“HWE input (hardware enable)” | ModuleIdent 0x3009C8
This module allows you to enable or disable the PWM output via the digital input.
The status of the binary signal is output via the “HWE Inputs - Input” process data value. The HWE input module provides the following features:
- Definition of the enable level for the digital input (0x80n0:04 “Invert Digital Input”)
- Parameterizable input characteristics (0x80n0:11 “Input Type”)
- Parameterizable filter time (0x80n0:12 “Filter Time”)
Definition of the PWM output enable level
The PWM output of the respective channel can be enabled via the digital input “Hardware Enable”. Enable is triggered by a rising edge or a falling edge.
- By default, PWM output is enabled as long as the “Inputs” process data value is set to TRUE.
- The enable level can be inverted using the settings objects (0x80n0:04 “Invert Digital Input”)
0x80n0:04 “Invert Digital Input” | Status at the digital input, “HWE inputs – input” | Output of the PWM output signal |
|---|---|---|
FALSE (default) | 1 – TRUE | is enabled |
2 – FALSE | is disabled | |
TRUE | 3 – TRUE | is disabled |
4 – FALSE | is enabled |
Notice | |
“Hardware enable” input in case of bus error (watchdog) The “Hardware Enable” input does not lose its functionality in the event of a bus error (watchdog). If the PWM output has been validly enabled prior to the bus error, this enable status remains in effect even during the bus error. |
Parameterizable input characteristics
The digital input can be interpreted as having either a positive switching or ground switching characteristic. This is defined at 0x80n0:11 “Input Type” (n = 1 for DI 1, n = 3 for DI 2, n = 5 for DI 3, n = 7 for DI 4):
Standard digital | Positive switching | |
|---|---|
0x80n0:11 „Input Type“ | Positive Switching (PNP) |
Signal voltage “0” | -3…+1.5 V DC |
Signal voltage “1” | 2.7…28 V DC |
Standard digital | Ground switching | |
|---|---|
0x80n0:11 „Input Type“ | Ground Switching (NPN) |
Signal voltage “0” | 2.5…28 V DC |
Signal voltage “1” | -3…+1 V DC |
In this operation mode, an additional pull-up resistor is connected to V+. | |
![]() | Sensors with open collector output circuits A sensor with an open collector output circuit corresponds to the “Input Type”: “Ground Switching (NPN)”.
|
Parameterizable filter time
The digital input module provides a parameterizable filter time. This can be used to suppress interference, such as bouncing of a switch signal. Signals with a pulse duration shorter than the set filter time are suppressed.
Filter function sequence
- The filter is enabled on delivery, index 0x80n0:02 “Enable Filter” = TRUE
- The filter is parameterized via index 0x8n0:12 “Filter Time”. The minimum pulse duration depends on the set software filter (see following table).
Available filter times:
Index 0x80n0:12 “Filter Time” | Meaning |
|---|---|
500dec: 500 µs | Signals < 500 µs are suppressed |
750dec: 750 µs | Signals < 750 µs are suppressed |
1,000dec: 1 ms | Signals < 1 ms are suppressed |
3,000dec: 3 ms | Signals < 3 ms are suppressed (default) |
10,000dec: 10 ms | Signals < 10 ms are suppressed |
20,000dec: 20 ms | Signals < 20 ms are suppressed |
- The filter is disabled by setting index 0x80n0:02 “Enable Filter” = FALSE. In this case, the input signal is only filtered via the hardware. In this case, the filter value is typically 10 µs.