Encoder operating voltage (supply voltage)
The encoder supply is generated internally from the 24 V of the power contacts. The encoder supply can be set in index 0x8001:17 “Supply voltage”. An operating voltage of 5 V DC is preset. Voltage values of 5 V DC, 12 V DC, and 24 V DC can be selected. The setting applies to both channels. Before switching to higher voltages, ensure that both encoders support the voltage range.
The following tolerances apply:
Voltage range | Tolerance |
|---|---|
5 V DC | +/-5% (4.75 V…5.25 V) |
12 V DC | +/-10% (10.8 V…13.2 V) |
24 V DC | -15% to +20% (20.4 V…28.8 V) |
![]() | Setting the encoder supply via index 0x8001:17 The encoder supply is set centrally for both channels via the index 0x8001:17 (channel 1). The corresponding index 0x8011:17 of the second channel has no parameterization function. |
Notice | |
Setting the encoder supply voltage
|