Status PDO
The analog input channel has a status word (16 bits) in which real-time information is transported on a cycle-by-cycle basis.
Interpretation:
Underrange [Bool] | Overrange [Bool] | Limit 1/2 [2 bit] | Error (+ Error-LED) [Bool] | Steady state [Bool] | Tare Active [Bool] | Warning (+ Warning-LED) [Bool] | TxPDO State [Bool] | TxPDO Toggle [Bool] | Meaning |
|---|---|---|---|---|---|---|---|---|---|
SW.0 | SW.1 | SW.3/2 | SW.6 | SW.8 | SW.11 | SW.12 | SW.14 | SW.15 | |
1 |
|
| 1 |
|
|
|
|
| Measuring range undershot, see chapter Range error |
| 1 |
| 1 |
|
|
|
|
| Measuring range exceeded, see chapter Range Error |
|
|
|
|
|
| 1 |
|
| Measuring range above or below the specified warning thresholds |
|
| > 0 |
|
|
|
|
|
| See limit function |
|
|
|
| 1 |
|
|
|
| Measured value is stable within the specified time and value window |
|
|
|
|
|
|
| 1 |
| EtherCAT PDO transport failed |
|
|
|
|
|
|
|
| 0/1/0/1.. | Value changes with each new measured value that is placed on EtherCAT |
|
|
|
|
| 1 |
|
|
| Tare value has been calculated and is currently calculated internally, see Tare |
Sync Manager 3 – SM3 Inputs
0x1An0 – AI Standard (INT16) Channel m (4.0) | |
|---|---|
Contents | PDOs connected |
0x60n0:01 - Status_Underrange (0.1) | 0x1An1 |
0x1An1 – AI Compact (INT16) Channel m (2.0) | |
|---|---|
Contents | Excluded PDOs |
0x60n0:11 - Value (2.0) | 0x1An0 |
0x1An2 - AI Standard (Real32) Channel m (6.0) | |
|---|---|
Contents | Excluded PDOs |
0x60n0:01 - Status_Underrange (0.1) | 0x1An0 |
0x1An3 - AI Compact (Real32) Channel m (4.0) | |
|---|---|
Contents | Excluded PDOs |
0x60n0:11 - Value (Real32) (4.0) | 0x1An0 |
0x1An4 - AI Cycle Counter Channel m (2.0) | |
|---|---|
Contents | Excluded PDOs |
0x60n0:14 – Input Cycle Counter (2.0) | - |
0x1A60 – DEV Inputs Device (2.0) | |
|---|---|
Contents | Excluded PDOs |
0xF600:04 – Status_Diag (0.1) | - |