Technical data
Technical data | CU2508 |
|---|---|
Operating voltage | 24 (18...30) VDC, 250 mA, 3-pin connector (+, -, PE) |
Number of Ethernet ports | 8 x 100 Mbit/s (100BASE-TX) and 1 x 1 Gbit/s (1000BASE-T, Uplink) |
Ethernet interface | RJ 45 |
Cable length | up to 100 m, min. CAT5 twisted-pair, shielded |
Diagnosis | via LED, software |
Protocols | depends on used CU2508 driver |
TwinCAT support | TwinCAT from version 2.11R2 (build 2028) TwinCAT3 |
Electrical isolation | 1,500 V |
Weight | approx. 500 g |
permissible ambient temperature range during operation | -25°C ... + 55°C |
permissible ambient temperature range during storage | -40°C ... + 85°C |
permissible relative humidity | 95 %, no condensation |
Dimensions (W x H x D) | approx. 146 mm x 100 mm x 30 mm |
on 35 mm mounting rail conforms to EN 60715 | |
Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP20 |
Installation position | variable |
Approval | CE, EAC, UKCA |
*) Real applicable approvals/markings see type plate on the side (product marking).