Mounting power supply cable
Install the cable for the power supply of the control panel using the material supplied for connector assembly. It consists of a 5-pin connection strip and a strain relief housing with cable tie.
If you require a replacement for the voltage connector or the strain relief housing, you can order these from Beckhoff Sales using the following ordering option:
- C9900-P927: power supply connector for CP69xx or CP66xx Control Panel, 5-pin connector with strain relief for the external supply cable
Mounting power supply cable
First mount the plug on the cable as follows:
- 1. Remove a few centimeters of the cable sheath.
- 2. Remove the insulation from the wire ends (8-9 mm).
- 3. Crimp the ferrules onto the stripped wire ends.
- 4. Insert the cable ends with the ferrules into the 5-pin connection strip. For the pin assignment of the connector, see Chapter 3.2.1 Power supply.
- 5. Screw the cable ends into the 5-pin connection strip.
- You have mounted the plug on the cable.