x60n0:12). - “Enable continuous latch extern” Index 0x80n0:22 = TRUE
The counter value is written to process data “Latch value” (0x60n0:12) at every parameterized edge at the gate/latch combination input.
Reactivating the output process data “Enable latch extern on positive edge” (0x70n0:02) or “Enable latch extern on negative edge” (0x70n0:04) is no longer necessary. - Saving of the count value in the process data “Latch value” (0x60n0:12) is confirmed by the bit in the process data “Latch extern valid” (0x60n0:02).
- The status of the gate/latch combination input can be recorded using the input process data “Status of input gate” (0x60n0:0C).
Lock counter value via a positive/negative edge at the gate/latch combination input (Enable pos./neg. gate)
- The level at the gate/latch combination input at which the counter value is locked during runtime can be specified via index 0x80n0:04 “Gate polarity”.
- 0: Disable gate
The gate/latch combination input is disabled to lock the counter. It can still be used as external latch input for storage. - 1: Enable pos. gate
The counter value is locked with HIGH level at the gate/latch combination input. - 2: Enable neg. gate
The counter value is locked with LOW level at the gate/latch combination input - The current level at the gate/latch combination input is displayed via the input process data “Status of input gate” (0x60n0:0C).