0x10F3, 0x10F8, 0xF915 | Information and diagnostic data (device-specific)

Index 10F3 Diagnosis History

Index (hex)

Name

Meaning

Data type

Flags

Default

10F3:0

Diagnosis History

Maximum subindex

UINT8

RO

0x15 (21dec)

10F3:01

Maximum Messages

Maximum number of stored messages
A maximum of 16 messages can be stored.

UINT8

RO

0x00 (0dec)

10F3:02

Newest Messages

Subindex of the latest message

UINT8

RO

0x00 (0dec)

10F3:03

Newest Acknowledged Messages

Subindex of the last confirmed message

UINT8

RW

0x00 (0dec)

10F3:04

New Messages Available

Indicates that a new message is available

BOOLEAN

RO

0x00 (0dec)

10F3:05

Flags

not used

UINT16

RW

0x0000 (0dec)

10F3:06

Diagnosis Message 001

Message 1

OCTET-STRING[20]

RO

{0}

…

…

…

…

…

…

10F3:15

Diagnosis Message 016

Message 16

OCTET-STRING[20]

RO

{0}

Index 10F8 Timestamp Object

Index (hex)

Name

Meaning

Data type

Flags

Default

10F8:0

Timestamp Object

Timestamp

UINT64

RO

 

Index F915 LED Status

Index (hex)

Name

Meaning

Data type

Flags

Default

F915:0

LED Status

Largest subindex of this object

UINT8

RO

0x10 (16dec)

F915:01

Run

See the LED description and the chapter “LED status via CoE 0xF915”

UINT32

RO

0x00000000 (0dec)

F915:02

Ch1 A

UINT32

RO

0x00000000 (0dec)

F915:03

Ch1 B

UINT32

RO

0x00000000 (0dec)

F915:04

Ch1 C / Ch2 A

UINT32

RO

0x00000000 (0dec)

F915:05

Ch1 DI / Ch2 B

UINT32

RO

0x00000000 (0dec)

F915:07

Latch

UINT32

RO

0x00000000 (0dec)

F915:09

Enc supply

UINT32

RO

0x00000000 (0dec)

F915:0A

Diag

UINT32

RO

0x00000000 (0dec)

F915:0F

Gate

UINT32

RO

0x00000000 (0dec)