EC/ED/EFxxxx wiring with push-in connection technology

WARNING

Risk of injury through electric shock and damage to the device!

Bring the bus terminal system into a safe, de-energized state before beginning to mount, disassemble, or wire the bus terminals!

EC/ED/EFxxxx wiring with push-in connection technology 1:
Fig.25: Connecting and disconnecting the conductors
1. Connecting solid conductors and conductors with ferrules (Fig. top left, step 2)
These can be connected using a direct plug-in technique, without tools.
  • Insert the conductor into the terminal point after stripping the insulation (2)
2. Connect stranded cables (Fig. top right, steps 1–3)
These must be connected via the push-button.

Disconnect cables (Fig. above steps 4–6)
The release is performed using the push-button for all conductor types.

Notice

EC/ED/EFxxxx wiring with push-in connection technology 2:

Observe the permissible connection cross-sections and stripping lengths

The permissible conductor cross-section and stripping length depend on the type of housing, please refer to the housing data in the “Technical data” chapter for the device in question.