80nE, Fn16, F915 | Information and diagnostic data

Index 80nE SlotGroup x (output x, input x) PWM Internal data

Index (hex)

Name

Meaning

Data type

Flags

Default

80nE:0

SlotGroup x (output x, input x) PWM Internal data

Max. subindex

UINT8

RO

0x03 (3dec)

80nE:01

Timer Resolution

 

UINT16

RO

0x0000 (0dec)

80nE:02

Duty Cycle

 

UINT16

RO

0x0000 (0dec)

80nE:03

Prescaler

 

UINT16

RO

0x0000 (0dec)

Index F616 PWM Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

F616:0

PWM Inputs

 Largest subindex of this object

UINT8

RO

0x0F (15dec)

F616:06

PWM Warning

Indicates undervoltage in the external power supply or an excessive PCB temperature; see the chapter“Hardware error diagnostics”

BOOLEAN

RO

0x00 (0dec)

F616:07

PWM Error

Displays hardware errors; see the chapter“Hardware error diagnostics”, for example:

  • Overcurrent
  • Short circuit
  • Undervoltage
  • Overtemperature

BOOLEAN

RO

0x00 (0dec)

F616:0D

PWM Diag

 

BOOLEAN

RO

0x00 (0dec)

F616:0E

TxPDO State

Validity of the data of the associated TxPDO (0 = valid, 1 = invalid).

BOOLEAN

RO

0x00 (0dec)

F616:0F

Input Cycle Counter

2 bit counter for synchronization (incremented only if a new value is present)

BIT2

RO

0x00 (0dec)

Index F716 PWM outputs

Index (hex)

Name

Meaning

Data type

Flags

Default

F716:0

PWM Outputs

 Largest subindex of this object

UINT8

RO

0x11 (17dec)

F716:07

PWM Reset

 

BOOLEAN

RO

0x00 (0dec)

F716:11

PWM Output Cycle Counter

The 16 bit counter is not active until the process data value has been mapped and the counter has been enabled via index 0x80n0:0C “Enable Output Cycle Counter watchdog” (see the chapter“Watchdog behavior when the PLC is inactive”).

UINT16

RO

0x00 (0dec)

Index F816 PWM Vendor data

Index (hex)

Name

Meaning

Data type

Flags

Default

F816:0

PWM Vendor Data

Largest subindex of this object

UINT8

RO

0x15 (21dec)

F816:12

PCB Temperature Warning Level

Warning threshold for overtemperature (see the chapter “Hardware error diagnostics”)

UINT32

RW

0x00000000 (0dec)

F816:13

PCB Temperature Error Level

Error threshold for overtemperature (see the chapter “Hardware error diagnostics”)

UINT32

RW

0x00000000 (0dec)

F816:14

External Supply Voltage Warning Level

Warning threshold for insufficient or missing external supply voltage (see the chapter “Hardware error diagnostics”)

UINT32

RW

0x00000000 (0dec)

F816:15

External Supply Voltage Error Level

Error threshold for insufficient or missing external supply voltage (see the chapter “Hardware error diagnostics”)

UINT32

RW

0x00000000 (0dec)

Index F915 LED Status

Index (hex)

Name

Meaning

Data type

Flags

Default

F915:0

LED Status

 Largest subindex of this object

UINT8

RO

0x10 (16dec)

F915:01

Run

See the chapter “Reading the LED Status via CoE”

UINT32

RO

0x00000000 (0dec)

F915:02

Dev error

UINT32

RO

0x00000000 (0dec)

F915:04

Ch.1 output

UINT32

RO

0x00000000 (0dec)

F915:05

Ch.3 output

UINT32

RO

0x00000000 (0dec)

F915:07

Ch.1 DI

UINT32

RO

0x00000000 (0dec)

F915:08

Ch.3 DI

UINT32

RO

0x00000000 (0dec)

F915:09

Up 24 V

UINT32

RO

0x00000000 (0dec)

F915:0C

Ch.2 output

UINT32

RO

0x00000000 (0dec)

F915:0D

Ch.4 output

UINT32

RO

0x00000000 (0dec)

F915:0F

Ch.2 DI

UINT32

RO

0x00000000 (0dec)

F915:10

Ch.4 DI

UINT32

RO

0x00000000 (0dec)

Index FA16 PWM Diag data

Index (hex)

Name

Meaning

Data type

Flags

Default

FA16:0

PWM Diag Data

Largest subindex of this object

UINT8

RO

0x16 (22dec)

FA16:03

Up Supply Voltage Available

FALSE: No peripheral voltage (power contacts) present

TRUE: Peripheral voltage (power contacts) is present.

BOOLEAN

RW

0x00 (0dec)

FA16:12

PCB Temperature

Current PCB temperature reading

UINT32

RW

0x00000000 (0dec)

FA16:13

External Supply Voltage

Currently measured externally supplied voltage

UINT32

RW

0x00000000 (0dec)

FA16:16

Output Cycle Counter Error

32-bit error counter; see the chapter “Watchdog behavior when the PLC is inactive”

UINT32

RW

0x00000000 (0dec)